background image

63 mm

THIS WAY 

UP WHEN 

WALL 

MOUNTING

TONE 

TONE TYPE 

TONE DESCRIPTION / APPLICATION 

 

         

                    

1. 

  970Hz 

    

O-O-O-O-O

 18

2. 

  800Hz/970Hz 

2Hz 

   

O-O-O-O-|

 1

3. 

 

 

800Hz - 970Hz @ 1Hz  

 

 

O-O-O-|-O

 1

4. 

 

 

970Hz 1s OFF / 1s ON  

 

 

O-O-O-|-| 

1

5.     970Hz, 0.5s / 630Hz, 0.5s  

 

O-O-|-O-O

 

4

6. 

 

 

554Hz, 0.1s / 440Hz, 0.4s (AFNOR NF S 32 001) 

O-O-O-|-|

 1

7. 

 

 

500 - 1200Hz, 3.5s / 0.5s OFF (NEN 2575:2000) 

O-O-|-O-|

 1

8.    

420Hz 0.625s ON / 0.625s OFF (Australia AS1670 Alert tone)

 

O-O-|-|-|

 9 

9.    

500 - 1200Hz, 0.5s / 0.5s OFF x 3 / 1.5s OFF (AS1670 Evacuation)

 

O-|-O-O-O

 1

10. 

 

 

550Hz / 440Hz @ 0.5Hz 

 

 

O-|-O-O-|

 19

11. 

 

 

970Hz, 0.5 ON / 0.5s OFF x 3 / 1.5s OFF (ISO 8201) 

O-|-O-|-O

 1

12. 

 

 

2850Hz, 0.5s ON / 0.5s OFF x 3 / 1.5s OFF (ISO 8201) 

O-|-O-|-|

 1

13. 

 

 

1200Hz - 500Hz @ 1Hz (DIN 33 404) 

 

O-|-|-O-O

 1

14. 

  400Hz 

    

O-|-|-O-|

 18

15. 

 

 

550Hz, 0.7s / 1000Hz, 0.33s 

 

 

O-|-|-|-O

 1

16. 

 

 

1500Hz - 2700Hz @ 3Hz 

 

 

O-|-|-|-|

 1

17. 

  750Hz 

    

|-O-O-O-O

 1

18. 

  2400Hz 

    

|-O-O-O-|

 1

19. 

  660Hz 

    

|-O-O-|-O

 18

20. 

 

 

660Hz 1.8s ON / 1.8s OFF 

 

 

|-O-O-|-|

 19

21. 

 

 

660Hz 0.15s ON / 0.15s OFF 

 

 

|-O-|-O-O

 19

22. 

 

 

510Hz, 0.25s / 610Hz, 0.25s 

 

 

|-O-|-O-|

 1

23. 

 

 

800 / 100Hz 0.5s each (1Hz) 

 

 

|-O-|-|-O

 1

24. 

 

 

250Hz - 1200Hz @ 12Hz 

 

 

|-O-|-|-|

 1

25. 

 

 

500Hz - 1200Hz @ 0.33Hz 

 

 

|-|-O-O-O

 1

26. 

 

 

2400Hz - 2900Hz @ 9Hz 

 

 

|-|-O-O-|

 18

27. 

 

 

2400Hz - 2900Hz @ 3Hz 

 

 

|-|-O-|-O

 18

28. 

 

 

800Hz - 970Hz @100Hz 

 

 

|-|-O-|-|

 1

29. 

 

 

800Hz - 970Hz @ 9Hz  

 

 

|-|-|-O-O

 1

30. 

 

 

800Hz - 970Hz @ 3Hz  

 

 

|-|-|-O-|

 1

31. 

 

 

800Hz, 0.25s ON / 1s OFF 

 

 

|-|-|-|-O

 1

32. 

 

 

500Hz - 1200Hz, 3.75s / 0.25s OFF (AS2220)  

|-|-|-|-|

 8 

SIZE C

SIZE C

SIZE C

SIZE AA

SIZE AA

SIZE AA

Wireless Sounder / Visual Indicator 

Installation Guide

1 Pre installation

4 Power device 

Cut out section

(shaded area)

To unlock the device, 

insert a 1.5 mm allen key  

to depress the locking clip 

and turn anticlockwise to 

release.

Unclip the battery retaining plate from the wireless module. 

When fitting / replacing batteries; observe correct polarity, 

using only specified batteries. 

Connect the power jumper across the PIN header.

3 Fix mounting plate

2 Components

Part no        Product description

device

unpowered

(pins unlinked)

device

powered

(both pins linked) 

!

Installation must conform to applicable local installation 

codes and should only be installed by a fully trained 

competent person. 

Ensure that the device is installed as per the site survey.

The use of a non-metallic spacer should be considered if 

mounting the device on to a metal surface.

Do NOT Press the Log On button on a pre-programmed device, 

as this will cause communication with the Control Panel to be 

lost. Should this happen, delete the device from the system 

and add it back on.

This device contains electronics that may be susceptible to 

damage from Electrostatic Discharge (ESD). Take appropri-

ate precautions when handling electronic boards.

Sounder/visual indicator variant 

Wireless module

Mounting plate

1

4

2

Remove the mounting plate by turning the device 

ANTICLOCKWISE, to release it from the mounting plate.

3

5 Optional device locking

6 Configuration

To lock the sounder into 

the wireless module, 

 

remove the cut out section 

as shown. 

Use both mounting holes.

Use suitable fasteners and fixings.

Once powered, reassemble the device.

When wall mounting, ensure the mounting plate is fitted in the 

orientation shown.

See the Specification section for compliance information.

CPR

FC-171-001

FC-171-002

FC-172-001

FC-172-002

FC-173-002

FC-173-003

FC-173-004

FC-178-002

FC-178-003

FC-178-004

White Wireless Sounder Base Only   

     

[2]

Red Wireless Sounder Base Only   

     

[2]

White Sounder Only 

 

 

     

[1]

Red Sounder Only 

 

 

     

[1]

Red Sounder Visual Indicator Only   

     

[1]

Amber Sounder Visual Indicator Only  

     

[1]

Clear Sounder Visual Indicator Only  

     

[1]

Red Visual Indicator Only

Amber Visual Indicator Only

Clear Visual Indicator Only

1

4

2

Battery retaining plate

3

Example shown:

FC-172-001

FC-171-001

©2021 EMS Ltd. All rights reserved                                                                      Page 1 of 2 

TSD047-99  Iss 16  23/11/2021   AJM

The device’s loop address is configured within the user interface’s 

menu structure. 

Refer to the programming manual for full programming details. 

Free to download from 

www.emsgroup.co.uk

FireCell = MK98

Fusion = TSD062

WZM = TSD143