background image

 

Summary of Contents for SPECLINE PRO 700

Page 1: ......

Page 2: ...NNECTION PANEL POWER SUPPLY UNIT 11 CONNECTION PANEL BATTERY MODULE 11 UNPACKING 11 SELECTING THE POINT OF INSTALLATION 11 FIRST START UP 12 SWITCHING THE POWER SUPPLY UNIT ON WITHOUT A MAINS CONNECTION COLD START 13 CONNECTING BATTERY MODULE 14 DESCRIPTION OF OPERATION OF THE UPS 15 GENERAL INFORMATION 15 PROTECTION DEVICES INCORPORATED IN THE POWER SUPPLY UNIT 16 COMMENTS REGARDING OPERATION 17 ...

Page 3: ...h water jackets pumps and solar systems The installation of a unit from this series guarantees correct operation for many hours in the event of a power outage thanks to the series connection of battery module modules In battery operation mode the Clear Digital Sinus CDS system enables the equipment to generate a sinusoidal waveform at output Specline series UPS units have been designed in such a w...

Page 4: ... will generate a visual and sound alarm Apart from excellent performance and reliability SPECLINE 700 UPS units feature these great advantages the CLEAR DIGITAL SINUS system generates an input voltage with a perfect sinusoidal shape This solution offers more opportunities to connect devices that are sensitive to the supply voltage waveform e g laboratory equipment telecommunication devices synchro...

Page 5: ...s properly authorized pursuant to the valid legal regulations CAUTION The appliance should be operated and stored in conditions concordant with those set in the specification technical documentation CAUTION The device is completely disconnected from the mains only when the power lead is removed from the mains socket the plug is removed from the mains socket CAUTION The appliance is equipped with a...

Page 6: ...TION There are no end user serviceable parts inside the UPS CAUTION SPECLINE PRO 700 UPS units are not intended for use directly with medical equipment life support systems or equipment that may affect health B Installation notes CAUTION SPECLINE PRO 700 UPS units may only be installed and maintained by qualified personnel CAUTION Before installation of the UPS OHS regulations for working with ele...

Page 7: ... specified in the manual Before connecting the device the technical condition of the connectors sockets and cables and of the appliance itself must be checked The device must be connected to a power circuit mains socket with three terminals phase neutral and grounding including a PE grounding conductor Failure to observe this requirement may result in electric shock To reduce the risk of electric ...

Page 8: ... at the UPS or in the building s electrical system terminals as this will remove the UPS s protective grounding There may be voltage on the UPS s output terminals even if the UPS is disconnected from the building s electrical system due to presence of power in the device s internal batteries Liquids and foreign bodies must not penetrate the UPS s housing WARNING This is a C2 category UPS If instal...

Page 9: ...es and may also be toxic To avoid the danger of fire and damage to the power system replace broken fuses with fuses of the same type and parameters Disconnect the device from the mains before cleaning Do not use liquid or sprayed cleaning agents Only qualified service technicians may disassemble UPS units E Transport and packaging remarks Exercise particular care when transporting the device Heavy...

Page 10: ...mbols a red diode continuously on mains power mode b red diode flashing every 2 5 sec battery charging mode c red diode flashing and an intermittent sound signal battery operation mode if the signal becomes continuous this means that the UPS will shut down in max 30 sec d red diode flashes rapidly and the sound signal reaches a high pitch an overload or short circuit condition 2 Main switch in the...

Page 11: ...n of the power supply unit immediately upon delivery Although the product is solidly packaged the appliance could have been damaged due to shocks experienced during transport If any damage is determined inform the carrier or seller SELECTING THE POINT OF INSTALLATION When selecting the place and method of installation you should take into consideration the high weight of the appliance The UPS shou...

Page 12: ...ly FIRST START UP NOTE Once unpacked the appliance should be placed in its working location and connected to the mains Next switch the power supply unit on by means of a switch on the front panel in order to charge the batteries The batteries will be fully charged after approx 10 48 h depending on their capacity and existing charge this fact will be duly signalled by the diode Now you can proceed ...

Page 13: ...gnalled by the diode switching off briefly approx every 2 5 seconds Please keep in mind that when the power supply unit is working in battery mode and the red diode starts to flash and the sound signal becomes continuous the device will shut down in no more than 30 sec SWITCHING THE POWER SUPPLY UNIT ON WITHOUT A MAINS CONNECTION COLD START If the mains voltage parameters are incorrect the unit ca...

Page 14: ...ly unit are delivered with fuses For transport and connection the fuses should be removed from their sockets They should be installed only after all the connections are made Fig 3 Connection system CAUTION Connecting excessively high voltage or wrong polarity may result in the necessity to return the UPS to the service CAUTION A special attention should be paid to the polarity of connections plus ...

Page 15: ... no input voltage is detected the unit immediately switches to battery operation The level of discharge of the battery during battery operation is indicated by a sound signal In the final phase of battery discharge the signal becomes continuous thereby indicating that the UPS will switch off shortly at full power this is approx 30 seconds while at lower power levels a somewhat longer period Once m...

Page 16: ... the rapid flashing of the diode A short circuit is also signalled by a very quick intermittent sound Because the battery is connected externally it is not built in additional protection devices have been utilised a Battery overvoltage protection The power supply unit is protected against the connection of a battery with a voltage greater than nominal In this case the car fusible cut out will burn...

Page 17: ...cation of the power supply unit The set contains one spare mains fuse and one spare battery fuse INTERACTION WITH ELECTRICAL GENERATORS EVER SPECLINE PRO 700 power supply units are VFD class devices that synchronise themselves with the mains voltage The unit has been designed to tolerate voltage fluctuations in the range of 184 264 V and changes in the frequency of 5 Hz in relation to the model fr...

Page 18: ...rotect human health and the natural environment against the negative effects brought about by the presence of hazardous materials and components and the improper storage and processing of such equipment Act of 29 July 2005 on Waste Electric and Electronic Equipment Article 22 1 Point 1 2 The crossed out waste container symbol means that in the European Union a used product should be handed over to...

Page 19: ...thresholds Mains UPS 184 264 V 2 OUTPUT Rated output voltage 230 V AC Output voltage range and tolerance normal mode 184 264 V 2 Output voltage range and tolerance battery mode 230 V 5 Shape of output voltage battery mode normal mode Sine wave same as input Output voltage rated frequency 50 Hz Output frequency range and tolerance mains operation mode Synchronously Output frequency range and tolera...

Page 20: ...onnection Battery overcurrent Automotive Fuse type UNIVAL 19 mm 40 A ACCESSORY AND EXTRA FUNCTIONS Power supply connection screw terminals max 4 mm2 cable Output connection number and type of sockets screw terminals max 4 mm2 cable Signalling Acoustic and optical CERTIFICATION Declarations CE Standards PN EN 62040 1 2009 PN EN 62040 2 2008 Note The manufacturer reserves the right to modify the abo...

Page 21: ...defects shall be determined by the manufacturer The guarantee shall not cover appliances with mechanical damage that were improperly maintained or used or that were modified in any way by the user In the event of any problems with the operation of the UPS first check the connection of the installation and battery safety switches and technical condition of the batteries Replace the safety switches ...

Reviews: