DOMIcondens HE 26 C

700

400

330

196

85

115

200

INSTRUCTIONS FOR USE, INSTALLATION AND MAINTENANCE

Summary of Contents for DOMIcondens HE 26 C

Page 1: ... cod 3540Z852 Rev 01 08 2012 DOMIcondens HE 26 C 700 400 330 196 85 115 200 INSTRUCTIONS FOR USE INSTALLATION AND MAINTENANCE ...

Page 2: ...ating systems in the UK and to encourage the regular servicing of all central heating systems to ensure safety and efficiency Please see installation and servicing guidelines Ferroli declare that no substances harmful to health are contained in the appliance or used during the appliance manufacture B This symbol indicates Caution and is placed next to all safety warnings Strictly follow these inst...

Page 3: ...display detail 11 fig 1 shows the actual heating delivery temperature and during heating standby time the message d2 Domestic hot water DHW A DHW demand generated by drawing domestic hot water is indicated by flashing of the hot water under the tap on the display The display detail 11 fig 1 shows the actual DHW outlet temperature and during DHW standby time the message d1 Comfort A Comfort demand ...

Page 4: ...SHIP Incorrect installation can cause damage or injury for which the manufacturer declines any responsibility Installation of this unit must be carried out in strict compliance with the present instructions and the following regulations applicable in Great Britain Gas Safety Regulations Installations Use Local Building Regulations The Building Regulations Part L The Buildings Standards Scotland Co...

Page 5: ...and the circuit with the non return valve at least 3 m from the boiler or an expansion tank for domestic use For installation follow the instructions contained in the kit Replenishing water It is necessary to provide for replenishing of the water lost by the sealed system Refer to standard BS6798 for the methods of filling and replenishing water in sealed systems There must not be a direct connect...

Page 6: ...e following extraction suction systems Before installation check and carefully observe the above prescriptions Also comply with the provisions concerning the positioning of wall and or roof terminals and the minimum distances from windows walls vents etc Expansion A For fume exhaust pipes longer than 1 metre during installation take in account the natural expansion of the materials when the boiler...

Page 7: ... case in areas with different pressures The exhaust and intake must not be positioned on opposite walls C6X Intake and exhaust with separately certified pipes EN 1856 1 B2X Intake from installation room and wall or roof exhaust IMPORTANT THE ROOM MUST BE PROVIDED WITH APPROPRIATE VENTILATION Separate ducts Max permissible length 55 meq Baffle to use 0 15 meq Ø 45 15 35 meq Ø 50 35 55 meq No baffle...

Page 8: ...s to the setting q02 displaying the actually saved value by pressing the DHW buttons If the pressure gauge reading is different from the nominal maximum pressure pro ceed by increases decreases of 1 or 2 units of parameter q02 by pressing the DHW buttons the value is stored after each modification wait 10 seconds for the pressure to stabilise Press the heating button ref 3 fig 1 The card goes to t...

Page 9: ...thermostat fault Exchangers dirty clogged on water side Clean the exchangers Faulty water circulation Fume thermostat contact open Check the thermostat Wiring disconnected Check the wiring F05 Fume pressure switch fault contact fails to close Wrong card parameter setting Check the card parameter and modify it if necessary Fan fault Wiring disconnected Check the wiring Faulty fan Check the fan Card...

Page 10: ...lied 14 Safety valve 81 Ignition and detection electrode 16 Fan 114 Water pressure switch 19 Combustion chamber 126 Contact fume thermostat 20 Burner assembly 138 External probe not supplied 21 Main nozzle 139 Room unit not supplied 22 Burner 145 Pressure gauge water gauge 26 Combustion chamber insulation 193 Trap 27 Copper exchanger for heating and hot water 277 Recuperator 28 Fume manifold 278 D...

Page 11: ...ar 2 Max gas delivery G20 m3 h 2 64 Min gas delivery G20 m3 h 1 06 Burner nozzles G31 no x Ø 11 x 0 79 Gas supply pressure G31 mbar 37 Max gas pressure at burner G31 mbar 35 0 Min gas pressure at burner G31 mbar 5 0 Max gas delivery G31 kg h 1 96 Min gas delivery G31 kg h 0 78 Max working pressure in heating bar 3 PMS Min working pressure in heating bar 0 8 Max heating temperature C 90 tmax Heatin...

Page 12: ...6 C 12 EN cod 3540Z852 Rev 01 08 2012 5 5 Wiring diagram fig 26 Electrical circuit 81 1kW L N 230V 50 Hz 16 N L 32 L N T T 278 T 42 4 3 2 1 44 38 114 ABM01 193 126 ON DAY 22 0004 REMOVE TO CONNECT THE CLOCK 139 138 72 ...

Page 13: ......

Page 14: ...ffect the customer s statutory rights If yes and if required by the manufacturer has a water scale reducer been fitted CONDENSING BOILERS ONLY The condensate drain has been installed in accordance with the manufacturer s instructions and or BS5546 BS6798 Yes If the condensate pipe terminates externally has the pipe diameter been increased and weatherproof insulation fitted Yes ...

Page 15: ...eer Name Company Name Telephone No Gas Safe Register No Comments Signature Date Engineer Name Company Name Telephone No Gas Safe Register No Comments Signature Date Engineer Name Company Name Telephone No Gas Safe Register No Comments Signature Date Engineer Name Company Name Telephone No Operative ID No Comments Signature Date Engineer Name Company Name Telephone No Gas Safe Register No Comments ...

Page 16: ...rvice Centre on 0843 479 0479 Calls to these numbers are charged at National Rate from BT landlines Calls made from mobile networks may be considerable more Phone numbers Installer Service Engineer BECAUSE OF OUR CONSTANT ENDEAVOUR FOR IMPROVEMENT DETAILS MAY VARY SLIGHTLY FROM THOSE QUOTED IN THESE INSTRUCTIONS ALL SPECIFICATIONS SUBJECT TO CHANGE Please note to avoid incurring unnecessary expens...