background image

 

 

A Sierra Monitor Company

 

APPLICABILITY & EFFECTIVITY 

Effective for all systems manufactured after April 2011 

 

 

 

Driver Manual  

(Supplement to the FieldServer Instruction Manual)

 

 

FS-8700-23 Cleaver Brooks Hawk 

 

Driver Version: 

1.01 

Document Revision:   1 

 

Summary of Contents for FS-8700-23

Page 1: ...mpany APPLICABILITY EFFECTIVITY Effective for all systems manufactured after April 2011 Driver Manual Supplement to the FieldServer Instruction Manual FS 8700 23 Cleaver Brooks Hawk Driver Version 1 01 Document Revision 1 ...

Page 2: ...ons 4 4 Data Array Parameters 5 5 Configuring the FieldServer as a ChB Link Client 6 5 1 FieldServer 6 5 2 Client Side Connection Descriptions 6 5 3 Client Side Node Descriptors 7 5 3 1 CB Link_ID 7 5 3 2 Node_Type 8 5 4 Client Side Map Descriptors 8 5 4 1 FieldServer Related Map Descriptor Parameters 8 5 4 2 Driver Related Map Descriptor Parameters 8 5 4 3 Timing Parameters 8 5 4 4 Map Descriptor...

Page 3: ...the FieldServer to transfer data to and from devices over RS 485 using CB Link protocol The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer Refer to Model 833 2771 CB Link Manual 65 0216 and Model 833 2757 General Purpose Interface ControlBus Module Manual 65 0220 from Cleaver Brooks 2 DRIVER SCOPE OF SUPP...

Page 4: ...re the PLC according to manufacturer s instructions A B C FURTHER CB LINKS C1 833 2425 833 2757 RS485 9600 N81 CLEAVER BROOKS MODEL 833 2771 CB LINK or HONEYWELL Q7700 NETWORK INTERFACE UNIT CB HAWK AKA ASCII INTERFACE EMS INTERFACE BDI CARD QS7850 GPI GENERALPURPOSE INTERFACE POSSIBLE DEVICES BCS7700 BURNER CONTROL CB HAWK BURNER CONTROL RM7800 BURNER CONTROL RM7800 EXPANDED ANNUNCIATOR QS7X00X C...

Page 5: ...ta format of each of the Data Arrays to facilitate correct storage of the relevant data Section Title Data_Arrays Column Title Function Legal Values Data_Array_Name Provide name for Data Array Up to 15 alphanumeric characters Data_Array_Format Provide data format Each Data Array can only take on one format FLOAT BIT Int16 Int32 Data_Array_Length Number of Data Objects Must be larger than the data ...

Page 6: ...ing the FieldServer to communicate with a ChB Link Server Note that indicates an optional parameter with the bold legal value being the default 5 1 FieldServer Section Title Bridge Column Title Function Legal Values Title Title for CSV file Any text Maximum 32 characters System_Node_ID Node ID of the FieldServer 8 254 Example Common Information Bridge Title System_Node_ID CB_Link client 11 5 2 Cli...

Page 7: ...ion R1 R2 Node_Type Specify controller connected to CB Link See Section 5 3 2 Example Client Side Nodes Nodes Node_Name CBlink_ID Protocol Port Node_Type CBH1 0 1 20 CB_Link R1 Hawk 5 3 1 CB Link_ID The CB Link ID is declared in the format A B C where A describes the number of CB Link units attached Legal values 0 1 Link Attached default 8 24 Multiple Links Attached B describes the slot the device...

Page 8: ...e in the related bp2 property file Any of the variable names in the related bp2 property file Data_Array_Name Name of Data Array where data is to be stored in the FieldServer One of the Data Array names from Data Array section above Data_Array_Offset Starting location in Data Array 0 to maximum specified in Data Array section above Function Function of Client Map Descriptor RDBC 5 4 2 Driver Relat...

Page 9: ...rver com Tel 408 262 2299 Fax 408 262 2269 Toll Free 888 509 1970 email support fieldserver com 5 4 4 Map Descriptor Example Client Side Map Descriptors Map_Descriptors Map_Descriptor_Name Data_Array_Name Data_Array_Offset Function Node_Name Scan_Interval Timeout Control_Source DA_AI_01 1 RDBC CBH1 10 30 Oper_Pressure DA_AI_01 2 RDBC CBH1 10 30 ...

Page 10: ...oneywell QS7800A S7830 Expanded Annunciator S7830 S7830 Expanded Annunciator Honeywell QS7800A S7800 Keyboard Display Module S7800 S7800 Honeywell QS7800A ST7800 Relay Module ST7800 Requires S7800 module Honeywell RM7800E G L M Relay Modules RM78XX RM78XX Honeywell RM7840E G L M Relay Modules RM78XX RM78XX Honeywell N A Q7700A B CB Link 833 2727 Display Module N A N A CB Link 833 2729 Data Control...

Page 11: ... Appendix A 1 This configuration file contains the mapping for the related module and can be used as a basis for building a configuration for the FieldServer Note SYSNet is the generic name for networks of the listed modules Controlbus is the generic name for the networks in a NIM CBLink configuration Appendix A 2 Driver Compatibility Matrix FieldServer Model Compatible with this driver FS x2010 Y...