INSTALLATION AND MAINTENANCE INSTRUCTIONS 

MAGDUOSRSQ

 MAGDUO Wall Sounder Red 

MAGDUOSWSQ

 MAGDUO Wall Sounder White 

26-1661-01

General Description 

The MAGDUO Wall Sounder unit allows for audible indication when the system enters an alarm condition. This 
device  is  compatible  with  the  MAGDUO  2-wire  range  of  Fire  Alarm  equipment  and  comprises  a  2-wire  zone-
powered  sounder.  This  device  may  be  installed  on  the  same  zone  as  the  FlexiPoint  detector/sounder  and 
associated MAGDUO devices.  

Before Installation 

The  Sounder  must  be  installed  in  compliance  with  the  control  panel  installation  manual.  The  installation  must 
also meet the requirements of any local authority. For maximum performance the sounder should be installed in 
compliance to BS5839 Pt1 : 2017. 

Spacing 

It is recommended spacing of sounders in accordance with BS5839 Pt1. For more specific information regarding 
sounder spacing, placement and special applications please refer to BS5839 Pt1 : 2017. 

Device Installation 

Surface Mounting 

Fix the surface back box to a flat vertical surface using at least two of the four mounting 
holes provided.  The back box may be drilled to allow cable access as required. A 20mm 
hole is  already provided  at the rear. Zone cabling may  be connected to the terminals  in 
the back box. 

Flush Mounting 

The  MAGDUO  Wall  Sounder  may  be  flush  mounted  utilising  the  optional  adaptor 
plate,  combined  with  any  standard  single  gang  flush  mounting  back  box  (with  a 
minimum internal depth of 47mm).  

After installing the back box securely, attach the adaptor plate using the two screws 
provided, and terminate your cables directly into a flying terminal block.

 

 

Installation 2nd Fix 

Once all testing has been carried out on the cabling and ‘continuity & integrity’ has 
been proven, the MAGDUO Wall Sounder front may be installed.  

Connect the wires from the MAGDUO Wall Sounder front in to the appropriate terminals 
in the back box 

according to the wire colours

. The MAGDUO Wall Sounder front may then 

be installed by locating the upper mounting 

hooks

 into the back box and then pushing the 

unit gently home. The single fixing screw may then be tightened as required.   

Please remember that all high voltage testing must be carried out before the installation 
of the MAGDUO Wall Sounder front unit, otherwise the electronics will be damaged. 