background image

ENDA ETM442 DIGITAL TIMER 

Thank you for choosing ENDA ETM442 digital timer. 

Supply Voltage

Order Code

230V AC  +%10 -%20

ETM442

24V AC  ±%10

ETM442-24AC

    * 48x48mm sized. 
    * 2x4 digits display.
    * 

.  

    * Selectable 9 different time bases between 

  

    * S

 

    

    

Easy to use by front panel keypad

0-99.99s and 0-9999h. 

electable PNP or NPN sensor type.

* Selectable up/down counting direction for time.    

    * Adjustable Minimum On and Off times for pulses.
    * Operation with or without memory for each output type.
    * 9 different output types.
    * Bottom display can be adjusted to show time unit or set value. 
    * Selectable functional reset.
    * Parameter access protection on 3 levels.

* Easy connection by removable screw terminal.

    * Having CE mark according to European Norms. 

ENDA

DIGITAL TIMER

PV

SV

OUT

SET

PRESET

RESET

ETM442

 Input types can be adjusted as PNP or NPN in programming mode. 
 Minimum On and Off times for input pulses can be adjusted between 5 and 100ms. 
 For PNP input types, active level is 5 to 30V pulse,
 For NPN input types, active level is 0 to 2V pulse.

 START input

 GATE input

 RESET input

INPUTS

 1/5

ETM442-E-03

Read this document carefully before using this device. The guarantee will be expired by 
damaging of  the device if you don't attend to the directions in the user manual. Also we don't 
accept any compensations for personal injury, material damage or capital disadvantages.  

ENVIRONMENTAL CONDITIONS

 Height

 Max. 2000m

 Ambient/storage temperature

 Max. relative humidity

0 ... +50

 

°C/-25 ... +70°C  (with no icing) 

Rated pollution degree

TECHNICAL SPECIFICATIONS 

80% up to 31

decreasing linearly  50% at 40

°C °C

According to EN 60529                Front panel :    IP60
                                                       Rear panel  :    IP20

 Do not use the device in locations subject to corrosive and flammable gases.

 Supply

 230V AC +%10 -%20, 50/60Hz or 24V AC ±%10, 50/60Hz or optional 9-30V DC SMPS module.

 Power consumption

Max. 5VA
2.5mm² screw-terminal connections

 Wiring
 Date retention 
 EMC
 Safety requirements

 EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B for the EMC standard)  

EEPROM (Min. 10 years)

 EN 61010-1: 2001 (pollution degree 2, overvoltage category II)

ELECTRICAL CHARACTERISTICS

HOUSING

 Housing type

 Suitable for flush-panel mounting according to DIN 43 700.

 Dimensions

 W48xH48xD87mm 

 Weight

 Approx. 210g (after packing)

 Enclosure material

 Self extinguishing plastics 

 While cleaning the device, solvents (thinner, benzine, acid etc.) or 

corrosive materials 

must not be used.

Accuracy

 ± % 0.1 ± 20ms  

OUTPUTS

 Control output (OUT)

 Relay : 250V AC, 2A (for resistive load), NO+NC
 Open collector output (S.S. OUT): Max. 30V DC, 100mA  

 Auxiliary power supply 

 12V DC, max. 50mA (without regulation)

  Life expectancy for relay

 Mechanical  30.000.000 operation; Electrical 300.000 operation

  Note : Relay and S.S.OUT outputs are in synchronization . When OUT relay is energized S.S. OUT transistor goes into saturation.
          

9-30V DC SMPS module

ETM442-12AC