background image

Field Charger/Power Supply

 FCPS-24FS6

FCPS-24FS8

PN: 51883:B          ECN 02-609

Document      #51883
12/04/02       Revision:

B

Summary of Contents for FCPS-24FS6

Page 1: ...Field Charger Power Supply FCPS 24FS6 FCPS 24FS8 PN 51883 B ECN 02 609 Document 51883 12 04 02 Revision B ...

Page 2: ...xplosions caused by escaping gas improper storage of flammable materials etc Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a prede termined rate or reaches a predetermined level Rate of rise heat detectors may be subject to reduced sensitivity over time For this reason the rate of rise feature of each detector should be tested at least o...

Page 3: ... anticipated or encountered Disconnect AC power and batteries prior to removing or in serting circuit boards Failure to do so can damage circuits Remove all electronic assemblies prior to any drilling filing reaming or punching of the enclosure When possible make all cable entries from the sides or rear Before making modifi cations verify that they will not interfere with battery trans former and ...

Page 4: ...4 FCPS 24FS PN 51883 B 12 04 02 Notes ...

Page 5: ... 23 3 2 6 Door Closers 23 SECTION 4 Trouble Supervision 24 4 1 Supervision via FACP Notification Appliance Circuit 24 4 1 1 Supervision of FACP to FCPS wiring 24 4 1 2 Supervision of FCPS 24FS Faults 24 4 1 3 Trouble Relay 25 4 2 AC Loss Reporting Delay 25 SECTION 5 Applications 26 5 1 Controlling Four NACs With One Input and Selective Silence 26 5 2 Controlling Three NACs and One Door Holder With...

Page 6: ...6 FCPS 24FS PN 51883 B 12 04 02 Notes ...

Page 7: ...s Laboratories Documents UL 464 Audible Signaling Appliances UL 864 Standard for Control Units for Fire Protective Signaling Systems UL 1638 Visual Signaling Appliances UL 1971 Signaling Devices for Hearing Impaired Other NEC Article 250 Grounding NEC Article 300 Wiring Methods NEC Article 760 Fire Protective Signaling Systems Applicable Local and State Building Codes Requirements of the Local Aut...

Page 8: ...e FACP the power supply will activate its Notification Appliance Circuits During the inactive or nonalarm state the power supply supervises its NAC field wiring for short and open conditions AC fail battery charger and ground fault troubles will also be monitored by the power supply If an NAC or power supply fault is detected the power supply Normally Closed Trouble contact will open If an alarm c...

Page 9: ... the power supply jumpers as described in Jumpers on page 10 2 Install the power supply as described in Installation on page 14 3 Program the power supply as described in Programming Options on page 19 4 Wire the power supply circuits referring to the options described in Trouble Supervision on page 24 and the application examples in Applications on page 26 5 Connect primary power source wiring wh...

Page 10: ...oded steady voltage input signal the jumper for the corresponding input circuit should be in the default position which jumpers the bottom two pins as illustrated in drawing at left If the source voltage to the input circuit is coded variable voltage the jumper for the corresponding input circuit should be moved to jumper the top two pins 1 5 LED Indicators AC Power on green LED indicates AC power...

Page 11: ...ts FCPS 24FS6 6 0 amps FCPS 24FS8 8 0 amps Output Circuit Types Four Style Y NACs require 4 7 KΩ End of Line Resistors or Style Z NACs using the optional ZNAC 4 Class A converter module OR Four resettable or nonresettable 24 VDC power outputs Refer to Fire Lite Device Compatibility Document for listed compatible devices Trouble Relay Contact Rating TB5 Fail safe Form C relay normally energized tra...

Page 12: ... Out 2 NAC Out 2 NAC Out 3 NAC Out 3 NAC Out 4 NAC Out 4 Supervised Earth AC Neutral AC Hot Trouble Relay Form C Fail safe shown energized Normally Open Normally Closed Common JP1 Ground Fault Detection cut to disable JP2 JP3 Coded Noncoded Input Selection JP4 Supervised Battery Battery 18 AH 24 VDC Nonpower limited LEDs Charger Trouble AC Loss yellow NAC Trouble yellow Battery Trouble yellow Grou...

Page 13: ...age 20 During the inactive state the remote power supply supervises its NAC field wiring for short and open conditions If a fault is detected the power supply will enter a trouble condition and illuminate the NAC Trouble LED When the NACs are activated the supervision is disabled and the circuits are no longer supervised Supervision of other power supply faults such as low battery battery charger ...

Page 14: ...g backbox Set the board and transformers aside in a safe clean place Avoid static discharge which may damage static sensitive components on the board 2 Mark and predrill holes for the top two keyhole mounting bolts 3 Install two upper fasteners in the wall with the screw heads protruding approximately 4 Using the upper keyholes mount the backbox over the two screws 5 Mark the lower two holes remov...

Page 15: ...Figure 2 2 Backbox Mounting Dimensions Bottom Height 15 00 38 10 cm 10 625 26 99 cm 0 75 1 9 cm 2 875 7 3 cm Backbox 14 5 36 8 cm Depth 3 050 7 75 cm Top 9 1 23 1 cm 2 7 6 86cm 1 125 2 868 cm Mounting Plate Pem Studs Backbox Mounting Holes rcpscabb cdr Ground Stud ...

Page 16: ...TB4 JP3 J3 TB5 TB2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM 1 2 3 4 5 6 7 8 9 10 8 7 6 5 4 3 2 1 TB2 3 2 1 Figure 2 3 NAC Style Y Class B 4 7KΩ ELR Horn Strobe Horn Strobe Horn Strobe Alarm Polarity Shown FCPS 24FS Circuit Board 24fsclsb cdr TB4 JP3 J3 TB5 TB2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1...

Page 17: ...W1 SW1 TB4 TB4 JP3 JP3 J3 TB5 TB2 JP1 JP2 JP2 EARTH NEUT HOT OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX AUX IN2 IN2 IN2 IN2 OUT1 OUT1 OUT1 OUT1 IN1 IN1 IN1 IN1 SYNC IN SYNC IN SYNC IN SYNC IN AUX AUX NO NC AUX TBL COM BATTERY AC BATT GND FLT NAC TRBL AC CHGR CAUTION HIGH VOLTAGE CAUTION HIGH VOLTAGE NAC 4CLASSA A A NAC 3CLASSA A A NAC 2CLASSA A A NAC 1CLASSA A A 8 9 8 8 9 9 10 11 12 13 14 15 0 0 ...

Page 18: ...ed For power limited applications use of conduit is optional 1 2 3 4 5 6 7 8 ON TB1 J2 TRANSFORMER 2 TRANSFORMER 1 J1 F1 JP4 30V 15A SW1 TB4 JP3 J3 TB5 TB2 JP1 JP2 EARTH NEUT HOT OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM BATTERY AC AC BATT CHGR GND FLT NAC TRBL CAUTION HIGH VOLTAGE CAUTION HIGH VOLTAGE NAC 4CLASS A A A NAC 3CLASS A ...

Page 19: ...tration for switch location and DIP switch placement in the ON and OFF positions ON 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 ON TB1 J2 TRANSFORMER 2 TRANSFORMER 1 J1 F1 JP4 30V 15A SW1 TB4 JP3 J3 TB5 TB2 JP1 JP2 EARTH NEUT HOT OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 8 7 6 5 4 3 2 1 3 2 1 10 9 8 7 6 5 4 3 2 1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM BATTERY AC AC BATT CHGR GND FLT...

Page 20: ...ontrolled by Control Input 1 and Outputs 3 42 are controlled by Control Input 2 Sync Input is monitored3 Only nonresettable Auxiliary Power is available from TB4 Terminals 9 10 Output 4 function follows DIP switch 8 setting 5 ON 6 OFF Split Temporal FCPS configured as Master switch 3 OFF Control Input 1 controls NAC Outputs 1 2 and Control Input 2 controls Outputs 3 42 which will generate a Tempor...

Page 21: ...e not used The power supply is the originator of the strobe synchronization pulses on its NAC outputs In sync generator mode the sync type System Sensor Wheelock or Gentex is selectable via DIP switches 1 and 2 When this power supply is configured as a sync follower Slave Synchronization mode the power supply s NAC outputs track the strobe synchronization pulses present at the supply s Sync Input ...

Page 22: ...ured as Slave switch 3 ON NAC Outputs 1 through 42 are controlled by Control Input 1 Sync Input is monitored2 Resettable or nonresettable Auxiliary Power Output is available from TB4 Terminals 9 10 Control Input 2 determines if reset will occur must go from On to Off for a 6 second reset to occur OFF ON Split Alarm FCPS configured as Master switch 3 OFF NAC Outputs 1 2 are controlled by Control In...

Page 23: ...tion will disable the charger It should only be disabled if an external battery charger is being used for the FCPS 24FS 3 2 6 Door Closers Output Circuit 4 can be configured as an NAC or door closer circuit Setting DIP switch 8 to the OFF position will configure Output Circuit 4 as an NAC Setting DIP switch 8 to the ON position will configure only Output Circuit 4 as a door closer circuit which wi...

Page 24: ...lts as an open circuit condition on its NAC An internal trouble contact is located between TB4 Terminal 3 In and TB4 Terminal 5 Out Any of the following conditions will cause the trouble contact to open provided the FACP Notification Appliance Circuit is not in alarm The following trouble conditions will cause a general NAC trouble A field wiring fault on the NAC output of the power supply An AC f...

Page 25: ...rouble 4 2 AC Loss Reporting Delay The reporting of AC loss to a central station is usually delayed in order to prevent multiple transmissions of AC loss and restoral thus allowing AC power to stabilize When a host FACP is programmed to delay AC loss reporting the FCPS 24FS must be configured to delay the reporting of AC fail This is accomplished by setting SW1 DIP switch 4 to the ON position This...

Page 26: ...M 1 2 3 4 5 6 7 8 9 10 8 7 6 5 4 3 2 1 8 7 TB2 3 2 1 OUT4 NAC4 8 7 TB2 8 9 8 8 9 9 10 11 12 13 14 15 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 0 1 2 3 4 7 6 5 TENS ONES ADDRESS LOOP 8 9 8 8 9 9 10 11 12 13 14 15 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 0 1 2 3 4 7 6 5 TENS ONES ADDRESS LOOP Figure 5 1 Controlling Four Outputs With One Input Control Module Relay Module EOL Power Supervision Relay A77 716B energized S...

Page 27: ...erminal 7 IN2 and Terminal 9 Aux Power 3 Do not loop wires under screw terminals Break wires to maintain proper supervision 4 An End of Line Resistor must be installed between TB4 Terminals 5 6 for control module wiring supervision the ELR value is dependent on the module employed 5 Supervise the power wiring between the FPCS 24FS auxiliary 24 VDC output on TB4 Terminals 9 10 with an EOL relay P N...

Page 28: ...C4 OUT3 NAC3 OUT3 NAC3 OUT4 NAC4 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM 1 2 3 4 5 6 7 8 9 10 8 7 6 5 4 3 2 1 8 7 6 5 8 7 6 5 TB2 TB2 3 2 1 8 9 8 8 9 9 10 11 12 13 14 15 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 0 1 2 3 4 7 6 5 TENS ONES ADDRESS LOO P Figure 5 2 Controlling Three NACs and One Door Holder With One Input Style Z Class A Style...

Page 29: ...power supply will result in an open circuit condition on the control module output circuit monitored by End of Line Resistor across Terminals 5 6 As an alternative the trouble contacts at TB5 of the power supply can also be used for independent trouble monitoring 3 Do not loop wires under screw terminals Break wires to maintain proper supervision 4 An End of Line Resistor must be installed between...

Page 30: ...IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM 1 2 3 4 5 6 7 8 9 10 8 7 6 5 4 3 2 1 8 7 8 7 TB2 TB2 3 2 1 8 9 8 8 9 9 10 11 12 13 14 15 0 0 1 1 2 2 3 3 4 4 5 5 6 6 7 7 0 1 2 3 4 7 6 5 TENS ONES ADDRESS LOOP Figure 5 3 Split Temporal Mode Application Style Z Class A Style Y Class B Temporal Bell Circuit 4 Temporal Bell Circuit 3 Horn Strobe Circuit 2 Horn Strobe Circuit 1 Use listed EL...

Page 31: ...sistor across Terminals 5 6 As an alternative the trouble contacts at TB5 of the power supply can also be used for independent trouble monitoring 2 Do not loop wires under screw terminals Break wires to maintain proper supervision 3 An End of Line Resistor must be installed between terminals 5 6 for control module wiring supervision the ELR value is dependent on the module employed and across term...

Page 32: ...a nonresettable power source such as the Aux Power output of the FCPS 24FS to Control Input 1 For addressable panel applications an addressable monitor module can be used to monitor the trouble contact of the FCPS 24FS and the resettable power connection from the FACP using an End of Line power supervision relay If the FCPS 24FS enters a trouble condition the Normally Closed trouble contact will o...

Page 33: ...t circuit for module wiring supervision the ELR value is dependent on the module employed 2 An End of Line power supervision relay must be connected between TB4 Terminals 5 6 The Normally Closed when energized power supervision relay contact must be in series with the End of Line Resistor referred to in note 1 3 Do not loop wires under screw terminals Break wires to maintain proper supervision 4 F...

Page 34: ... to TB4 Terminal 3 24 VDC is applied directly to Terminal 4 from the FACP 2 The Normally Closed alarm relay may consist of an actual relay in the FACP or a control module which may be mounted remotely or at the FACP 3 A monitor module may be used to monitor the FCPS 24FS Trouble contacts at TB5 Any power supply trouble will cause the contacts to change states 4 A maximum of 4 0 amps from the FCPS ...

Page 35: ... the notification appliances when its Normally Open contact 7 9 closes FACP NAC programmed for Sync NAC 1 TB4 JP3 J3 TB5 TB2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM 1 2 3 4 5 6 7 8 9 10 8 7 6 5 4 3 2 1 3 2 1 TB4 JP3 J3 TB5 TB2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX...

Page 36: ...vices from the same manufacturer in each system FACP NAC programmed for Sync NAC 1 TB4 JP 3 J3 TB 5 TB 2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO NC AUX TBL COM 1 2 3 4 5 6 7 8 9 10 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 3 2 1 TB4 JP3 J3 TB5 TB2 JP1 JP2 OUT4 NAC4 OUT3 NAC3 OUT2 NAC2 OUT1 NAC1 AUX IN2 IN2 OUT1 OUT1 IN1 IN1 SYNC IN SYNC IN AUX NO ...

Page 37: ... supply requires connection to a separate dedicated AC branch circuit which must be labeled FIRE ALARM This branch circuit must connect to the line side of the main power feed of the protected premises No other non fire alarm equipment may be powered from the fire alarm branch circuit The branch circuit wire must run continuously without any disconnect devices from the power source to the power su...

Page 38: ...peres A Table 6 2 shows how to convert milliamperes and microamperes to full amperes 6 3 2 How to Calculate System Current Draw Use Table 6 3 on page 39 to calculate current draws as follows 1 Enter the quantity of devices in all three columns 2 Enter the current draw where required Refer to the Fire Lite Device Compatibility Document for compatible devices and their current draw 3 Calculate the c...

Page 39: ...6 3 System Current Draw Calculations Device Type Calculate Column 1 Primary Non Fire Alarm Current amps Calculate Column 2 Primary Fire Alarm Current amps Calculation Column 3 Secondary Non Fire Alarm Current amps Qty X current draw Total Qty X current draw Total Qty X current draw Total Main Circuit Board 1 X 0 091 1 X 0 091 1 X 0 065 Power Supervision Relay X 0 025 X 0 025 X 0 025 NAC Output 1 X...

Page 40: ...rm Systems require 24 hours of standby power followed by 5 minutes in alarm NFPA 72 Central Auxiliary and Remote Station Fire Alarm Systems require 60 hours of standby followed by 5 minutes in alarm Batteries installed in a system powered by a generator need to provide at least 4 hours of standby power 6 4 2 Selecting and Locating Batteries Select batteries that meet or exceed the total ampere hou...

Page 41: ...er Module 16 see also ZNAC 4 8 Class B see also Style Y 8 Coded Input 10 Coded Noncoded Input Selection 10 coding NAC 8 compatibility input circuit 8 control circuit 8 current 11 see also input circuit 11 voltage 11 current maximum continuous 8 maximum short term 9 standby 11 total continuous 11 total short term 11 D dimensions backbox 15 E ELR installation 24 see also End of Line Resistor 24 End ...

Page 42: ...um current 8 see also NAC output 11 Style 11 voltage rating 11 output power 8 P Power nonresettable 8 resettable 8 power supply board layout drawing 12 connectors and jumpers 12 power supply requirements 37 powering supply 37 power limited 8 power limited wiring 18 R relay trouble 8 9 11 25 reporting delay AC loss 25 resettable power 22 S secondary power see also battery 11 Specific Application Po...

Page 43: ...ransportation prepaid to the manufacturer This writing constitutes the only warranty made by this manufacturer with respect to its products The manufacturer does not represent that its products will prevent any loss by fire or otherwise or that its products will in all cases provide the protection for which they are installed or intended Buyer acknowledges that the manufacturer is not an insurer a...

Page 44: ...World Headquarters One Fire Lite Place Northford CT 06472 1653 USA 203 484 7161 Fax 203 484 7118 www firelite com ...