background image

 

 

 
 
 

 

 
 
 
 

 

 

QUICK REFERENCE GUIDE 

ICX207D (v. 1.0) 

 

Summary of Contents for Dixell iChill ICX207D

Page 1: ...QUICK REFERENCE GUIDE ICX207D v 1 0 ...

Page 2: ...NECTIONS 8 5 1 PROBES CONNECTION 8 5 2 DIGITAL INPUT CONNECTION 10 5 3 ANALOG OUTPUT CONNECTION 10 6 LAN CONNECTION 15 6 1 CONNECTION DIAGRAM WITH IC206CX O IC208CX 16 6 2 CONNECTION DIAGRAM TO CONNECT IC205D OR IC207D 17 7 ELECTRICAL CONNECTIONS 17 8 MECHANICAL CHARACTERISTIC 18 9 TECHNICAL SPECIFICATIONS 19 9 1 SUPPLY VOLTAGE 19 9 2 ANALOGUE INPUTS 19 9 3 DIGITAL INPUT 19 9 4 ANALOGUE OUTPUTS 19...

Page 3: ... before any kind of maintenance The instrument must not be opened In case of failure or faulty operation send the instrument back to the distributor or to Dixell S r l See address with a detailed description of the fault Consider the maximum current which can be applied to each relay see Technical Data Ensure that the wires for probes loads and the power supply are separated and far enough from ea...

Page 4: ...ate the waste Public or private collection points must be used to dispose of the goods in accordance with local laws Furthermore at the end of the product s life it is also possible to return this to the retailer when a new purchase is made This equipment may contain hazardous substances Improper use or incorrect disposal can have adverse effects on human health and the environment The symbol show...

Page 5: ...s it is compatible with the iCHILL 206CX EVO iCHILL 208CX EVO iCHILL 205D and iCHILL 207D The connection between the expansion board and iCHILL controller must be performed via LAN The expansion board does not have internal parameterization enabling the operation and configuration of the inputs and outputs must be performed by configuring the parameters of the Ichill controller 3 CONNECTIONS ...

Page 6: ...alog input 2 NTC PTC DI 43 Pb3 Analog input 3 NTC PTC 0 20mA 4 20mA 0 0 5V DI 44 Pb4 Analog input 4 NTC PTC 0 20mA 4 20mA 0 0 5V DI 45 Pb5 Analog input 5 NTC PTC 0 20mA 4 20mA 0 0 5V DI 46 Pb6 Analog input 6 NTC PTC DI 47 Pb7 Analog input 7 NTC PTC DI 48 Pb8 Analog input 8 NTC PTC DI 49 Supply AC Power supply 24 Vac DC Power supply 24 Vdc 50 Pbc Common line analog input NTC PTC DI 51 GND Ground 52...

Page 7: ... the device and the electrical power components the distance between the device and the power cables sufficient passage for the cooling air Always comply with the laws and regulations applicable in the country where the device is installed Always protect the device for it to always be accessible solely by authorised personnel In case of malfunctions always contact the relative distributor for the ...

Page 8: ...ION 5 1 1 Temperature probes NTC e PTC Every probe has to be connected between an input Pb1 or Pb2 or Pb3 etc and the common line PbC 5 1 2 Pressure probes or current probes 4 20mA Pb3 or Pb4 or Pb5 can be used to connect a current probe the connection has to be done between an input and 12V ...

Page 9: ...00 Quick reference guide ICX200D EVO rel 1 0 9 20 5 1 3 Rathiometric pressure probes 0 5V Pb3 or Pb4 or Pb5 can be used to connect a rathiometric probe the connection has to be done between an input 5V and GND ...

Page 10: ... OUTPUT CONNECTION Depending on the configuration assigned to the parameters of the Ichill 200 EVO serie it is possible to use the analog outputs as 0 10Vdc or PWM for PWM configuration is necessary to use Dixell fan speed controller model XVxxPK It is not possible to use fan speed controller designed by other company NOTE the analogue outputs are not opto insulated Any devices that require 24Vac ...

Page 11: ...1592028300 Quick reference guide ICX200D EVO rel 1 0 11 20 5 3 1 0 10V analog output to control condenser fan ...

Page 12: ...8300 Quick reference guide ICX200D EVO rel 1 0 12 20 5 3 2 PWM analog output to control condenser fan OUT2 and OUT 3 have to be configured to manage PWM signal use only Dixell devices XV05PK XV10PK and XV22PK ...

Page 13: ...1592028300 Quick reference guide ICX200D EVO rel 1 0 13 20 5 3 3 0 10V analog output for servomotors actuators ...

Page 14: ...ac dc power supply To connect servomotors or actuators that require 24Vac dc power supply please follows the connections showed in the image below Make attention that the power supply of the ICX207D and the power supply of the servomotors actuators must be supplied for two different transformers ...

Page 15: ...o configure the expansion is necessary to enable expansion presence via parameter CF78 Presence expansion card I O configure the address of communication with the iCHILL with parameter EI01 configure expansion ICX207D the communication address via dip switch which must match the address set in parameter EI01 of the Ichill configure the inputs and outputs using the parameters EI02 EI43 of the Ichil...

Page 16: ...1592028300 Quick reference guide ICX200D EVO rel 1 0 16 20 6 1 CONNECTION DIAGRAM WITH IC206CX O IC208CX Not used ...

Page 17: ... ELECTRICAL CONNECTIONS The wiring connections for power sensor analog outputs and digital inputs have to be ordered separately from the device following two available models DWDEX15 KIT 1 5 mt DWDEX30 KIT 3 mt Connectors for relay connections remote keypad the evening RS485 and LAN are provided with the device ...

Page 18: ...ence guide ICX200D EVO rel 1 0 18 20 8 MECHANICAL CHARACTERISTIC Mount DIN rail EN 50022 DIN 43880 Material PC ABS Thermoplastic Self extinguishing V0 UL94 Comparative Tracking Index CTI 300V Colour Black IP protection IP10 ...

Page 19: ...ut 3 NTC PTC 4 20mA 0 5V Digital Input Type of analogue input configurable via software parameter NTC 50T110 C 10KΩ 1 a 25 C PTC 50T150 C 990Ω 1 a 25 C Rathiometric 0 5 4 5V Current 4 20mA Digital input free contact don t supply voltage Operation range 50 C 110 C 58 F 230 F NTC probe 50 C 150 C 58 F 302 F PTC probe 0 bar 50 bar 0 psi 302 psi pressure probe Resolution 0 1 C 1 F 0 1 bar 1 psi 9 3 DI...

Page 20: ... same secondary of the controller s power in order to prevent the outputs from malfunctioning or being damaged 9 5 DIGITAL OUTPUTS Type Relays with NO contacts Number of outputs 5 IC205D model 7 IC207D model Maximum load 5A 250Vac SPST 5 2 A Note Verify maximum current of the loads and maximum current of the common line of the relay 10A max There is double insulation between the digital outputs an...