background image

Description

Hydrogen detector-transmitter E2611-H2

 is intended for early detection of

leakages or accumulation of hydrogen in confined spaces.
The instrument is based on fully calibrated and  temperature compensated
semiconductor  metal-oxide  (MOS)  gas  sensor  with  high  repeatability,
stability and long lifetime. The sensor exhibits high sensitivity and selectivity
to methane. Pellistor (catalytic bead) sensor is available as an option.
E2611  provides  two  independent  analog  outputs  OUT1  and  OUT2,  user-
selectable to 4-20 mA or 0-10 V, proportional either to gas concentration or
temperature.  RS485  Modbus  RTU  digital  communication  interface  allows
easy  instrument  configuration  and  integration  into  various  automation
systems.  Two  relays  RE1  and  RE2  with  closing  contacts  can  be  used  to
switch 24 V or 230 V powered alarm sirens, ventilation fans, shut-off valves
or other actuators.

Safety requirements

Always adhere to the safety provisions applicable in the country of use. Do
not perform any maintenance operation with the power on. Do not let water
or foreign objects inside the device.

Operating conditions

The  device  should  be  used  in  explosion-safe  (non  ATEX  -rated)  indoor

areas at the atmospheric pressure ±10%, <95 %RH, without condensation,
and  temperature  within  the  range  -30...+70  °C  for  MOS-type  devices  /
-20...+60 °C for pellistor type.

Metal-oxide and pellistor sensors cannot properly operate in a zero or low

oxygen  content  atmosphere.  Normal  ambient  oxygen  concentration  is
recommended.

Avoid  exposure  to  highly  corrosive  gases  (H

2

S,  SO

2

,  HCl,  Cl

2

  etc),  and

volatile silicon containing materials.

Avoid mechanical shock or strong vibrations.

Avoid sources of electromagnetic interference

Installation and connections

The gas detector should be mounted on a wall at a place located not more
than 5 m from possible gas leakage source and not very close to ventilation
openings, with the sensor pointing downwards. As hydrogen is much lighter
than  air,  it  is  advisable  to  place  the  device  near  the  ceiling.  The  device
should be available for maintenance and repair.
1.  Detach  the  base  of  the  enclosure  by  gently  pulling  along  four  guiding
pins.
2. Fix the base on the wall with two screws. (see drawing below).

85

37

8

5

63

3. Connect power supply and external devices to the terminal blocks on the
PCB according to the connection diagram below.

To power the instrument from an external 24 VDC source, connect terminals
0 V and +U to  the  source. If an integrated  mains power supply module is
used, connect terminals L and N to the mains.
To use analog outputs, connect the terminals OUT1 and/or OUT2 and 0 V
to the input of the secondary instrument (indicator or controller).

NB!

 The outputs are not galvanically isolated from 24 V power supply and

share  common  0  V.  Allowed  load  resistance  limits  are  stated  in
Specifications table.
The  type  of  each  analog  output  can  be  independently  selected  with  the
appropriate jumper (J1 for OUT1 and J2 for OUT2). With jumper open, the
output type is 4-20 mA. With jumper closed, the output type is 0-10 V.

To  use  relay  outputs,  connect  the  chosen  actuators  to  the  relay  terminals
RE1 and/or RE2.

NB! 

Actuator short-circuits shall be avoided, to protect the instrument relays

use external fuses or safety switches.

4. Turn on the power. It may take up to five minutes after switching on for
the  sensor  to  stabilize.  During  this  period  relays,  analog  outputs  and
Modbus interface are off. A LED placed on the PCB of the device allows to
control the connection process. The LED response to different processes is
presented in the table below.

Process

LED mode

Sensor heating period

Blinking 0.5 Hz (50% on, 50% off)

Sensor absence or malfunction

Blinking 0.5Hz (90% off, 10% on)

Relay 1 turned on

Blinking 1 Hz (50% on, 50% off)

Relay 2 turned on

Blinking 2 Hz (50% on, 50% off)

Modbus response

The signal is modulated with short onoff
pulses, even single Modbus cycle is traceable*

Normal measurement

Continuous light

5. Push enclosure to the base.

Operation

For  best  stability  the  gas  detector  should  be  powered  permanently.  If  the
instrument is left for a long time in unpowered state, then after initial power-
on  the  metal-oxide  gas  sensor  needs  some  time  to  heat  up  and  burn
adsorbed  contaminants.  So  for  first  tens  of  seconds  of  few  minutes  an
alarm  activation  may  be  possible.  After  this  heating-up  period  the
instrument turns into normal mode.

When the concentration of the detected gas reaches the LOW alarm level,
the  control  LED  starts  blinking  and  the  buzzer  starts  beeping  with  1  Hz
frequency.  When  the  HI  alarm  level  is  reached,  the  frequency  of
blinking/beeping  is  2  Hz.  The  alarm  signal  turns  off  automatically,  if  gas
concentration decreases to 80% of the alarm setpoint.

Configuring

Gas  detector  E2611  shares  all  functionalities  of  the  PluraSens®
multifunctional transmitter platform. The features and options include:
- digital output change rate limiting filter
- digital integrating (averaging) filter
- temperature measurement channel with internal sensor
- free assignment of each analog output to chosen parameter
- flexible setting of analog output scales for each output
- output shift and slope adjustment for calibration
- free assignment of each of two relays to chosen parameter
- several relay control logic modes (HI or LO with hysteresis, U or П)
- switch delays and minimum on/off state durations for each relay
- Modbus controlled forced state option for analog outputs and relays.
E2611  can  be  configured  through  its  RS485  interface  by  Modbus  RTU
commands. A standard configuration kit includes Model E1087 USB-RS485
converter and E26XX Configurator software. Please contact your Seller or
the Manufacturer for more information.

Return to default settings

To reset the device’s Slave ID, baudrate and sbit number to factory settings,
proceed as follows:
1. De-energize the device

2. Connect the J3 jumper

3. Turn on the device

4. De-energize the device

5. Disconnect the J3 jumper

6. Turn on the device

Calibration

E2611-H2 has been calibrated by Manufacturer with standard gas mixtures
before delivery. The semiconductor gas sensor exhibits high stability and >
5  years  lifetime.  However,  as  the  gas  sensor  is  directly  exposed  to
environment, the instrument requires at least annual field recalibration with
a  portable  calibration  kit.  The  catalytic  sensor  is  more  sensitive  to  the
environment and requires calibration every 3...6 months.
The calibration should be performed by qualified specialist. Please contact
your dealer for more information.

Warranty

This  product  is  warranted  to  be  free  from  defects  in  material  and
workmanship for a period of one year from the date of original sale. During
this warranty period Manufacturer will, at its option, either repair or replace
product that proves to be defective. This warranty is void if the product has
been  operated  in  conditions  outside  ranges  specified  by  Manufacturer  or
damaged  by  customer  error  or  negligence  or  if  there  has  been  an
unauthorized modification.

Delivery set

– Methane detector-transmitter E2611-H2
– Mounting accessories: 2 screws and 2 plastic dowel plugs

Input 1 4-20 mA / 0-10 V

Input 2 4-20 mA / 0-10 V

0V / GND

Controller

OUT1
OUT2
0V

A
B

RS485

+U = 11...30 VDC

L
N

90...265 VAC

RE1

RE2

Fieldbus

S

PSU

24 VDC

+

-

J1 J2

230 VAC

J3

Control LED