background image

CAUTION!

 

DO NOT INSTALL, USE OR OPERATE THIS EQUIPMENT UNTIL THIS MANUAL HAS BEEN READ

AND UNDERSTOOD. READ AND SAVE THESE INSTRUCTIONS FOR FUTURE USE.

FORM ASX-31003-C, Page 1

The ASX Pressure control system uses the flexibility of our highly efficient EC motors and controllers in 
conjunction with accurate pressure measuring equipment and a versatile setpoint control unit to maintain a 
user-defined duct static pressure.

The system consists of the following three components:

NOTE:

  Fan must be sized appropriately for the system it is connected to as well as all intended system 

 configurations.

NOTE:

  The ACU can be used to manually control the output of the motor independently from the rest of the 

 

pressure control system. This is beneficial for system balancing as well as for fine tuning of the setpoint 

 

control system. Refer to the ASX ECM - ACU Control Specification Sheet for details on how to operate 

 

the ACU controller.

A direct drive ASX fan with 

Eco-Drive motor and Automation 

Control Unit (ACU).

FORM ASX-31003-C

INSTALLATION, OPERATING AND MAINTENANCE INSTRUCTIONS

PRESSURE CONTROL OPTION WITH ECM MOTORS

A static pressure tap located in the 

duct, connected to an electronic 

pressure transducer.

A setpoint control with three 

character, digital display.

Air Specialties Express, 448 S. Main St., P. O. Box 930040, Verona, WI 53593-0040    Phone: (877)945-9175    Fax: (608)845-6504    www.airspecialties.com

Summary of Contents for ASX-31003-C

Page 1: ... NOTE The ACU can be used to manually control the output of the motor independently from the rest of the pressure control system This is beneficial for system balancing as well as for fine tuning of the setpoint control system Refer to the ASX ECM ACU Control Specification Sheet for details on how to operate the ACU controller A direct drive ASX fan with Eco Drive motor and Automation Control Unit...

Page 2: ...hat the tube is perpendicular to the airstream Attach flexible tubing to the outlet of the pressure tap Follow any applicable codes or requirements when choosing a flexible tube to use Pressure Transducer The purpose of the pressure transducer is to translate the duct pressure reading from the static pressure tap into a 0 10VDC signal The transducer can be field configured to operate within three ...

Page 3: ...his is intended to aide in the system balancing process More details on how to utilize the startup mode can be found in the ACU Control Specification Sheet If you wish to get the ACU out of startup mode simply power cycle the ACU 5 times while there is a positive voltage between 0 1 and 10 VDC present across the Signal and Common tabs Setpoint Control The purpose of the Setpoint control is to rece...

Page 4: ...er a passcode To access the Programming menu press and hold both the Prg muteand the Setbuttons until a 0 appears on the display Next press the arrow until the number 77 is displayed Finally press the Set key to enter the Programming menu By pressing the or arrows you can scroll through all of the parameters that are in the programming menu Pressing the Set button will allow you to enter and chang...

Page 5: ... for the pressure transducer in the table above Exit the programming menu to save the setting Reverse Direct acting mode The pressure control system is capable of maintaining negative or positive pressure in a duct system The typical application is a negative duct pressure as monitored at the inlet of an exhaust fan An application where positive duct pressure may be experienced would be at the out...