1592019030 XEV02D GB r1.2 04.06.2015 

XEV02D 

1/4 

XEV02D 

SLAVE DRIVER FOR DIGITAL™ COMPRESSORS 

1.

GENERAL WARNING .................................................................................................................... 1

2.

GENERAL DESCRIPTION ............................................................................................................ 1

3.

WIRING CONNECTIONS .............................................................................................................. 1

4.

ALARM FUNCTIONS ..................................................................................................................... 1

5.

FRONT PANEL .............................................................................................................................. 2

6.

USER INTERFACE ........................................................................................................................ 2

7.

PARAMETER LIST ........................................................................................................................ 2

8.

DIGITAL INPUTS ........................................................................................................................... 3

9.

ELECTRICAL CONNECTIONS ...................................................................................................... 3

10. RS485 SERIAL LINE ..................................................................................................................... 3
11. USE THE HOT-KEY....................................................................................................................... 3
12. ALARM MENU ............................................................................................................................... 3
13. DISPLAY MESSAGES ................................................................................................................... 3
14. TECHNICAL DATA ........................................................................................................................ 3
15. STANDARD VALUES .................................................................................................................... 3

1. GENERAL WARNING

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

This manual is part of the product and should be kept near the instrument for easy and quick 
reference. 

The  instrument  shall  not  be  used  for  purposes  different  from  those  described  hereunder.  It
cannot be used as a safety device. 

Check the application limits before proceeding.

Dixell  Srl  reserves  the  right  to  change  the  composition  of  its  products,  even  without  notice, 
ensuring the same and unchanged functionality. 

1.2

 

SAFETY PRECAUTIONS 

Check the supply voltage is correct before connecting the instrument.

Do not expose to water or moisture: use the controller only within the operating limits avoiding 
sudden  temperature  changes  with  high  atmospheric  humidity  to  prevent  formation  of 
condensation 

Warning:

 disconnect all electrical connections before any kind of maintenance.

Fit the probe where it is not accessible by the End User. The instrument must not be opened.

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell S.r.l.” 
(see address) with a detailed description of the fault. 

Consider the maximum current which can be applied to each relay (see Technical Data).

Ensure that the wires for probes, loads and the power supply are separated and far enough from 
each other, without crossing or intertwining. 

In  case  of  applications  in  industrial  environments,  the  use  of  mains  filters  (our  mod.  FT1)  in 
parallel with inductive loads could be useful. 

2. GENERAL DESCRIPTION

The 

XEV02D

  is  a  slave  module  designed  to  be  used  with  a  master  controller.  It  acts  as  a  pure 

transducer  controller,  receiving  a  regulatig  input  from  a  master  controller  and  transforming  it  in  the 
relative  modulating  signal  for  the  digital  unloader  valve.  The 

XEV02D

  module  is  equipped  with  a 

temperature  probe  input  (which  could  be  an  NTC86K  or  NTC/PT1000  type).  It  has  a  digital  output 
(relay) which is used for alarm or as compressor output, an open collector output which can be used 
as alarm output and a modulating output (TRIAC type) to drive the unloader digital valve. There are 
also two configurable digital inputs, the first one is free of  voltage and the other ones is isolated in 
order to simplify connections (high voltage input). The display permits to see the value of temperature 
or  the  control  input  value  or  the  output  activation  value  in  percentage.  The  local  keyboard  allows 
programming the instrument without any other devices. To complete instrument equipment, a RS485 
serial port permits to connect the 

XEV02D

 to any modbus network and an HOT-KEY port to change 

configuration are present. 

3. WIRING CONNECTIONS

Please use the following scheme to make the right wirings. 

NOTE: 

-

The DIGITAL valve must be connected directly to terminals 23 and 24

-

The TRIAC output will work at the same power supply of the module

-

The high voltage digital input (D.I.2, terminals 8-9) works at the same voltage of the 

Power Supply 

4. ALARM FUNCTIONS

4.1

 

HIGH TEMPERATURE ALARM CONTROL (TRIP) 

DLT alarm is generated when DLT probe (P2) temperature is: 

T >= dLt 

Until alarm delay time (

dLd

) is active the total compressor capacity will be limited to 

Cdd

If alarm delay time (

dLd

) is disabled or elapsed: 

-

General alarm LED and digital output set as alarm (

oAx=ALr

) is activated 

-

If a digital output is set as compressor output (

oA1=CPr

) this is also deactivated.

-

If a digital output is set as demand output (

oA1=dmd

) this is also deactivated.

-

Solenoid valve control output deactivates.

-

Buzzer activates (depending on the 

bEn

 parameter).

Alarm reset is automatic and happens when both of the following conditions occur:  
-

Temperature measured by probe will be 

T <= dLt – dth

 and 

-

Upon expiry of the stand-by timer for compressor head cooling (par. 

dCt

).

