background image

Liebert

®

 GXT4

 208V, 5000-10,000VA, 6000RTL630

User Manual

Summary of Contents for Liebert GXT4

Page 1: ...Liebert GXT4 208V 5000 10 000VA 6000RTL630 User Manual ...

Page 2: ......

Page 3: ...ode 11 1 7 1 Mains Mode 11 1 7 2 Manual Bypass Mode 12 1 7 3 Battery Mode 12 1 7 4 Battery Recharge Mode 12 1 7 5 Frequency Converter Mode 12 1 7 6 Active ECO Mode 13 2 0 INSTALLATION 14 2 1 Unpacking and Inspection 14 2 2 What s Included 14 2 3 Preparation for Installation 14 2 3 1 Installation Environment 14 2 4 Install the Main Cabinet 15 2 4 1 Tower UPS Installation 15 2 4 2 Rack Installation ...

Page 4: ...e Bypass 37 5 0 COMMUNICATION 38 5 1 Liebert IntelliSlot Communication Cards 38 5 1 1 Liebert MultiLink 38 5 2 USB Port Communication 39 5 2 1 Configuration Program 39 5 3 Terminal Block Communication 40 5 3 1 Any Mode Shutdown 40 5 3 2 Battery Mode Shutdown 41 5 3 3 On Battery 41 5 3 4 Low Battery 41 5 4 Remote Emergency Power Off 42 6 0 MAINTENANCE 43 6 1 Replacing the Internal Battery Pack 43 6...

Page 5: ... Figure 13 Power distribution box removal from 5000 and 6000VA models 18 Figure 14 Power distribution box removal from 8000 and 10 000VA models 19 Figure 15 Distribution box electrical connections diagram 20 Figure 16 Terminal block connections 21 Figure 17 Operation and display panel 22 Figure 18 Menu structure 24 Figure 19 Startup screen 25 Figure 20 Startup screens 25 Figure 21 Starting and Sta...

Page 6: ...39 Table 10 Internal battery pack models 43 Table 11 Description of the displayed fault 48 Table 12 Audible alarm description 49 Table 13 Troubleshooting table 49 Table 14 UPS specifications 5000 6000 8000 and 10 000 models 50 Table 15 UPS specifications Liebert GXT4 6000RTL630 51 Table 16 Internal battery cabinet specifications 52 Table 17 Power distribution specifications GXT4 5000RT208 GXT4 600...

Page 7: ...d for use with a four wire input L1 L2 N G The Liebert GXT4 6000RTL630 is designed be used with a three wire two phase utility source L1 L2 G WARNING The battery can present a risk of electrical shock and high short circuit current The following precautions should be observed when replacing the battery pack Wear rubber gloves and boots Remove rings watches and other metal objects Use tools with in...

Page 8: ...RT208 contain no user serviceable parts except the internal battery pack and the Power Module The UPS On Off push buttons do not electrically isolate internal parts Under no circumstances attempt to gain access internally due to the risk of electric shock or burn Do not continue to use the UPS if the front panel indications are not in accordance with these operating instructions or the UPS perform...

Page 9: ...cates caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve regulated lead acid battery Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage WEEE i PbH2SO4 R ...

Page 10: ...y life LCD for user friendly operation and local monitoring and configuration of operational parameters Flexible network management with Liebert MultiLink software Fan fault self inspection and automated diagnostic function Intelligent fan operation automatically changing rotation speed depending on system requirements to decrease power consumption and noise Input circuit breaker to ease recovery ...

Page 11: ...Ds Figure 2 Liebert GXT4 5000VA and 6000VA with input power hard wired box rear view NOTE Hard wired and hard wired receptacle boxes that include a manual bypass switch permit AC power to continue to flow from the utility input to the load while the box is removed from the UPS For details refer to 1 4 Removable Power Distribution Box Upper Bezel Operation and Display Panel Lower Bezel and Battery ...

Page 12: ...ker REPO Connection Block Output Breaker for L6 30R 4 Input Breaker for L6 30P 1 1 2 3 4 5 Output Breaker for L6 20R 2 and 3 Output Breaker for L6 30R 5 IT Power System Access Cover External Battery Connector Liebert IntelliSlot Port USB Port Terminal Block Communication Maintenance Bypass Switch Knockouts for Hard Wired Power Input REPO Connection Block Input Breaker Switch Output Breaker Switch ...

Page 13: ... two 5 20R two L6 20R PD2 003 receptacles four 5 20R two L6 30R PD2 005 Receptacles four L5 20R two L6 30R PD2 004 Receptacles four L5 20R two L5 30R PD2 006 Receptacles four L6 20R two L6 20R L14 30 Input Power Connector Input Power Breaker Maintenance Bypass Breaker Output Power Breakers for Pigtails Push Button Output Power Breakers for Two L5 20 Receptacles second push button breaker obscured ...

Page 14: ...for 5 20R Receptacles L6 30ROutput Receptacles PD2 101 Receptacles two L6 30R eight 5 20R p similar features on other distribution boxes arranged differently Output Circuit Breaker Switch for L6 30R Pigtail 2 2 1 PD2 102 Receptacles four L6 20R four 5 20R PD2 103 Receptacles four L6 30R four 5 20R PD2 104 Receptacles four 5 20R two L6 30R two L6 20R PD2 105 Receptacles four 5 20R two L5 30R two L5...

Page 15: ...4 continued PD2 107 Receptacles four L5 20R four 5 15R PD2 109 Receptacles two L14 30R PD2 201 Receptacles two IEC320 C19 eight IEC320 C13 PD2 108 Receptacles two L6 30R two L6 20R PD2 200 Receptacles four IEC320 C19 four IEC320 C13 PD2 204 Receptacles two IEC309 32A four IEC320 C13 PD2 202 Receptacles 12 IEC320 C13 ...

Page 16: ...uit In normal operation the rectifier power factor correction PFC circuit converts mains AC power to regulated DC power for use by the inverter while ensuring that the waveshape of the input current used by the UPS is near ideal Extracting this sinewave input current achieves two objectives The mains power is used as efficiently as possible by the UPS The amount of distortion reflected on the main...

Page 17: ...Bypass The Liebert GXT4 provides an alternate path for mains power to the connected load in the unlikely event of a UPS malfunction Should the UPS have an overload overtemperature or any other UPS failure condition the UPS automatically transfers the connected load to bypass Bypass operation is indicated by an audible alarm and illuminated amber Bypass LED other LEDs may be illuminated to indicate...

Page 18: ...to clear the prompt and silence the audible alarm Once the alarm prompt has been acknowledged the screen showing the estimated battery run time and battery capacity will be visible Refer to 7 0 Troubleshooting For approximate battery run times refer to Table 21 NOTICE Risk of loss of power to the connected load Can cause equipment damage Turning Off the Liebert GXT4 when it is in Battery Mode will...

Page 19: ...al costs Active ECO mode keeps the rectifier and inverter operating allowing the inverter to remain synchronized to bypass This synchronization allows the transfer of the connected equipment to UPS inverter power almost seamlessly if bypass power falls outside the user set limits Once bypass power returns within the acceptable parameters the UPS will return to Active ECO Mode operation The default...

Page 20: ...ng sheet ISO 14001 compliance 2 3 Preparation for Installation 2 3 1 Installation Environment Install the Liebert GXT4 indoors in a controlled environment where it cannot be accidentally turned Off Place it where air flows unrestricted around the unit The installation location must be free of water flammable liquids gases corrosives and conductive contaminants Maintain a minimum clearance of 100mm...

Page 21: ...et 3 Connect the spacers and the support bases as shown in Figure 9 Each Liebert GXT4 needs two assembled support bases one in the front and one in the rear 4 Adjust the direction of the operation and display panel and logo on the Liebert GXT4 a Remove the front plastic bezel cover as shown in Figure 10 Figure 10 Remove the front plastic bezel cover b Pull the operation and display panel gently ro...

Page 22: ...y cabinets connected to 6000VA Liebert GXT4 1 Inspect the external battery cabinet for freight damage Report damage to the carrier and your local dealer or Emerson representative 2 Optional rack mount hardware is shipped with the external battery cabinet and may be installed at this time if desired 3 Use the enclosed support bases for the tower option to prevent tip over One additional set of supp...

Page 23: ...n connector Follow the instructions below for removal and installation NOTE When removing the External Battery Cabinet the circuit breaker on the rear of the cabinet must be turned off before disconnecting the cable NOTE If the UPS is to be shipped or stored for an extended time the connector should be disconnected This will minimize any standby current drain on the batteries and help attain their...

Page 24: ...lide the plastic cover over the connector and tighten the screws Figure 13 Power distribution box removal from 5000 and 6000VA models 2 6 2 Remove the Power Distribution Cover from 8000 and 10 000VA Models 1 Shut down the Liebert GXT4 for help refer to 4 5 Shut Down the Liebert GXT4 a From the Main Menu select CONTROL press Enter then select TURN ON OFF b Press the enter key c Select TURN UPS OFF ...

Page 25: ... Power Distribution Box on 8000 and 10 000VA Models 1 With the cover or distribution box removed press the UPS and distribution box connectors together Ensure that the connectors are fully seated 2 Align the screw holes and press the power distribution box onto the UPS making sure that the tabs at the bottom of the box fit into the slots on the UPS 3 Attach the box to the UPS by installing screws ...

Page 26: ...ribution box electrical connections diagram Terminal Block Connections Conduit entry holes are provided on the rear and side of the box Input and output wiring should not share the same conduit Emerson recommends using strain relief when installing the wire Table 2 Branch circuit breaker ratings Unit Rating Maximum Breaker Rating 5000VA D Type 30A Long Delay 6000VA 8000VA D Type 60A Long Delay 10 ...

Page 27: ...e within sight of the UPS or have appropriate an appropriate lock out Maintain service space around the UPS or use flexible conduit 3 The installer must provide output distribution panels circuit breaker protection or emergency disconnects according to local codes Output circuits must not share a common conduit with any other wiring L2 N L1 L2 N L1 OUTPUT INPUT L2 N L1 L2 N L1 OUTPUT INPUT Liebert...

Page 28: ... are Inverter Battery Bypass ECO Mode Fault Figure 17 shows the indicators locations their descriptions and functions are shown in Table 4 Table 4 LED indicators LED Indicators LED Color Description Inverter Green On when the inverter is supplying power Bypass Amber On when the load is supplied by the mains through automatic manual bypass Battery Amber On when the load is supplied by the battery F...

Page 29: ...ns Control Buttons Description ESC Button Pressing this button returns to the previous menu or aborts any change in the input data field before confirming Up Button Pressing this button can move the cursor up or increase the value displayed in the input data field When a menu is displayed on several screens pressing the button can scroll up Down Button Pressing this button can move the cursor down...

Page 30: ...S Off Address MAC Address IPV4 Address IPV6STATIC Address IPV6AUTO Address IPV6LINK Startup on Bypass Enable Auto Restart Enable Auto Shutdown Frequency Selection Output Level Selection Battery Cabinets Low Battery Time Warning Batt Test Interval Batt Replace Time BATT UPS Turn UPS On Off View Log Clear Log Start Windows System Status Main Menu Network Time Since Startup Battery Input Load Output ...

Page 31: ...ton to select YES and press the Enter button The UPS will start up the LCD will display UPS STARTING and then START SUCCESSFUL after the UPS is turned On as shown in Figure 21 Figure 21 Starting and Start Successful screens EMERSON Network Power O P 0V HZ 0 0A I P 230V 50HZ 0 0A BATT 100 320MINS LOAD 0 TURN ON UPS YES NO O P 0V 0HZ 0 0A I P 230V 50HZ 0 0A BATT 100 320MINS LOAD 0 AC NOT AVAILABLE S...

Page 32: ...acklight turns off It will remain off until a control button is pressed 3 4 3 Main Menu Screen Press the Enter button in the default screen to enter the MAIN MENU screen as shown in Figure 23 Figure 23 Main Menu screen To select a submenu press the Up or Down button to move the cursor to the required item then press the Enter button to enter its submenu or set its parameter STATUS Screen In the MA...

Page 33: ... the CONFIGURATION screen press the Up or Down button to move the cursor to the required item then press the Enter button to enter a submenu or set its parameters VOLTAGE 120V FREQUENCY 60HZ CURRENT 17 6A POWER 2112KWH OUTPUT CAP 90 WATT 1620W VA 1800VA LOAD VOLT 120V FREQ 60 HZ CURR 18 6A POWER 97KWH INPUT CAPACITY 90 RUNTIME 100MINS VOLTAGE 80V BATTERY 05D 15H 30M TIME SINCE STARTUP 1 UPS 2 BATT...

Page 34: ...ress the Enter button to confirm the settings Battery Screen Select MAIN MENU CONFIGURATION BATTERY to enter the BATTERY screen This menu has four screens as shown in Figure 27 Figure 27 Battery screen OFF AUDIBLE ALARM NO STARTUP ON BYPASS NO GUARANTEE SHUTDOWN YES ENABLE AUTO RESTART AUTO BYPASS ENABLE FREQUENCY SELECTION 230 VOLTAGE SELECTION 0 CABINETS EXT BATT CABINET 2 MINS LOW BATTERY TIME ...

Page 35: ... ECO MODE screens as shown in Figure 28 Figure 28 ECO Mode screen Press the Up or Down button to move the cursor to the required item and press the Enter button to confirm the settings LCD screen Select MAIN MENU 2 CONFIGURATION 6 LCD to enter the LCD screen This menu has two submenus as shown in Figure 29 Figure 29 LCD screen ON ECO MODE 3 Hz FREQUENCY TOLERANCE 10 VOLTAGE TOLERANCE 5 MINS REQUAL...

Page 36: ...them refer to the Configuration Program user manual on the included CD Figure 30 Language screen Select 2 COLOR and press the Enter button to enter the COLOR screen as shown in Figure 31 Figure 31 Color screen FACTORY DEFAULT screen Select Main Menu 2 CONFIGURATION 7 FACTORY DEFAULT to enter the FACTORY DEFAULT screen as shown in Figure 32 Figure 32 Factory Default screen 1 English 2 EMERSON EMERS...

Page 37: ...r the TURN ON OFF screen This screen shows one of two displays depending on the state of the UPS as shown in Figure 34 Figure 34 Turn UPS On or Off screen ALARM CONTROL screen Select Main Menu 3 CONTROL 2 ALARM CONTROL to enter the ALARM CONTROL screen as shown in Figure 35 This section allows active audible alarms to be silenced To completely turn off the audible alarm refer to CONFIGURATION UPS ...

Page 38: ...as two submenus as shown in Figure 37 Figure 37 Log screens CLEAR LOG Screen Select MAIN MENU LOG CLEAR LOG to enter the CLEAR LOG screen as shown in Figure 38 Figure 38 Clear Log screen Press the Up or Down button to move the cursor to the required item Press the Enter button to confirm the settings 1 START 2 CANCEL 3 BATT TEST RESULT 1 VIEW LOG 2 CLEAR LOG 255 OD 1H 17m AGO UPS switch to Online ...

Page 39: ...een The NETWORK screen displays the MAC address and the IPv4 IP address If the Liebert GXT4 is fitted with an optional Liebert IntelliSlot Web card Liebert IS WEBCARD the screen will display IPv6 IP address settings IPv6 requires configuration as shown in Figure 40 Figure 40 Network screens PN GXT4 2000RT230 SN 1XXX60XXX1AFCXX FW VER U100D100 HW VER H100 ADDRESS MAC 00 02 11 4X AX ADDRESS IPV4 10 ...

Page 40: ...he inverter UPS Internal Temperature Return To Normal The internal temperature of the UPS recovers to normal range UPS Load Return From Overload The loads are reduced and the UPS recovers to normal state from overload Load On Inverter The inverter is on and supplies protected power to the load Load On ECO Bypass The UPS is on ECO mode the mains is supplying power to the load directly to reduce ene...

Page 41: ...e EVENT LOG screen see Figure 37 and select VIEW LOG to view the entire Event log Table 8 Fault list Fault Description UPS Self Test Failed The battery is bad or weak or not connected UPS Overload The UPS is overloaded Inverter Out Of Order The inverter has failed Battery Weak Bad The battery is bad or weak Output Short Circuit The output connection is short circuited DC Bus Overvoltage The DC bus...

Page 42: ...e connected equipment is not exceeding the UPS rated capacity The UPS is now providing conditioned and protected power to the connected equipment 4 3 Manual Battery Test To initiate a manual battery test select MAIN MENU CONTROL BATT TEST START If the battery test results show FAILED allow the UPS to recharge the batteries for 24 hours Retest the batteries after 24 hours of charging After the batt...

Page 43: ...cable from the wall socket 2 Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped this indicates that the power off is complete 3 Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet After powering Off the UPS the UPS ceases output and the load is powered Off 4 7 Maintenance Bypass Maintenance Bypass Mode ...

Page 44: ...xternal temperature humidity and contact closure inputs using external sensors The Liebert IS UNITY DP compatibility will be a future release contact your Emerson sales representative for availability Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink the UPS or any additional ancillary product for the Liebert GXT4 These instructions are available at mult...

Page 45: ... is Auto Select with bypass enabled Set the Low Battery Warning alarm time from 2 to 30 minutes default is 2 minutes Enable Disable the Auto Battery test default is Enable Enable Disable Auto Restart after removing Remote shutdown default is Disable Set the wiring mode of Remote shutdown default is normally open Set the Auto Enable output after remote shutdown default is Disable Set the Auto Batte...

Page 46: ...nd Pin 2 and mounted at a remote location NOTE Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown depending on the settings in the configuration program A current limited source for this optocoupler 12VDC 50mA will be available from the UPS The connection to the UPS for remote connection will be via terminal block connector Any Mode Shutdown wiring must conform to a...

Page 47: ...wer from the battery and has reached the Low Battery Warning time selected in the configuration program this dry contact will be closed NOTE Remote Power Off will be performed by NO contact A current limited source 12VDC 50mA will be available from UPS The connection to the Liebert GXT4 for remote connection will be via terminal block connector Battery Mode Shutdown wiring must conform to all nati...

Page 48: ...d equipment to comply with national and local wiring codes and regulations REPO switch connection diagram CAUTION To maintain safety SELV barriers and electromagnetic compatibility signal cables should be shielded and run separately from power cables 1 2 Normally closed switch system fail safe UPS ships with REPO jumper installed allowing the UPS to operate Opening the REPO connection will disable...

Page 49: ...g A trained user can replace the internal battery pack when the UPS is always in a restricted access location such as a rack or server closet Contact your local dealer or Emerson representative to obtain the pricing of the appropriate replacement battery pack Table 10 Internal battery pack models UPS Model Number Replacement Internal Battery Kit Model Quantity Required GXT4 5000RT208 GXT4 6000RT20...

Page 50: ...nd battery receptacles as shown in Figure 43 Figure 43 Disconnecting the battery plug and battery receptacle front view 5 Grasp the battery handle and pull one of the internal battery packs out of the UPS as shown in Figure 44 Repeat this step if both battery packs will be replaced Each model has two battery packs Front Bezel Battery Door Screws 6 8000VA 10 000VA model shown 5000VA 6000VA model ar...

Page 51: ... a long time Emerson recommends connecting the UPS to input power for at least 24 hours every four to six months to ensure full recharge of the batteries 6 3 Precautions Although the Liebert GXT4 has been designed and manufactured to ensure personal safety improper use can result in electrical shock or fire To ensure safety observe the following precautions Turn Off and unplug the Liebert GXT4 bef...

Page 52: ... 10 000VA models NOTICE During the procedure the connected load will not be protected from power disturbances such as spikes sags and failure To remove the UPS power module without shutting off power to the connected load 1 Place the UPS on internal bypass This may be done by any of the three following methods a Refer to 4 4 Manual Bypass b Slide the bracket away from the manual bypass switch on t...

Page 53: ...17 Close the input circuit breaker on the rear of the UPS see Figure 6 18 Close the output circuit breaker on the rear of the UPS see Figure 6 19 Move the bypass breaker on the rear of the UPS back to the INVERTER position see Figure 6 20 Slide the bracket back next to the manual bypass breaker and tighten its thumbscrew 21 Press the On button on the front panel one time to return the UPS to Norma...

Page 54: ... down through communication Contact customer service UPS overload The UPS is overloaded Reduce the load and contact customer service Inverter Out of Order The inverter is faulty Contact customer service Battery Weak Bad The battery is bad or weak Replace the battery Output Short Circuit The output connection is short circuited Shut down the equipment and contact customer service DC Bus Overvoltage...

Page 55: ...tery is connected If it is not make the connection and try to start the unit If the battery is connected leave the UPS connected to input power for 24 hours to recharge batteries then try to start the unit Battery indicator is illuminated UPS is not plugged in UPS is operating from battery mode Ensure UPS is securely plugged into the wall receptacle UPS input protection fuse has blown opened UPS i...

Page 56: ...attery Operation 40 70 Hz Input Power Connection Hard Wired Terminal Block 3W G L L N G L1 N L2 N Maximum Allowable VAC 150VAC Output AC Parameters Factory Default VAC 120 208VAC 120 degrees L1 L2 Factory Default Output Phase Angle 120 degrees Allowable Output Phase Angle 120 180 240 degrees auto sensing on initial application of input AC Factory Default L1 N L2 N VAC 120VAC nominal User Configura...

Page 57: ...on PD L630 power distribution box Frequency 50Hz or 60Hz Nominal Waveform Sinewave Duration Inverter Will Support Rated Load 105 to 130 1 Minute 131 to 150 10 seconds 151 to 200 1 second 200 impact load At least 5 cycles Bypass Protection Limits Disable Bypass Operation If input voltage exceeds 15 of the nominal voltage Re Enable Bypass Operation If input voltage returns to within 10 of nominal ou...

Page 58: ...07 x 310 Weight lb kg Unit 75 8 34 4 45 4 20 6 71 1 32 3 Shipping 81 1 36 8 50 7 23 76 4 34 7 Type Valve regulated non spillable flame retardant lead acid Quantity x V x Rating 2 x 6 x 12V x 9 0 AH 2 x 10 x 12V x 5 0AH 2 x 12 x 12V x 9 0 AH Battery Mfr Part CSB UPS12460F2 CSB HR1221W CSB UPS12460F2 Backup Time See Table 21 Recharge Time 3 hours to 90 capacity after full discharge into 100 load Env...

Page 59: ... Up to 10 000 ft 3000m at 77 F 25 C without derating Agency Safety UL 1778 c UL Listed RFI EMI FCC Class A Transportation ISTA Procedure 1A Table 18 Power distribution specifications GXT4 5000RT208 GXT4 6000RT208 and GXT4 6000RTL630 PD Model Power Distribution Box Model PD2 HDWR MBS PD2 001 PD2 002 PD2 003 PD2 004 PD2 005 PD2 006 PD2 007 PD2 L630 Dimensions W x D x H in mm Unit 5 2x15 5x3 5 132x39...

Page 60: ... 8 5 15 20R 4 L6 20R 4 5 15 20R 4 5 15 20R 4 L6 30R 4 5 15 20R 2 L6 30R 2 L6 20R 4 5 15 20R 2 L5 30R 2 L5 20R 4 L6 20R 4 L5 20R Table 20 Power distribution box specifications for GXT4 8000RT208 and GXT4 10000RT208 POD Model Power Distribution Box Model PD2 107 PD2 108 PD2 109 PD2 200 PD2 201 PD2 202 PD2 204 Dimensions W x D x H in mm Unit 7 4 x 5 7 188 x 145 Shipping 11 9 x 20 6 x 8 7 302 x 522 x ...

Page 61: ...131 108 145 120 132 30 82 67 102 73 98 40 53 46 71 49 73 50 45 37 50 40 52 60 37 28 43 31 46 70 28 23 36 26 40 80 25 19 28 21 34 90 21 16 26 18 28 100 18 14 22 16 25 Internal Battery 2 External Battery Cabinets 10 341 321 428 330 345 20 165 152 199 157 205 30 133 109 146 121 150 40 100 77 113 82 124 50 74 53 92 64 101 60 53 47 71 49 80 70 48 40 53 43 68 80 42 33 48 37 52 90 37 27 43 31 49 100 31 2...

Page 62: ... 153 203 158 225 50 150 134 161 140 195 60 134 110 147 122 161 70 112 95 133 102 149 80 100 77 113 82 137 90 82 67 102 73 126 100 74 53 91 64 110 Internal Battery 6 External Battery Cabinets 10 480 463 480 467 480 20 430 341 442 420 452 30 317 219 334 301 423 40 204 164 227 183 321 50 162 148 191 153 227 60 148 131 159 138 195 70 134 110 147 122 162 80 120 97 135 104 152 90 103 80 122 92 142 100 9...

Page 63: ...itions are not met the run time calculation will not be modified If the configuration program is used to change the number of battery cabinets then the values in Table 21 will be restored This will override any value that is Auto Learned 8 2 Product Warranty Registration Registration is not required to activate the product warranty on a Liebert UPS Registration is required to qualify for the Produ...

Page 64: ...ert com Monitoring liebert monitoring emerson com 800 222 5877 Outside North America 00800 1155 4499 Single Phase UPS Server Cabinets liebert upstech emerson com 800 222 5877 Outside North America 00800 1155 4499 Three Phase UPS Power Systems 800 543 2378 Outside North America 614 841 6598 Environmental Systems 800 543 2778 Outside the United States 614 888 0246 Locations United States 1050 Dearbo...