Safety

2.1

Safety instructions

Only use the product in original status without unauthorised modifications.

Only use the product if it is in perfect technical condition.

Take into consideration the ambient conditions at the location of use.

Before working on the product, switch off the power supply and secure it
against being switched on again.

2.2

Intended use

The proportional-pressure regulator is intended to regulate a pressure propor-
tional to a specified setpoint value. The product is intended for use in industrial
environments.

2.3

Training of qualified personnel

Work on the product may only be carried out by qualified personnel who can eval-
uate the work and detect dangers. The qualified personnel have skills and experi-
ence in dealing with electropneumatic (open-loop) control technology.

2.4

Approvals

In combination with the UL inspection mark on the product, the information in this
section must also be observed in order to comply with the certification conditions
of Underwriters Laboratories Inc. (UL) for USA and Canada.

UL certification information

Product category code

QUYX, QUYX7

File number

E322346

Considered standards

UL 610101, CAN/CSAC22.2 No. 61010-1

UL mark

Tab. 1 

The unit shall be supplied by a power source which fulfils the requirements
on a limited-energy circuit in accordance to IEC/EN/UL/CSA 61010-1 or on a
Limited Power Source (LPS) in accordance to IEC/EN/UL/CSA 60950-1 or
IEC/EN/UL/CSA 62368-1 or a Class 2 circuit in accordance to NEC or CEC.

Electrical data and ambient conditions

Supply voltage

24 V DC

Max. power

4.2 W

Rated pressure

up to 1.1 MPa

Max. installation height

2000 m

Tab. 2 

3

Further information

Accessories 

è

 www.festo.com/catalogue.

Spare parts 

è

 www.festo.com/spareparts.

4

Service

Contact your regional Festo contact person if you have technical questions

è

 www.festo.com.

4.1

Function

4.1.1

Functional principle

The VPPE-... is intended for regulating pressure proportionally to a specified set-
point value. Manually adjustable pressure regulators can be replaced by remotely
adjustable electric closed-loop controllers. This allows various machine paramet-
ers to be available quickly and automatically.

Fig. 1 

4.2

Configuration

4.2.1

Product design

1 Side mounting hole

2 Input supply port

3 LED display

4 Electrical connection

5 Status LED

6 Earth terminal, external (front and

back)

7 Up arrow button

8 Down arrow button

9 EDIT button

10 Output supply port

11 Exhaust supply port

12 Front mounting hole

Fig. 2 Product design VPPE-...-E1

1 Side mounting hole

2 Input supply port

3 Earth terminal, external (front and

back)

4 Electrical connection

5 Up arrow button

6 LED display

7 Status LED

8 Down arrow button

9 EDIT button

10 Output supply port

11 Exhaust supply port

12 Front mounting hole

Fig. 3 Product design VPPE-...-E1T

8136809

VPPE-3-1-1/8-...-E1

Proportional-pressure regulator

8136809
2021-01e
[8136811]

Operating instructions

Festo SE & Co. KG
Ruiter Straße 82
73734 Esslingen
Germany
+49 711 347-0

www.festo.com

Summary of Contents for VPPE-3-1-1/8 E1 Series

Page 1: ...t in accordance to IEC EN UL CSA 61010 1 or on a Limited Power Source LPS in accordance to IEC EN UL CSA 60950 1 or IEC EN UL CSA 62368 1 or a Class 2 circuit in accordance to NEC or CEC Electrical data and ambient conditions Supply voltage 24 V DC Max power 4 2 W Rated pressure up to 1 1 MPa Max installation height 2000 m Tab 2 3 Further information Accessories è www festo com catalogue Spare par...

Page 2: ...s maintained uncontrolled Leakage results in a change of pressure over the long term 1 Connect the VPPE with a setpoint value signal The VPPE has a so called differential input The setpoint signal is applied to the contact pin 2 and pin 4 where the lower potential must be connected to the contact pin 2 and the higher potential to the contact pin 4 Contact pin 2 setpoint value can be connected to c...

Page 3: ...on option v V 1 x xx v 1 sec in V 1 sec out 2 Pr Pr Pr1 Pr2 Pr3 3 bAr bAr bAr PA PSI 4 OFS 5 rnG 6 Frc 0 00 10 0 V voltage variant 4 00 20 0 mA current variant 7 An An SP O SP SP L HY HY SP H n Lo n Hi n Lo n Hi n Lo n Hi HY n Lo n Hi n Lo n Hi n Lo n Hi 8 Eco OFF OFF 1 999 sec 9 Pin OFF OFF 1 999 back to no 1 Tab 8 7 5 Preparation 8 Operation NOTICE When switching off the VPPE make sure that the ...

Page 4: ...e of protection IP 65 in combination with connector socket according to accessories Permissible temperature range Environment C 0 60 Storage C 10 60 Medium C 10 50 Electrical connection Pin contact M12x1 5 pin Permitted supply voltage 24 V DC 10 Setpoint variable input resistance 0 10 V 4 20 mA 10 kΩ voltage 250 Ω current Load actual value output min 2 kΩ voltage max 500 Ω current Residual ripple ...

Reviews: