background image

Liebert

®

 

ITA

 

User

 

Manual

 

 

16-20

kVA

 

UPS

Summary of Contents for Liebert ITA

Page 1: ...Liebert ITA User Manual 16 20kVA UPS ...

Page 2: ......

Page 3: ...ts and special safety instructions provided by Emerson Warning 1 The UPS must be installed commissioned and serviced by engineers designated by the manufacturer or its agent Failure to observe this could result in personnel safety risk UPS malfunction and invalidation of warranty 2 The UPS has been designed for commercial and industrial use only and is not recommended for use in life support appli...

Page 4: ...el Components behind the protective cover which can only be removed by using a tool are restricted to service personnel 2 The UPS meets the safety requirements completely in operator access area Only service personnel can contact with the hazardous voltage inside the UPS However the risk of contacting these voltages is minimized because the components with hazardous voltage may be contacted only b...

Page 5: ...llation And Commissioning 7 2 1 Unpacking Inspection 7 2 2 Installation Preparation 7 2 2 1 Location 7 2 2 2 Environmental Requirement 7 2 2 3 Installation Tools 9 2 3 External Protective Devices 9 2 3 1 Rectifier And Bypass Input 9 2 3 2 Battery Input 10 2 3 3 UPS Output 10 2 4 Mechanical Installation 10 2 4 1 Tower Installation 10 2 4 2 Rack Installation 11 2 5 Connecting Power Cables 13 2 5 1 C...

Page 6: ...5 Setting Parameters Of Double Bus System 37 Chapter 4 Operation And Display Panel 39 4 1 Introduction 39 4 1 1 LED Indicators 39 4 1 2 Audible Alarm Buzzer 39 4 1 3 Control Buttons 40 4 1 4 LCD And Menu Buttons 40 4 2 LCD Screen Types 40 4 2 1 Start Screen 40 4 2 2 Primary Screen 41 4 2 3 Default Screen 41 4 3 Detailed Description Of Menus 42 4 4 Prompt Window 43 4 5 UPS Alarm Message List 44 Cha...

Page 7: ...mmunication Cables 53 Chapter 7 Maintenance 54 7 1 Fan Maintenance 54 7 2 Battery Maintenance 54 7 3 Cleaning UPS 55 7 4 Checking UPS State 55 7 5 Checking UPS Functions 55 Chapter 8 Options 56 8 1 Option List 56 8 2 Battery Module 56 8 2 1 List Of Battery Module Options 56 8 2 2 Appearance Of Battery Module 57 8 2 3 Backup Time Of Standard Battery Module For Single UPS 57 8 3 POD 58 8 4 Communica...

Page 8: ......

Page 9: ...rference thus adaptable to areas with unstable mains supply High power density Full digital control technology based on digital signal processor DSP to achieve high system reliability with self protection and fault diagnosis functions Intelligent battery management to extend the battery module life Operation and display panel with both LCD and LED indication to help you learn about the UPS operati...

Page 10: ... indicator DIP switch and battery cold start button with protective cover Figure 1 2 UPS front panel Rear panel As shown in Figure 1 3 the UPS rear panel provides parallel ports LBS ports I O terminal block intelligent card port dry contact ports USB port and ventilation holes The SIC SNMP card in the intelligent card port is optional purchase it if you need to use Parallel port LBS port Dry conta...

Page 11: ...tifier PFC circuit The inverter then converts DC power into pure sine wave AC power and supplies the AC power to the load through the electronic transfer switch 3 When the mains is abnormal the rectifier PFC circuit boosts the battery voltage and supplies it to the inverter The inverter then converts it into pure sine wave AC power and supplies the AC power to the load through the electronic trans...

Page 12: ...ng power by the mains after processing of the rectifier and the inverter and meanwhile the charger is charging the battery The operation mode is Normal mode In Normal mode the inverter indicators are on green 1 5 2 Bypass Mode If the overload overtime inverter or rectifier failure appears during the UPS operation in Normal mode the UPS will transfer to Bypass mode that is the load is powered by th...

Page 13: ...he power loss Note 1 In ECO mode if the bypass failure or abnormal bypass voltage appears when the output is not overloaded the UPS will transfer to Normal mode However if the bypass failure or abnormal bypass voltage appears when the output is overloaded the UPS will not transfer to Normal mode but shut down the bypass 2 In ECO mode the efficiency of the UPS is up to 98 1 5 5 Fault State In Norma...

Page 14: ...ult 20 Output Mains efficiency 93 up to 94 Type Sealed lead acid maintenance free battery Cell No 30 32 34 36 38 40 default 32 Rated voltage 360Vdc 480Vdc Battery Charge power 4 5kW 0 C 30 C 4 05kW 30 C 35 C 3 6kW 35 C 40 C Adjust automatically according to the ambient temperature Mains Battery 0ms Transfer time Inverter Bypass Synchronous transfer 1ms Asynchronous transfer default 20ms Or 40ms 60...

Page 15: ...on After the UPS arrival you should unpack it and check the following items 1 Visually inspect the UPS appearance for transportation damage If any problem is found please notify the carrier immediately 2 Check the accessories and models against the delivery list If any problem is found please notify the dealer immediately 2 2 Installation Preparation 2 2 1 Location To extend the UPS life the chose...

Page 16: ...ess than 200mm it needs to be considered according to the actaul situation for the sake of maintenance convenience Battery room A small amount of hydrogen and oxygen will be generated at the end of battery charging therefore you must ensure that the fresh air ventilation of battery installation environment meets the EN50272 2001 requirements The battery ambient temperature should keep constant for...

Page 17: ...ctive devices must be installed at the external AC input end of the UPS This section provides the general guidance for qualified installation engineer The qualified installation engineer should learn about the local wiring regulations and other related information 2 3 1 Rectifier And Bypass Input Overcurrent The appropriate overcurrent protective device should be installed on the mains input power...

Page 18: ...n overcurrent protective device Otherwise the external battery cabinet should provide DC compatible circuit breaker to provide the overcurrent protection for the UPS and its batteries 2 3 3 UPS Output The protective device must be installed for the UPS output power distribution The protective device must be different from the input power distribution protection air breaker and provide the overload...

Page 19: ...s for UPS 1 Use eight M4 10 screws to fix two brackets accessories respectively on both sides of the UPS front panel as shown in Figure 2 6 Figure 2 6 Installing brackets Note It is prohibited to move the UPS through the brackets 2 Install the guide rails You need to use guide rails when you select Liebert ITA series UPS and its options and select the rack installation The installation procedures ...

Page 20: ...e rail onto the rack through the guide rail screws a total of eight each left guide rail and right guide rail need four guide rail screws as shown in Figure 2 9 Guide rail screw 4 pcs Guide rail Guide rail holder Square hole Figure 2 9 Installing the guide rail Note 1 The guide rail holder must be close to the front of the rack 2 Any end of one guide rail has six installation holes see Figure 2 7 ...

Page 21: ...hown in Figure 2 12 It is prohibited to move the UPS and battery modules through the brackets Two persons or more are required for the installation UPS Battery module 4 pcs Figure 2 12 Installation of UPS with battery modules 2 5 Connecting Power Cables I O cables and battery cables are required for connection When connecting the cables you should follow the local wiring regulations take the envir...

Page 22: ...ote The UPS is high leakage current equipment it is not recommended to configure the MCB with leakage current protection function Table 2 4 UPS I O MCB selection Model Input interface Recommended capability of input external MCB Battery MCB Output interface Recommended capability of output external MCB 16kVA 3 in 1 out Terminal block 3 in 1 out main 63A 3P bypass 125A 1P DC 80A 3P or 4P Terminal b...

Page 23: ...n Figure 2 15 Cable entry hole with plate 12 pcs Figure 2 15 Protective cover B of the I O terminal block Before installing the protective cover B of the I O terminal block remove the iron plates on the cable entry holes and install the bushings label 21101494 accessories After the cable connection fix the protective cover B of the I O terminal block Power distribution mode There are two modes for...

Page 24: ...N mN PE oA oB oC oN oN PE C B A N PE PE C B A N UPS output Main input Figure 2 16 3 in 3 out common source configuration cable connection 3 in 3 out split bypass configuration 1 Remove the protective cover A of the I O terminal block 2 Remove the plates on six cable entry holes of the protective cover B according to the cable direction 3 Pass all the cables to be connected to the I O terminal bloc...

Page 25: ...Insulating film Copper shorting Buckle bar 10 Figure 2 18 Pasting the insulating film to the copper shorting bar 10 6 As shown in Figure 2 19 short connect bA bB and bC terminals using the copper shorting bar 7 short connect the two PE terminals of the I O terminal block of the UPS using the copper shorting bar 10 with insulating film short connect oA oB and oC terminals using the copper shorting ...

Page 26: ...e copper shorting bar 7 short connect oA oB and oC terminals using the copper shorting bar 5 short connect mN and bN terminals and two oN terminals using the two copper shorting bar 4 10 4 7 5 4 8 UPS oN oA oB oC PE mNbN bA bB bC A C B N PE PE L N UPS oputput Main input Bypass input mA mB mC Figure 2 20 3 in 1 out split bypass configuration cable connection 8 Connect the live lines main input phas...

Page 27: ...t or 1 Phase Output default password 12345 and power off the system completely then power on the system again enter this menu to confirm that the setting is valid 4 Power off the system completely and restore the EPO jumpers of the dry contact port 4 and remove the main input cable From 3 in 1 out to 3 in 3 out 1 Remove all copper shorting bars shown in Figure 2 19 and Figure 2 20 of the 3 in 1 ou...

Page 28: ...ce and accessories of the battery and carefully read this manual and the user manual provided by the battery manufactory 2 Maintain at least 10mm clearances between the front rear side panels of the battery and the wall or adjacent equipment to keep well ventilated 3 Maintain some clearances between the top of the battery and the upper baffle to facilitate monitoring and maintenance of the battery...

Page 29: ...cables of the positive battery module are shown in Figure 2 25 and the cables of the negative battery module are shown in Figure 2 26 Connect the Bat Bat N Bat and PE terminal to the corresponding terminal of the UPS and the terminals of the other end color red black and yellow to the corresponding terminals of the battery module Red Black Yellow PE Bat N Bat 600 10 900 10 Red Black Yellow Figure ...

Page 30: ...22 Chapter 2 Single UPS Installation And Commissioning Liebert ITA 16kVA And 20kVA UPS User Manual Bat Bat Bat N PE Figure 2 27 Cable connection diagram of the positive battery module ...

Page 31: ...tage and frequency are normal 4 The output terminals of the UPS and the POD if configured are energized upon the startup If the load is connected with the output terminals make sure that the power to the load is safe 2 6 2 Single UPS Parameters Setting Power on the UPS according to step 1 step 4 in 2 6 3 Normal Mode Start Up it is prohibited to start the inverter Press the menu key to enter the fu...

Page 32: ...ication address For RS485 communication 1 Single Group Batt Cap Set the parameter according to the actual total battery capicitity 0014 Battery Cells Number Set total battery number 32 Equalize Charge Allowed Enabled or disabled Enabled Temp Compensation Enabled or disabled Disabled Batt Temp Sensor Position Set the position of the temperature sensor NONE Shared Battery Each UPS in parallel system...

Page 33: ...2 Note The default value of Battery Cells Number is 32 set the paramerter according to the atcual requirement Select Enabled in Shared Battery according to whether the battery is shared Set System Configuration to Single if the system is single system Select Normal or ECO according to the UPS working mode select 50Hz or 60Hz in Output Frequency Level according to the power grid frequency level as ...

Page 34: ...e load 2 LCD displays the self test screen the fault indicator red and the inverter indicator green are on at the same time for about five seconds After the self test the UPS enters the bypass state the fault indicator turns on and the buzzer beeps for one second 3 The rectifier runs in normal state for about 30 seconds the start up of the rectifier is finished 4 Finish and check the parameter set...

Page 35: ... LCD of each UPS 3 2 Requirements A UPS system composed of multiple parallel connected UPSs is equivalent to a large UPS system Nevertheless it provides increased system reliability To ensure equal utilization of all UPSs and compliance with relevant wiring regulations the following requirements must be met 1 All single UPSs must have the same capacity and must be connected to the same bypass sour...

Page 36: ...nal block of the rear panel of the UPS the layout of the I O terminal block is shown in Figure 2 13 Power distribution mode There are two modes for UPS parallel power distribution using the 1 1 parallel POD optional provided by Emerson self distribution The I O cable connections are divided into four types 3 in 3 out common source configuration factory default 3 in 3 out split bypass configuration...

Page 37: ...t 3 in 1 out factory default 3 in 3 out If you need to change the mode from 3 in 3 out to 3 in 1 out or from 3 in 1 out to 3 in 3 out carry out the parallel connection after changing the single system to the needed system Refer to Changing power distribution mode in 2 5 1 Connecting I O cables for the changing method 3 4 2 Connecting Parallel Cables The parallel system provides parallel cable opti...

Page 38: ... the parallel system 2 The parallel communication fault occurs during the parallel commissioning check whether the connection of the parallel cables is correct and whenther the pin1 pin9 of the parallel cables are connected The parallel addresses for all UPSs in parallel system should be set The parallel addresses can be set through the DIP switch on the front panel of the UPS see Figure 1 2 Remov...

Page 39: ...ntly the battery cables connection of each UPS in the parallel system is the same with that of the single UPS refer to 2 5 2 Connecting Battery Cables for the installation method The schematic diagram of battery strings in 1 1 parallel system with independent battery strings is shown in Figure 3 4 Refer to 2 5 Connecting Power Cables to configure a 4P MCB Note Make sure that the LCD settings are c...

Page 40: ...s of the battery strings respectively to Bat Bat N Bat and PE terminals of the corresponding I O terminal block of the UPS in the parallel system through each battery MCB as shown in Figure 3 5 PE UPS 1 UPS 2 UPS 1 MCB UPS 2 MCB PE Positive battery string PE Bat Bat N Bat Bat Bat N Bat PE Negative battery string Figure 3 5 Connection diagram of shared battery string in 1 1 parallel system Refer to...

Page 41: ...on and cable connection is correct and there is no short circuit and that the positive pole and negative pole of the battery are correct Especially when each UPS of the parallel system shares the battery strings check these items carefully 3 Check all the working status of the parallel system ensure that the phase sequence of the main bypass and output of each UPS is correct and consistent that th...

Page 42: ... Units to X 0 X 3 Take the 3 1 parallel system for example set System Configuration to Parallel Parallel requisite units to 3 Parallel Redundant Units to 1 as shown in Figure 3 8 ITA 016 kVA Settings Unit 1 Enabled Disabled System Configuration Parallel Parallel requisite units 3 ESC Disabled Shared Battery 1 2 3 4 Single Parallel 14 30 36 ITA 016kVA Settings Unit 1 0 1 2 3 ECO Mode Normal Output ...

Page 43: ...UPS and all UPSs are powered on at the same time and enter the bypass mode After the start of the rectifier is finished press the ON key of one UPS for two seconds the inverter indicator green will be on Measure whether the inverter output voltage is normal If the 1 1 parallel POD is configured close the corresponding input MCB bypass MCB and output MCB of the POD 2 Start the inverter of the secon...

Page 44: ... single UPS and parallel system respectively The bypass input power and main input power must use the input terminal of the same neutral line If the input terminal has leakage current the leakage current protective device should be installed before the input terminal 3 6 4 Connecting LBS Cables In double bus system connect the two ends of the LBS cable to any LBS port of the two parallel systems r...

Page 45: ...le port LBS cable DB9 male port DB9 female port Figure 3 10 LBS cable connection 3 6 5 Setting Parameters Of Double Bus System Take the double bus system formed by the 1 1 parallel system for example set System Configuration to Parallel Parallel requisite units to 1 Parallel Redundant Units to 1 For the master system set LBS Function to MASTER For the slave system set LBS Function to SLAVE Ensure ...

Page 46: ...l 14 30 36 ITA 016kVA Settings Unit 1 0 1 2 3 ECO Mode Normal Output frequency Level 50Hz ESC 1 Parallel Redundant Units Normal ECO 50Hz 60Hz 14 30 36 ITA 016kVA Settings Unit 1 200 208 220 230 380 400 415 480 LBS Function MASTER Command password ESC 380V Output Voltage Level NONE SLAVE MASTER 14 30 36 ITA 016kVA Settings Unit 1 YDN23 Velocity 3 Phase Output or 1 Phase Output Three ESC YDN23 Proto...

Page 47: ...ontrol buttons FAULT CLEAR ON OFF ALARM CLEAR EPO Figure 4 1 Operation and display panel 4 1 1 LED Indicators The LED indicators are composed of the inverter indicator and the fault indicator Table 4 1 gives the indicators description Table 4 1 Description of LED indicators Indicator Color State Meaning On Load power is supplied by the inverter Blinking Inverter on starting up synchronizing or sta...

Page 48: ...4 1 4 LCD And Menu Buttons The operation and display panel provides an LCD and five menu buttons F1 F2 F3 F4 HELP Table 4 4 gives the function description of the menu buttons Table 4 4 Menu buttons function description Function 1 Function 2 F1 F2 F3 F4 ESC Escape Left Up Right Down Enter Button HELP HOME LCD provides you with the user friendly interface and the 320 240 dot matrix image display The...

Page 49: ...rmation window Data window Menu window Keypad window Figure 4 3 Primary screen The current icons on top of the F1 F4 and HELP menu buttons give the explanations of each button From any menu in primary screen pressing the F1 button can return to the Output menu For details about the primary screen refer to 4 3 Detailed Description Of Menu Items 4 2 3 Default Screen During the UPS operation if there...

Page 50: ... voltage V Line voltage L N voltage V Phase voltage L N current A Phase current Frequency Hz Output frequency L L voltage V Line voltage AC Output Power factor Power factor Sout kVA Sout Apparent power Pout kW Pout Active power Qout kVAR Qout Reactive power Load level The percentage of the UPS rated load Load Crest factor Output current crest factor Sout kVA Sout Apparent power Pout kW Pout Active...

Page 51: ... system again and the setting can take effect Battery maintenance test The battery maintenance test will partly discharge the battery to get rough assessment of the battery capacity The load ranges from 20 to 100 Battery capacity test The battery capacity test will completely discharge the battery to get accurate assessment of the battery capacity The load ranges from 20 to 100 System test The UPS...

Page 52: ...s and check whether the alarm disappears 2 Press the FAULT CLEAR button Battery fault Battery is depleted reserved Battery replaced Battery test failure and the battery should be replaced Battery low pre warning Before the end of the discharge battery undervoltage pre warning may occur After this pre warning the battery should have the capacity for three minutes discharging with full load The time...

Page 53: ...an failure 4 prolonged inverter overload Fan fault At least one of the cooling fans has failed Inverter relay fail At least one of the relays of inverter side is open or short circuit This fault is locked until power off for a 3 in 1 out system possible causes for relay fault type inverter fuse open inverter IGBT open Bypass STS fail At least one of the static switches of bypass side is open or sh...

Page 54: ...ct port 4 2 Whether the LCD displays Parallel comm Fail Battery float charging Battery status floating charge mode Battery boost charging Battery status boost charge mode Battery discharging Battery status discharge mode Battery period testing Automatically periodic battery maintenance test 20 capacity discharge Batt capacity testing User initiated battery capacity test 100 capacity discharge Batt...

Page 55: ...e start up mode of the single UPS includes normal mode start up and battery mode start up refer to 2 6 3 Normal Mode Start Up and 2 6 4 Battery Mode Start Up for details For the detailed information of the parallel UPS refer to 3 5 3 Power On Commissioning For Parallel System 5 2 Transfer Procedures Between Operation Modes Note The Inverter operation mode include Normal mode mains inverter and Bat...

Page 56: ...normal protection 2 After the UPS transfers to the maintenance bypass the UPS is not in operation and the LCD is no display and only the user terminal block silkprint USER of the single POD is electrified Be careful when removes the UPS to be maintained 5 2 5 Transfer From Maintenance Bypass Mode To Inverter Mode After UPS maintenance you can use this procedure to transfer the load from the mainte...

Page 57: ...disconnected 5 5 Auto Restart When the mains power failure the UPS draws power from the battery to supply the load until the batteries are depleted then the UPS will shut down The UPS will automatically restart and recover output power supply After the mains power is restored The UPS Auto Restart function is enabled After the Auto Restart is delayed default ten minutes During the Auto Restart dela...

Page 58: ...5 Enter to move the cursor to the data window of the LCD 3 Use F3 and F4 up and down arrow to select the required language 4 Press F5 Enter to confirm 5 Return to the Output menu by repeatedly pressing F2 ESC At this point all texts on the LCD will be displayed in the selected language 5 8 Changing Current Date And Time Procedures for changing the system date and time 1 From the Output menu press ...

Page 59: ...ork Shutdown has been installed to protect data and reduce loss Refer to the corresponding user manual for the installation and operation guide JBUS MODBUS adapter card Through the background monitoring software JBUS MODBUS adapter card adapter card for short can adopt JBUS MODBUS RTU protocol to manage the UPS and the field lighting power system FLP The adapter card gets various electrical parame...

Page 60: ...Output port of battery status 2 2 GND GND 3 1 ON_BYPASS The level is 12V when the system runs in bypass mode 3 Output port of bypass status 3 2 GND GND 4 1 EPO_NC EPO activated when opened to 4 2 4 2 12V EPO activated when opened to 4 1 4 3 12V EPO activated when shorted to 4 4 4 Input port of remote EPO 4 4 EPO_IN EPO activated when shorted to 4 3 5 1 BFP_O Bypass backfeed protection relay normal...

Page 61: ...nnecting the REPO cable users should parallel connect 12V of the REPO port with one end of the electronic switch and parallel connect EPO_IN with the other end of the electronic switch Note the difference between the port silkscreen and during connection When the REPO switch at the user end closes the UPS will generate an alarm and cut off the output immediately and the UPS will not return to the ...

Page 62: ...k regularly the screws at the battery connection parts fasten it immediately if not tight 2 Make sure that the safety equipment are complete and that the function is normal especially that the settings of the battery management parameters are normal 3 Measure and record the internal temperature of the battery room 4 Check whether the battery ports are damaged or hot and whether the chassises and t...

Page 63: ...ld find out the reason such as operator intervention overload internal fault and so on 3 Check if the battery is discharging When AC mains is normal the battery should not discharge if the UPS operates in Battery mode you should find out the reason such as mains failure battery test operator intervention and so on 7 5 Checking UPS Functions Note UPS functions check procedures may cause power inter...

Page 64: ...US assembly for Liebert NX and ITA UPS UF RS485 232 to 485 communication assembly for ITA UPS Communication options UF RS232 RS232 communication card options for Liebert ITA UPS UPS02R100 SiteMonitor network license monitoring software number of users 5 UPS03R100 SiteMonitor network license monitoring software number of users 20 Monitoring options UPS04R100 SiteMonitor network lisence monitoring s...

Page 65: ...rding to actual requirement as shown in Figure 8 2 Plastic panel Figure 8 2 Removing the plastic panel The battery module provides ventilation holes battery ports and battery fuse box on the rear panel as shown in Figure 8 3 保险 F 32AH 400Vdc CAUTION ForContinuedProtection Against Risk of Fire ReplaceOnlyWithFuseof TheSa meTypeandRating 注意 为避免着火的危险 请用同种容量和型号的保险替换 Battery port 1 Battery port 2 Batte...

Page 66: ...6m 8 21m 31m 33m 43m 62m 1h15m 10 31m 41m 47m 62m 1h15m 1h52m Table 8 6 Backup time list 4 Backup time No of the battery module 5 4kW 4 5kW 3 6kW 3kW 1 8kW 1 5kW 4 47m 62m 1h15m 1h46m 3h07m 3h45m 6 1h15m 1h46m 2h15m 2h42m 5h 6h06m 8 2h 2h22m 3h07m 3h45m 7h05m 7h35m 10 2h30m 3h07m 3h57m 5h 9h06m 10h26m Note The backup time will have some difference owing to the different battery manufacturer model ...

Page 67: ...ock Note 1 Main input mA mB mC mN Bypass input bA bB bC bN Output oA oB oC oN Grounding PE 2 In factory four copper shorting bars 3 have been used to short terminals between mA and bA mB and bB mC and bC mN and bN respectively PE terminal PE terminal Rear panel of the single POD Figure 8 4 Front panel and rear panel of the single POD UPS1 main input MCB UPS2 main input MCB UPS2 bypass input MCB UP...

Page 68: ...ation cable Type Name Description Appearance UHRK2S671SL4 Communiation cable For N 1 parallel system N 1 communication cables are needed For example two communication cables are needed in 1 1 parallel system three communicatio cables are needed in 2 1 parallel system four communication cables are needed in 3 1 parallel system 8 5 Guide Rail The guide rail is used in rack installation of UPS POD op...

Page 69: ...ouble Bus System for the installation and commissioning of the LBS system 8 7 Battery Cabinet If the cost saving and the more backup time are required the external battery cabinet with big capacity battery cabinet for short is recommended The battery cabinet is designed with the appearance of the e rack cabinet in which can embed 32 cell or 30 cell CBS batteries including cables and MCBs in the ba...

Page 70: ...ard UF SNMP810 Remote monitor UPS through TCP IP protocol and Internet Support remote safe shutdown Provide an extended net port cascade connect up to eight temperature humidity sensors RS485 card UF RS485 Be used to connect UPS to RDU A monitoring unit or connect to the cascade communication in parallel system MODBUS card UF MODBUS410 Select it when the UPS is connected to the monitoring system o...

Page 71: ...sation connect to the COM1 port of the SIC card and set DIP switch of the temperature sensor to 1 For the installation and setting of the SIC card refer to RDU SIC Card User Manual 2 When using the SiteMonitor monitoring software connect the USB port on the UPS rear panel and install the corresponding drive programmes in the SiteMonitor monitoring software VCD ...

Page 72: ...eads by applying a unique combination of industry expertise technology and resources to make the future of our customers enterprises and networks possible While every precaution has been taken to ensure the accuracy and completeness of this literature Emerson Network Power assumes no responsibility and disclaims all liability for damages resulting from use of this information or for any errors or ...