In any case the regulation always re-starts after expiring both anti-short cycle timers 

2on

 (minimum 

time  between  two  consecutive  compressor  activations)  and 

2oF

  (minimum  time  between  one 

compressor stop and next start-up).  
Press any key to deactivate the buzzer at any time. 

4.2

 

HIGH TEMPERATURE ALARM CONTROL (LOCKOUT) 

DLT lockout alarm occurs after 

a dLn number of DLT alarms

 during the time interval (in hours) 

dLi

The logic behind this control is as follows: 
-

if 

dLn=0

, this control is deactivated (whatever the value of 

dLi

);

-

if 

dLn≠0 

and 

dLi=0

, block occurs after a number of DLT alarms equal to 

dLn

 is had;

-

if 

dLn≠0 

and 

dLi≠0

, block occurs after a number of DLT alarms equal to 

dLn

 in time interval in 

dLi 

(expressed in hours). 

When the above-described condition occurs: 
-

General alarm LED and digital output set as alarm (

oAx=ALr

) is activated.

-

If a digital output is set as compressor output (

oA1=CPr

) this is also deactivated.

-

If a digital output is set as demand output (

oA1=dmd

) this is also deactivated.

-

Solenoid valve control output deactivates.

-

Buzzer activates (depending on the 

bEn

 parameter).

Alarm reset is 

manual 

by means of controller on-off procedure or a special Modbus control. 

In any case the regulation always re-starts after expiring both anti-short cycle timers 

2on

 (minimum 

time  between  two  consecutive  compressor  activations)  and 

2oF

  (minimum  time  between  one 

compressor stop and next start-up).  
Press any key to deactivate the buzzer at any time. 

4.3

 

LOW TEMPERATURE ALARM CONTROL (LOCKOUT) 

If the temperature probe P2 measures a lower value than the one set in parameter 

ALL

 and if this 

condition persists for longer than the value set in parameter 

dLL

-

General alarm LED and digital output set as alarm (

oAx=ALr

) is activated.

-

If a digital output is set as compressor output (

oA1=CPr

) this is also deactivated.

-

Solenoid valve control output deactivates.

-

Buzzer activates (depending on the 

bEn

 parameter).

Alarm  reset  is 

manual 

by  means  of  controller  on-off  procedure  or  by  using  a  special  MODBUS 

command. 
In any case the regulation always re-starts after expiring both anti-short cycle timers 

2on

 (minimum 

time  between  two  consecutive  compressor  activations)  and 

2oF

  (minimum  time  between  one 

compressor stop and next start-up).  
Press any key to deactivate the buzzer at any time 

4.4

 

MISSING REGULATION SIGNAL CONDITION (TRIP) 

A missing regulation signal alarm is generated if the control signal drops below the value set in the 
parameter 

dSL

 (percentage value, if 

dSL=0

 this control is deactivated) and if this condition persists 

longer than 

dEr

 seconds. 

If so: 
-

General alarm LED and digital output set as alarm (

oAx=ALr

) is activated.

-

If a digital output is set as compressor output (

oA1=CPr

) this is also deactivated.

-

Solenoid valve control output deactivates.

-

Buzzer activates (depending on the 

bEn

 parameter).

Summary of Contents for XEV02D

Page 1: ...LARM CONTROL TRIP DLT alarm is generated when DLT probe P2 temperature is T dLt Until alarm delay time dLd is active the total compressor capacity will be limited to Cdd If alarm delay time dLd is disabled or elapsed General alarm LED and digital output set as alarm oAx ALr is activated If a digital output is set as compressor output oA1 CPr this is also deactivated If a digital output is set as d...

Page 2: ...essed for 3 sec 2 The instruments will show the first parameter present in the Pr1 menu 6 4 ACCESS TO PR2 PARAMETER MENU To access to Pr2 menu 1 Enter the Pr1 menu 2 Select Pr2 parameter and press SET 3 The PAS label will be shown then 0 with 0 blinking Insert 321 password through UP and DOWN buttons then press SET to confirm 6 5 CHANGE A PARAMETERS VALUE To change any parameter value follow this ...

Page 3: ...on max stored value is 19h59min 12 1 ALARMS ARCHIVE ERASING All saved alarms can be deleted by keeping the ALARM SET key pressed for 5 sec when into ALARM MENU The display will show the rSt label flashing for 3 sec and then the default display visualization will be restored Lod variable NOTE All saved alarms can be also deleted via special MODBUS command 13 DISPLAY MESSAGES Mess Cause Outputs A02 ...

Page 4: ...in 5 Pr1 2oF Delay between DG compressor switch off and start up 0 to 999 sec 120 Pr1 odo Power on regulation delay 0 to 999 sec 5 Pr1 dSL Lower limit for control signal in percentage 0 function disabled 0 to 100 0 Pr2 Si0 Minimum input value in percentage 0 to 100 0 Pr2 Si1 Maximum input value in percentage 0 to 100 100 Pr2 PMi Minimum load in percentage 0 to 100 0 Pr2 PMA Maximum load in percent...