background image

Uninterruptible Power Supply 
User Manual

SDU DC UPS B-Series

Summary of Contents for SolaHD SDU DC UPS B Series

Page 1: ...Uninterruptible Power Supply User Manual SDU DC UPS B Series ...

Page 2: ...ration 10 Turning ON the UPS Normal Mode 10 Turning OFF the UPS 10 Remote ON OFF 10 Self Testing 10 LED Status 11 Contact Relay Truth Table 12 UPS Battery 13 Battery Types 13 Batteries for SDU 24 BATB 13 Batteries for SDU 24 BATEM 13 Battery Backup Times 14 SDU 10 24B with SDU 24 BATB 14 SDU 20 24B with SDU 24 BATB 14 SDU 10 24B with SDU 24 BATEM 14 SDU 20 24B with SDU 24 BATEM 14 Specifications 1...

Page 3: ...ery Connection Use only the SOLA cable provided with unit or SOLA type SDU 24EXTBC6 CAUTION Risk of electric shock and personal injury Do not remove the cover as the unit has no user serviceable parts inside GENERAL INSTALLATION SAFETY PRECAUTIONS This product is for indoor use only in a Pollution Degree II environment Overvoltage Category II system Device provides Double Insulation based on 100 V...

Page 4: ...ule A272 368 Rev 0 8 2021 Safety Instruction Sheet SDU BATEM DC Uninterruptible Power Supply Battery Module A272 369 Rev 0 8 2021 Introduction Congratulations on your choice of the SDU DC B Series Uninterruptible Power System UPS The SDU DC is an advanced 24 Vdc UPS that combines an industry leading design unique installation options and a wide operational temperature range see Specifications The ...

Page 5: ...4 DB9 Interface kit to convert relay contact signals to DB9 signals SDU PMBRK Chassis mounting brackets to secure the UPS to the wall back of the panel or enclosure Product Description Figure 1 Figure 2 1 Output LED Indicates the output status of the DC UPS See Table 1 2 Battery LED Indicates the status of the battery module connected to the DC UPS See Table 1 3 Contact Relay Terminals The control...

Page 6: ...a protected area with adequate airflow and free of excessive dust Do not operate the UPS outdoors DIN Rail Mounting 1 Tilt and place the unit onto the DIN rail 2 Push the unit downward until it stops 3 Push at the lower front edge to lock Ensure that the retainer has locked Removing the Unit from the DIN Rail Push the button and swing the bottom out and up Figure 5 ...

Page 7: ... brackets P N SDU PMBRK are sold separately Please refer to the installation instructions supplied with the brackets NOTE If you will be shipping the UPS already mounted we recommend using the chassis mounting brackets P N SDU PMBRK to secure the UPS Figure 6 ...

Page 8: ...Page 6 Figure 7 Figure 8 ...

Page 9: ...Page 7 Figure 9 ...

Page 10: ...ly from a properly grounded earthed DC supply To reduce the risk of electric shock do not remove the cover For service contact a qualified technician Figure 10 Connections 1 Use the polarized cable to connect the power module to the battery module 2 Connect the power module dc input connector to the 24 Vdc input power source 3 Hardwire the load to the power module output terminal connector ...

Page 11: ...earthed DC supply To reduce the risk of electric shock do not remove the cover For service contact a qualified technician Figure 11 Connections 1 Use the polarized cable to connect the power module to the battery module 2 Connect the power module dc input connector to the 24 Vdc input power source 3 Hardwire the load to the power module output terminal connector Charging the Battery ...

Page 12: ...ent draining of the battery Turning OFF the UPS 1 Disable the DC UPS by disconnecting R1 and R2 through turning off the Remote ON OFF toggle switch if not using a toggle switch remove the Remote ON OFF Bypass Jumper 2 De energize the DC input supply 3 Disconnect the DC input supply Battery Module and the load Remote ON OFF Turns UPS output on when terminals R1 and R2 are shorted Figure 12 NOTE The...

Page 13: ...tection Steady Red BATTERY Input loss Battery Mode Load Within Range Green Flashing 0 5s ON 0 5s OFF Overtemperature Protection Steady Red Battery Condition Battery LED NORMAL input present Battery Full Steady Green Battery Charging 50 Capacity Green Flashing 0 25s ON 0 25s OFF Battery Charging 50 Capacity Green Flashing 1s ON 1s OFF BATTERY Input loss Battery Mode Load Within Range OFF Overtemper...

Page 14: ...n 1 2 Pin 2 3 Pin 4 5 Pin 5 6 Pin 7 8 Pin 8 9 N C N O N C N O N C N O Normal mode O X O X O X Battery mode 30 100 SOC O X X O O X Battery mode Low Battery 20 30 SOC X O X O O X Battery fault I I I I X O Legend X Contact close O Contact open I Indeterminate N C Normally close N O Normally open ...

Page 15: ...sa Battery Co Ltd NPX25 Table 4 Batteries for SDU 24 BATEM Manufacturer Type Rating CSB GP1272 12 V dc 7 2 Ah Recharging the Battery Locate the recharge label on the box containing the product The label will indicate the last recharge date Please refer to the label for the next recharge due date If the product is due for recharge please follow the wiring diagram Figure 10 to recharge the SDU 24 BA...

Page 16: ...21 10 6 4 2 units 116 50 28 17 10 3 units 178 80 46 31 20 4 units 237 113 65 43 31 Table 7 SDU 10 24B with SDU 24 BATEM Load 20 2 A 40 4 A 60 6 A 80 8 A 100 10 A 1 unit 135 52 28 19 14 Table 8 SDU 20 24B with SDU 24 BATEM Load 20 4 A 40 8 A 60 12 A 80 16 A 100 20 A 1 unit 48 17 9 6 4 NOTE Run times are based on new fully charged battery module at a temperature of 25 C 77 F with purely resistive DC...

Page 17: ...tput Power 240W 480 A PROTECTION Input Current Protection Normal Mode Internally Fused 30A 32VDC Peak current capability Normal Mode Power boost allows for 150 of rated load for 4 seconds Reverse Polarity input voltage UPS goes to battery mode Reverse Polarity battery input UPS does not turn on Output Short Circuit UPS shutdown Auto recovery Battery Over Voltage Protection Charging stops at 28V Au...

Page 18: ...r the Battery Red color Black color NOTE The maximum length of the connection between the power module and battery module is 6 ft 1 85m Relay Contact Terminals Use connector size range 24 16 AWG 0 34 4mm2 Mounting Use DIN TS35 7 5 or TS35 15 rail system Apply to both thin and thick DIN Rail 1 0 and 1 5mm optional screw mounting set SDU PMBRK SAFETY APPROVALS SDU DC UPS System cULus Listed UL CSA 6...

Page 19: ...TB 6 hours for 2 battery modules 3 hours for each additional battery module SDU 24 BATEM 8 hours for 1 battery module Backup Times See Tables 5 8 Weight 11 46 lb 5 2 kg 16 lb 7 26 kg Enclosure Dimensions 7 57 in x 4 85 in x 4 33 in 192 4 mm x 123 3 mm x 110 mm 11 50 in x 5 57 in x 4 57 in 292 mm x 142 mm x 116 mm Mounting Simple snap on system for DIN rail TS35 7 5 or TS35 15 or optional chassis m...

Page 20: ...tage is not within the acceptable range of 22 1V 28 6V Adjust dc input voltage Other failure Contact Technical Support UPS cannot turn ON at Battery Mode Battery is Drained or not connected Connect or recharge battery Backup time is too short Battery is not fully charged Recharge the UPS for at least three 3 hours Battery has low capacity due to deterioration Replace the battery Other failure Cont...

Page 21: ...ssories in the accessory slot and disconnect any cables connected to the computer interface port to avoid unnecessary draining of the battery During extended storage in environments where the ambient temperature is 15 C to 30 C 5 F to 86 F charge the UPS battery every 4 months During extended storage in environments where the ambient temperature is 30 C to 45 C 86 F to 113 F charge the UPS battery...

Page 22: ...SA 847 268 6651 Warranty Warranty Information Please refer to the Terms Conditions of Sale at https www appleton emerson com documents appleton grp llc terms of sale policies procedures en us 7444090 pdf Product Literature For additional product literature including French and Spanish manuals please visit www solahd com While every precaution has been taken to ensure accuracy and completeness in t...

Page 23: ...e Industriel Nord 35 rue André Durouchez CS 98017 80084 Amiens Cedex 2 France T 33 3 2254 1390 China Sales Office Shanghai T 86 21 3338 7000 Canada EGS Electrical Group Canada Ltd 99 Union Street Elmira ON N3B 3L7 Canada T 1 888 765 2226 Middle East Sales Office Dammam Saudi Arabia T 966 13 510 3702 Chile Sales Office Las Condes T 56 2928 4819 India Sales Office Chennai T 91 44 3919 7300 Korea Sal...