background image

F&F Filipowski sp. j.

Konstantynowska 79/81   95-200 Pabianice   

phone/fax: (+48 42) 215 23 83 / 227 09 71    POLAND

http://www.fif.com.pl   e-mail: fif@fif.com.pl

ELECTRICITY CONSUMPTION METER

three-phase

Do not dispose of this device to a garbage bin with other unsorted waste! 

In  accordance  with  the  Waste  Electrical  and  Electronic  Equipment  Act 
any  household  electro-waste    can  be  turned  in  free  of  charge  and  in  any 
quantity to a collection point established for this purpose, as well as to the 
store in the event of purchasing new equipment (as per the old for new rule, 
regardless of brand). Electro-waste thrown in the garbage bin or abandoned 
in the

 

bosom of nature pose a threat to the environment and human health.

LE-03

WARRANTY.

  The  F&F  products  are 

covered by a warranty of the 24 months   
from the date of purchase.  Effective only 
with  proof  of  purchase.  Contact  your 
dealeror  directly  with  us.  More  infor-
mation how to make a compliant can be 
found on the website:
www.fif.com.pl/reklamacje

Sealing

Meter number

Dimensions

Pulse output

The meter is equipped with pulse output SO+ - SO-. This allows 
you  to  connect  another  pulse  device  (SO)  that  reads  pulses 
generated by the meter.
No additional connected equipment is required for proper opera-
tion of the meter.

The  meter  has  sealable  input  and  output  terminal  covers 
to prevent  any attempts to bypass the meter.

The meter is marked with individual serial number allowing its 
unambiguous identification. The marking is laser engraved and 
cannot be removed.

Length of the SO+ SO- pulses depends on the load of the meter:

5÷40A

80 ms

75A

46 ms

45A

75 ms

80A

42 ms

50A

68 ms

85A

40 ms

55A

62 ms

90A

38 ms

60A

57 ms

95A

36 ms

65A

52 ms

100A

34 ms

70A

48 ms

Purpose

Functioning

LE-03 is a static (electronic) calibrated electricity meter of three-
phase alternating current in a direct system.

A special electronic system under the influence of flowing current 
and applied voltage in each phase generates pulses proportional 
to the energy drawn in the respective phase. Energy consumption 
in the phase is indicated by a flashing of corresponding LED (A, B, 
C). The sum of the three phase pulses is indicated by a flashing LED 
(800  pulses/kWh)  and  converted  into  energy  absorbed 
throughout the three-phase system. Its value is displayed by the 
segment LCD display. The fractional digit represent the decimal 
(.1 kWh = 100Wh).

Meter front description

LCD displa

y

kWh r

eading LED

met

er number

terminal c

ov

er

s

sealing poin

ts

A

B

C

imp/kWh

phase load LED

888888.8

- 1-

- 2-

- 3-

- 4-

5

9 0 8 3 1 2

5 9 1 7 0 2

Reviews: