background image

Dokumentet kan ändras utan föregående meddelande. Subject to change without notice.

Functions and benefits 

•  Actilume is a control system based on the DALI protocol for 

maximum comfort and up to 75% energy conservation. This 
allows for a quick return on your investment.

•  Actilume is a plug and play system, which does not require the 

user to be specially trained in lighting control.

•  Actilume consists of three small special sensors in a single case, 

which are connected to a control unit with preprogrammed 
modes.

•  The two most common system functions, open plan office or 

office room, can be selected with a push button on the sensor 
unit. 

•  The light sensor is adapted and sensitive to visible light, like 

the human eye. This allows for automatic energy conservation 
by means of daylight adjustment, with no inconvenient side 
effects for the user.

•  The proximity sensor is very sensitive to human movement, 

and, in combination with an optional time delay, it is adapted 
for optimum performance in an office environment.

•  The lighting can easily be operated manually using one or 

more spring-return push buttons or pull switches. On/off and 
dimming functions are available. The same functions are also 
available with remote control. In this way, the light can always 
be adjusted to the user’s preferences.

•  In addition, Actilume can easily be programmed to additional 

special modes. These are specially designed in line with the 
latest lighting installation directive, EN 12464. These additional 
modes are easily programmable with a push of the IRT 9090/00 
IR transmitter. The Actilume system always switches to the 
maximum light level before daylight adjustment begins.

Deployment with service button on the sensor

Startup  

•  Requirement: Fixture correctly positioned, e.g. over the work-

space.

•  Power up the fixture. 
•  The light will switch on after approximately 15 seconds via the 

proximity sensor. 

Automatic setup of daylight adjustment to approx. 5–600 lux

 

1. Press down the button on the sensor for more than three se-
conds, or until the light flashes once. The light will now adjust 
to approximately 80 %. Make sure there is nothing preventing 
the sensor from reading a neutral surface.  
NOTE! No interference from daylight! 
2. After 30 seconds, the Actilume system will save the light 
level to a new reference value, or setpoint. This is indicated by 
a flashing light. The 30-second delay is there to allow time for 
the user and any items, such as a ladder, to be moved out of 
the way. 

Manual setting of daylight 

A new value can be saved by adjusting the light manually to 
the desired level using a pull cord, push button or IR transmit-
ter, then quickly pressing the service button within 30 seconds. 
Instructions for manually setting a new value with an IR trans-
mitter can be found on the following pages.

After automatic/manual setup 

One of the two standard modes (Mode 1 or Mode 2) can now 
be selected easily in Actilume with a press of the button on the 
sensor unit (press for less than 3 seconds). When the button is 
released, the light will flash once or twice.

1

e-Sense Actilume

Summary of Contents for e-Sense Actilume

Page 1: ...ing installation directive EN 12464 These additional modes are easily programmable with a push of the IRT 9090 00 IR transmitter The Actilume system always switches to the maximum light level before daylight adjustment begins Deployment with service button on the sensor Startup Requirement Fixture correctly positioned e g over the work space Power up the fixture The light will switch on after appr...

Page 2: ...ts to daylight Mode 1 one flash Office room Mode 2 two flashes Open plan office solution 1a The light is switched on when the proximity sensor is trig gered if the light level is too low Daylight adjustment active 1b The light is switched off when the proximity sensor is triggered if the light level is sufficient The light is switched on when daylight adjustment is active if the level drops below ...

Page 3: ...ex or the light level is wrong relative to the amount of daylight See illustration below Example Classroom A normal classroom has a large window area along one of the long walls The lighting closest to the window is connected to DALI 1 Window and is adjusted from 3 100 The fixtures in the centre and further inside the space are adjusted with an offset of 30 which compensates for the lower level of...

Page 4: ...measure ment The desired setpoint must be set with no interference from daylight Small sharp reflections from glass objects for example may affect the total value The sensor should be pla ced so that it reads the work surface in a workspace An ideal position would be directly above the centre of the desk but if the sensor is integrated into the end of a fixture it should be directed away from the ...

Page 5: ...0 0 Switched off Daylight adjustment workspace light only 6 Corridor Corridor Auto on off 15 60 min 20 On 7 Toilet Washbasin Toilet Auto till från 15 15 min toilets only 100 On Daylight adjustment washbasin only 8 Meeting room conference room with light scenarios Channel 1 Channel 2 Manual on Auto off 15 0 Switched off No daylight adjustment 9 Office landscape requires switching off centrally with...

Page 6: ...th 230 V Programming a preset mode 1 Press button MODE 2 Select a MODE from 1 to 10 3 Send the new information with a press of the green button Aim carefully at the IR receiver the sender has a very narrow beam to prevent accidental transmission to nearby systems The light will flash once to confirm the new setting Setting daylight level With the IRT 8099 IR transmitter Fagerhult order no 86155 it...

Page 7: ...mall movements 1 Press the TEST button once The light will adjust downwards First check that there are no people under the sensor Walk slowly towards the zone until the light flashes Reset the fun ction by pressing the TEST button again To check the mode that has been programmed e Sense Acti lume can indicate the mode that is selected 1 Press the MODE button once The light is first adjusted downwa...

Page 8: ... room with light scenarios Switched off 9 Office landscape requires switching off centrally with 230 V On 10 Office landscape according to EN 12464 requires switching off centrally with 230 V On Change level before switching off The low level background before switching off available in mo des 2 6 and 9 is preprogrammed to 20 In modes 4 7 and 10 the level only applies to DALI 2 and is selected to ...

Page 9: ...o install deploy and use NOTE Important Philips has updated the Actilume system and has added functions for Philips OccuSwitch DALI also This means that the programming tool IRT 8099 00 has been replaced with IRT 9090 00 with effect from 2014 All the original program ming functions are the same but the new functions cannot be programmed into Actilume generation 1 which Fagerhult uses in all its fi...