Direct Vent 

Wall Furnace

MoDels

DV-210-sG

DV-215-sG

this appliance  may be installed in an after-

market, permanently located, manufactured 

home (usa only), or mobile home, where not 

prohibited by state or local codes.
this appliance is only for use with the type of gas 

indicated on the rating plate.  this appliance is 

not convertible for use with other gases, unless 

a certified kit is used.

installation instructions

anD

oWner's Manual

WarninG:    if  not  installed,  operated,  and 

maintained in accordance with the manufactur-

er's instructions, this product could expose you 

to substances in fuel or from fuel combustion 

which can cause death or serious illness.

installer:  leave this manual with the appli-

ance.

consumer: retain this manual for future refer-

ence.

—  Do not store or use gasoline or other flamma

-

ble vapors and liquids in the vicinity of this or 

any other appliance.

—  WHat to Do iF You sMell Gas

  •  Do not try to light any appliance.

  •  Do not touch any electrical switch; do not 

use any phone in your building.

  •  Immediately call your gas supplier from a 

neighbor’s  phone.  Follow  the  gas  suppli-

er’s instructions.

  •  If you cannot reach your gas supplier, call 

the fire department.

—  installation and service must be performed by 

a qualified installer, service agency or the gas 

supplier.

WarninG: if the information in these instruc-

tions are not followed exactly, a fire or explosion 

may result causing property damage, personal 

injury or loss of life.

Page 1

Summary of Contents for DV-210-SG

Page 1: ...th or serious illness Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store or use gasoline or other flamma ble vapors and liquids in the vicin...

Page 2: ...ifications 6 Gas Supply 7 Clearances 8 Installation Instructions 8 9 Thermostat Location 10 Lighting Instructions 11 Pilot Flame Characteristics 12 Main Burner Flame Characteristics 12 Maintenance 12...

Page 3: ...ied service person More frequent cleaning may be required due to excessive lint from carpeting bedding materials etc It is impera tive that control compartments burners and circulating air passageways...

Page 4: ...g vehicle trailer or area Finally let the service man and firefighters check for escaped gas Have them air out the area before you return Properly trained LP Gas service people should repair the leak...

Page 5: ...uiredinaccordance with the above provisions shall comply with NFPA 720 and be ANSI UL 2034 listed and IAS certified 3 SIGNAGE Ametalorplasticidentificationplateshallbe permanently mounted to the exter...

Page 6: ...erformed only by a qualified agency The term qualified agency meansanyindividual firm corporationorcompanywhicheitherin person or through a representative is engaged in and is responsible for a the in...

Page 7: ...that a drip line be installed near the gas inlet This should consist of a vertical length of pipe tee connected into the gas line that is capped on the bottom in which condensation and foreign partic...

Page 8: ...nimum wall depth is 4 1 2 114mm and maximum wall depth is 13 330mm The use of tubes not supplied by the manufacturer result in unsatisfactory performance The furnace is to be located on an outside wal...

Page 9: ...l Remove 5 127mm diameter air inlet tube from collar of air drop assembly 2 Attach3 76mm diameterflueoutlettubeontoflueoutletcollar oncombustionchamber Besure3 76mm diameterflueoutlet tube is placed a...

Page 10: ...d be Across the thermopile terminals 400 450 millivolts with ther mostat off Across the thermopile terminals 150 250 millivolts with ther mostat on Across the thermostat wires at the valve less than 3...

Page 11: ...to desired setting 16 CAUTION Pilot access cover must be kept tightly closed during operation To Turn Off Gas To Appliance FOR YOUR SAFETY READ BEFORE LIGHTING Warning If you do not follow these inst...

Page 12: ...ted After this the valve and orifice elbow can be removed as a unit Cleaning The Pilot Burner Cleaning of the pilot may be an annual necessity due to spiders After removing the supply tubing and orifi...

Page 13: ...properly size orifice 4 Pilot and main burner go out during normal operation a Check millivolts b Check for proper size of pilot flame c Check for defective or weak thermopile d Check input reduce as...

Page 14: ...HOLE 11 852098 NUT FOR ORIFICE FITTING 12 742134 BURNER ORIFICE DV 210 NAT 12 742133 BURNER ORIFICE DV 215 NAT 12 742297 BURNER ORIFICE DV 210 LPG 12 742282 BURNER ORIFICE DV 215 LPG 13 742038 ORIFICE...

Page 15: ...12433 10 0109 Page 15 PARTS VIEW...

Page 16: ...appliance is equipped with a three prong grounding plug for your protection against shock hazard and should be plugged directly into a properly grounded three prong re ceptacle Do not cut or remove th...

Page 17: ...ms Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...