background image

Part No: INST-AIRCURTAIN 

 Version 1.1

INSTALLATION & 
MAINTENANCE 
INSTRUCTION

S

SPECIFICATIONS

AIR CUR

T

AIN

1. GENERAL

1.1  It is important these Installation and Maintenance Instructions are fully adhered to.

1.2  Full details of the unit supplied are shown on the product nameplate.  

If in doubt about any detail, contact FANTECH or its agents for clarification.

1.3  Electrical installation must be carried out by suitably qualified and competent personnel in accordance 

with all current statuary requirements.

1.4  Any declarations made by FANTECH about product installation and safety,  

are dependent on the air curtain being used within installations which themselves meet the 
requirements of the relevant Standards and Directives of your region.

1.5  The air curtain must be installed in a dry, sheltered position and is not suitable for operating in 

temperatures above 40 °C.  The air curtain is not suitable in corrosive or explosive atmospheres.

1.6  The installer should provide easy access to the air curtain to facilitate future maintenance.

1.7  The installer should ensure the air curtain is adequately supported.

1.8  This product is not intended for use by young children or infirm persons unless they have been 

adequately supervised by a responsible person to ensure that they can use the product safely. Young 
children should be supervised to ensure that they do not play with the appliance.

AC1209 
AC1212 
AC1215

Model

Voltage 

(V)

Frequency 

(Hz)

Low Speed

High Speed

Current

(A)

Power

(W)

Outlet 

Velocity 

(m/s)

Noise 

(dB(A))

Current

(A)

Power

(W)

Outlet 

Velocity 

(m/s)

Noise 

(dB(A))

AC1209

230

50

0.956

220

15

54

1.2

276

18

57

AC1212

230

50

1.217

280

15

55

1.391

320

18

58

AC1215

230

50

1.522

350

12.5

54

1.896

436

14

57

  

These instructions must be read fully 

before commencing installation.

09/21

Page 1/4

Summary of Contents for AC1209

Page 1: ...tered position and is not suitable for operating in temperatures above 40 C The air curtain is not suitable in corrosive or explosive atmospheres 1 6 The installer should provide easy access to the air curtain to facilitate future maintenance 1 7 The installer should ensure the air curtain is adequately supported 1 8 This product is not intended for use by young children or infirm persons unless t...

Page 2: ...ection is via terminal block behind centre inlet grille 2 4 Means for electrical disconnections must be incorporated in the wiring installation in accordance with the relevant wiring and electrical regulations 2 5 Accessories 6 sets of bolts M8 x 60mm washers spring washers nuts 2 6 Installation position to follow the diagram below 2 7 Coverage height 3 5m To install air curtain horizontally 2 8 I...

Page 3: ...n addition all rotating items should be checked after 12 months 4 3 Bearings are of the sealed for life type and will not need a detailed inspection Model Dimensions mm Weight kg A B C D E F G AC1209 900 50 400 113 249 230 214 12 4 AC1212 1200 200 400 113 249 230 214 13 6 AC1215 1500 350 400 113 249 230 214 17 6 2 9 Other installation methods see following diagram 2 10 More than one air curtain un...

Page 4: ...fantechtrade co nz Australia 1300 387 587 New Zealand 0800 106 266 Scan the above QR code or visit www fantech com au warranty to view WARRANTY information online info fantechtrade com au 09 21 Part No INST AIRCURTAIN Version 1 1 Page 4 4 ...