background image

Uninterruptible Power Supply 

Instruction Manual

SDU AC - A Series

SDU500A, SDU850A

SDU500A-5, SDU850A-5

Summary of Contents for SDU A Series

Page 1: ...Uninterruptible Power Supply Instruction Manual SDU AC A Series SDU500A SDU850A SDU500A 5 SDU850A 5 ...

Page 2: ...ced DIN Rail Clip SDUCFRELAYCARD Dry contact relay status with LED diagnostics and standby Mode capability Please refer to SDU AC A Series COMM Cards Manual SDUENETIPCARD Network communication module is a high performance communication solution for industrial field devices It is designed for use with high performance networks such as real time Ethernet and synchronized applications such as servo d...

Page 3: ... 0 Installation Instructions 3 4 0 Specifications 5 5 0 General Description 6 6 0 System Block Diagram 8 7 0 Operating Instructions 9 8 0 Diagnostics 11 9 0 Battery Back Up Times 12 10 0 Software and Interface 13 11 0 Storage 14 SDU AC A Series Instruction Manual iii ...

Page 4: ...ont Panel 6 Figure 5 Product Dimensions 7 Figure 6 SDU AC A Series UPS System Block Diagram 8 Figure 7 UPS Control Panel Configuration 10 Figure 8 Connecting UPS to Computer 13 Figure 9 UPSMON Control Panel Monitor System 13 TABLES Table 1 Green Mode Setting Table 9 Table 2 Diagnostics LED Alarms 11 Table 3 Battery Back Up Time Chart 12 iv Contents ...

Page 5: ...to switch ON the UPS When power fails the UPS can be automatically turned OFF as long as the connected loads are not operating to save the battery energy The SDU also includes an automatic self test feature to test the UPS function and battery If the battery is no longer useful the unit will sound an alarm and an LED indicator will illuminate This SDU AC A Series has a communication port that can ...

Page 6: ...es or other openings of the UPS Keep all vents free of dust accumulation that could restrict airflow Do not dispose of batteries in a fire they may explode Do not open or damage the battery Released electrolyte is harmful to the skin and eyes and may be toxic This equipment is suitable for use in Class I Div 2 Groups A B C D T3 When installed in a hazardous location adhere to the following Cet équi...

Page 7: ...onal card remove the COMM PORT cover and insert the card Refer to the SDU COMM CARD Manual for more details Refer to inside cover for COMM CARD options or contact your SolaHD representative 3 DIN Rail Mounting Follow instructions below Figure 3 Mounting the UPS DIN Rail A Tilt unit as illustrated B Put it onto the DIN rail C Push downwards until stopped D Push at the lower front edge to lock E Sha...

Page 8: ...then apply power to the UPS Reference Figure 2 5 Internal Battery Charge the UPS battery for a minimum of 8 hours before initial use The UPS charges its battery whether the UPS is on or off when it is connected to AC power 6 Warning Label Apply the provided electrical shock warning label to the panel making it clearly visible to the user 7 Do not connect Ground to Neutral on either input or output...

Page 9: ...tinuous beeping sound ENVIRONMENT Ambient Operation 0 95 humidity non condensing 50 C up to 6 600 ft 2000m Audible Noise 40 dBA 1 m from surface Vibration Operating IEC60068 2 6 Sine Wave 10Hz to 500Hz 19 6m S displacement of 0 35mm 60 min per axis for all X Y Z direction Non operating IEC60068 2 6 Random 5hz to 500Hz 2 09Grms 20 min per axis for all X Y Z Shock Operating IEC60068 2 27 Half Sine W...

Page 10: ...ry needs to be recharged and tested The LED will illuminate when the unit is subjected to an overload condition If the unit shuts down due to overload the LED and alarm will continue for two minutes 3 ON Battery Indicator Yellow LED The LED illuminates when the UPS is supplying battery power to the loads 4 AC Input Normal Indicator Green LED The LED illuminates when the line input voltage is norma...

Page 11: ... SDUENETIPCARD NETWORK COMM CARD can be purchased separately The UPS can detect the presence of a COMM CARD and identify what kind of COMM CARD is inserted USB communication will have precedence over COMM CARDS 10 REMOTE ON OFF TERMINALS Use a switch to remotely toggle ON OFF state Non Polarized terminals Catalog Number Dimensions in Inches Millimeters H W D SDU AC A SERIES 4 87 123 7 11 10 281 9 ...

Page 12: ...6 0 System Block Diagram Figure 6 SDU AC A Series UPS System Block Diagram 8 6 0 System Block Diagram ...

Page 13: ... ON OFF TEST button for at least 1 second to perform a self test During the self test the UPS momentarily operates in back up mode YELLOW LED will illuminate momentarily then goes back to GREEN If the UPS passes the self test it returns to AC mode If the YELLOW LED does not illuminate momentarily please contact SolaHD Technical Support or your local SolaHD distributor for a replacement Additionall...

Page 14: ...d auto recovers once AC power returns This 3 minute window or maximum run time depending on loading allows the user to shut off or place equipment into safe mode 7 7 REMOTE ON OFF Allows the user to perform remote power ON OFF functions using a switch on terminals non polarized to toggle ON OFF state To Enable the UPS close the switch that is connected to the terminals To Disable the UPS open the ...

Page 15: ...ad around 105 of it s rated capacity YELLOW RED After continuous alarm for 3 seconds the UPS will be on standby mode Next the alarm will sound for 2 minutes and the UPS will shut down Load 120 of it s rated capacity YELLOW RED After continuous alarm for 3 seconds the UPS will be on standby mode Next the alarm will sound for 2 minutes and the UPS will shut down LOW BATTERY YELLOW During back up mod...

Page 16: ...PW36 12 YUASA NPW45 12 Load Level Approximate Back Up Time Minutes Back Up Time Minutes 10 120 78 20 51 34 30 29 5 17 40 19 5 11 50 16 9 60 11 6 5 70 8 5 80 6 5 3 5 90 5 2 5 100 4 2 Table 3 Battery Back Up Time Chart Do not attempt to open the UPS or replace the battery Call SolaHD Technical Support for further instructions Do not mount the UPS in upside down orientation 12 9 0 Battery Back Up Tim...

Page 17: ...MON software users can perform monitoring functions and an orderly shutdown of protected equipment in the event of power failure UPSMON displays diagnostic information such as voltage frequency and battery levels It also allows configuration of the UPS features Additional details available by selecting the Help and Support button of the control panel as shown in Figure 9 Figure 8 Connecting UPS to...

Page 18: ...served Specifications are subject to change without notice Aunque se han tomado todas las precauciones para asegurar la exactitud y acuciosidad de este manual SolaHD no asume responsabilidad alguna y rechaza toda responsabilidad por daños que pudieran resultar debido al uso de esta información o por cualquier error u omisión El nombre y el logotipo de SolaHD son marcas registradas de Appleton Grp ...

Page 19: ...SDU AC A Series Instruction Manual ...

Page 20: ...struction materials group has the products to meet your needs Power Quality Solutions The SolaHD brand offers the broadest power quality line including uninterruptible power supplies power conditioners voltage regulators shielded transformers surge protection devices and power supplies Heating Cable Systems This group is made up of the EasyHeat and Nelson brands They offer a broad range of electri...