background image

PRODUCT OVERVIEW

PRODUCT APPLICATION:

The Firex Series Duct Smoke Detectors provide early detection of smoke and products of combustion present in the air moving through an HVAC
duct in commercial, industrial and residential applications.

These devices are designed to prevent the recirculation of smoke in areas by the air handling systems, fans and blowers.  Complete systems
may be shut down in the event of smoke detection.

NOTE

For the correct installation of a duct smoke unit, please refer to the NFPA 72E (Standard for Automatic Fire Detectors) and NFPA 90A (Standard
for Installation of Air Condition and Ventilation Systems.)

This detector is not intended for open area protection nor should it be used for early warning detection or replace a regular fire detection system.

Maple Chase provides a special U.L. 50 listed, NEMA 3R rated weatherproof enclosure separately (Model 555) which should be used in
appropriate outdoor applications for protection from the elements.  Other installations above the roof line (attics, banjo type roofs, etc.) do not
require the special Model 555 weatherproof enclosure as long as the Maple Chase duct smoke detectors are not exposed to dripping water or
other environmental  elements.  The Model 555 weatherproof enclosure should be used in all applications where environmental elements are a
concern or local code requires a weatherproof enclosure for proper installation.  All installations of our duct smoke detectors and weatherproof
enclosures should be done in accordance with all applicable electrical and building codes.

PRODUCT DESCRIPTION:  

The Firex Smoke Detector is fitted with a mounting base that will accept an Ionization Detector Head Model # 2850-450 or Photoelectric Detector
Head Model # 2850-550.  The duct unit supports 2 sets of form “C” and 1 form “A” Alarm Contacts and 1 form “C” Trouble Contact. The trouble
contact supervises the presence of the input power and removal of the detector head. 

THE TROUBLE CONTACTS (TERMINALS 4-15-5) ARE SHOWN IN THE NON-ENERGIZED CONDITION.

The trouble contact 

will not

operate in the event of a smoke alarm.

The Firex Duct Detector models 2650-760 and 2650-761 will operate on one of the following input voltage sources: 24VAC, 24VDC, 115VAC
and 230VAC.

The duct smoke detector units are designed to operate in duct widths from 12 inches to 10 feet wide with an air velocity between 300 and 4,000
feet per minute. To verify correct installation, the pressure differential between the input and exhaust tubes should be measured using a
Magnehelic pressure gauge or equivalent.  An acceptable reading must be between 0.01 and 1.2 inches of water.

For a Duct Smoke Detector unit to operate correctly, it must be installed 6 duct widths from any obstruction i.e. elbows, deflector plates, filters,
dampers, etc. In situations where the criteria cannot be met, deviations are acceptable providing they meet the pressure differential
requirements.

SAMPLING TUBES:

The principal of operation of a duct detector is based on the Venturi effect.  Two tubes extend into the HVAC duct.  Air flowing through the duct
is forced into the air intake tube via the air intake holes, and passes over the detector head.  The air will be drawn out via the exhaust tube back
into the HVAC duct.  (7” exhaust tube provided in the installation kit.)

When the particles of smoke suspended in the air stream reach the alarm threshold of the detector head, the unit will go into alarm.

Duct Unit Installation

DUCT SMOKE LOCATION PRE-REQUISITES:

This guideline contains general information on duct smoke detector installation, but does not preclude the NFPA documents listed.  Maple Chase
Company assumes no responsibility for improperly installed duct detectors.  To determine the correct installation position for a Firex Duct Smoke
Detector, the following factors must be considered.

1)  

A uniform non turbulent airflow of between 300 ft/min to 4,000 ft/min. must be present in the HVAC duct.  To determine the duct
velocities examine the engineering specifications that define the expected velocities or use an Alnor model 6000P
velocity/meter (or equivalent).

2)  

In order to prevent stratification, duct smoke units, where possible, must be located a minimum of six duct widths down stream

from a source of turbulence i.e. elbows, deflector plates, filters, dampers, and inlets.

MODEL  2650-760 Ionization
MODEL  2650-761 Photoelectric

INSTALLATION INSTRUCTIONS FOR
UNIVERSAL DUCT SMOKE DETECTORS

R

AP 186   MA 2650-760; 01/01

Summary of Contents for 2650-760

Page 1: ...2650 760 and 2650 761 will operate on one of the following input voltage sources 24VAC 24VDC 115VAC and 230VAC The duct smoke detector units are designed to operate in duct widths from 12 inches to 10 feet wide with an air velocity between 300 and 4 000 feet per minute To verify correct installation the pressure differential between the input and exhaust tubes should be measured using a Magnehelic...

Page 2: ...dths of 2 5 TO 5 0 554 For duct widths of 5 0 TO 10 0 The standard sampling tubes are steel tubes with air intake holes drilled down the entire length of the tube These tubes must be cut to length and must span the entire width of the duct Sampling tubes over 3 0 feet must be supported on the opposite side of the duct To ensure the correct operation of the sensing tube the red end cap red stopper ...

Page 3: ...trouble contacts 4 15 5 will not change state in the event of a fire alarm operational or functional testing The trouble contacts can be tested by rotating the Apollo detector head counter clockwise and removing the detector head This action will extinguish the pilot green LED and cause the trouble contacts to change state 4 15 will be closed continuity 5 15 will be open circuit Replacing the dete...

Page 4: ...on must be assessed on its own merits If the protected area is of a very dirty nature then the Firex Duct units will have to be checked and cleaned on a Quarterly basis or when cleaning is required As a guideline the detector head should be cleaned every six months or as required The best methods of cleaning are to vacuum the detector head thoroughly or to blow the detector head out using compress...

Page 5: ...TEST RESET ALARM WHEN NOT INTERCONNECTED PILOT 2 Remote Accessories Approved For Use With This Detector 535 Remote Alarm 542 Remote Alarm Pilot Horn key operated Test Reset Switch 536 Remote Alarm push button Test Reset Switch 543 Remote Alarm Pilot Horn 537 Remote Alarm Pilot push button Test Reset Switch 544 Remote Alarm Trouble Pilot Horn key operated Test Reset Switch 538 Remote Alarm key oper...

Page 6: ...ROBE OPERATE ON ALARMED DETECTOR ONLY 30 DETECTORS MAX ALL RELAYS OPERATE WITH SINGLE ALARM ALL HORN STROBES OPERATE WITH SINGLE ALARM 10 DETECTORS MAX COMMON TEST RESET 30 DETECTORS ONLY NORMALLY OPEN RESET SWITCH Unit 1 Unit 2 Unit 3 Unit 1 Unit 2 Unit 3 Unit 1 Unit 2 Unit 3 Unit 1 Unit 2 Unit 3 12 12 12 H RED BLK H RED BLK H RED BLK 13 14 19 20 13 14 19 20 13 14 19 20 12 12 12 H RED BLK H RED B...

Reviews: