SMOKE ALARM DESCRIPTION
Ionisation 230V AC smoke alarm
with Easy Access Battery Door and
False Alarm Control
SMOKE ALARM FEATURES
• Interconnects with up to 36 Model GC240, I240C, PG240, PAD240, PADC240,
IAR230C, PAR230, FADC230 smoke alarms and H230, H230CT, HR230C heat alarms.
Unique power connector prevents interconnection with incompatible smoke alarms or
security systems.
• Tamper-resist bracket quickly snaps into place and serves as a safeguard
against tampering.
• Multi-purpose green and red LEDs indicate that the smoke alarm is receiving AC
power, working under normal operation, in alarm, or under False Alarm Control.
• Loud alarm horn—85 decibels at 3 metres (10 feet)—sounds to alert you of
an emergency.
• Test button checks smoke alarm operation.
• Features False Alarm Control, which, when activated, quiets unwanted alarms for up to
15 minutes.
• Features easy access front loading battery compartment. Battery door
cannot be closed if battery is not properly installed.
• Features a latching LED which blinks the initiating alarm's red LED 3 times
each minute until manually reset.
• Has a ramp-up test horn feature which emits 2 reduced-volume beeps
before reaching the full 85db level during testing.
IMPORTANT SAFETY INFORMATION
PLEASE READ AND SAVE THESE
INSTRUCTIONS
W
A
R
N
I
N
G
•
AC smoke alarms require constant 230V AC, 50Hz power to operate
properly.
Mains-powered smoke alarms WILL NOT work if AC power is not
connected or has failed or been interrupted for any reason. Model FADC230
requires a working 9-volt battery to operate properly in the event of a power
failure. DO NOT use any other kind of battery except as specified in this manual.
DO NOT connect this smoke alarm to any other type of smoke alarm or auxiliary
device, except those listed in this manual.
•
DO NOT remove or disconnect battery or turn off AC power to quiet
unwanted alarms.
This will remove your protection. Open windows or fan the air
around smoke alarm to silence it. Model FADC230 features a False Alarm Control
button which, when activated, will quiet unwanted alarms for up to 15 minutes.
•
The Push-to-Test button accurately tests all smoke alarm functions.
DO NOT use any other test method.
Test smoke alarm weekly to ensure
proper operation.
•
This smoke alarm should be installed only by a qualified electrician.
•
This smoke alarm is designed to be used inside a single family household
only.
In multi-family buildings, each individual living unit should have its own
smoke alarms. Do not install in non-residential buildings or places which house
many people like hotels, motels, dormitories, hospitals, nursing homes, or
group homes of any kind. This smoke alarm is not a substitute for a complete
alarm system.
•
Install a smoke alarm in every room and on every level of the home.
Smoke
may not reach the smoke alarm for many reasons. For example, if a fire starts in
a remote part of the home, on another level, in a chimney, wall, roof, or on the
other side of a closed door, smoke may not reach the smoke alarm in time to
alert household members. A smoke alarm will not promptly detect a fire EXCEPT
in the area or room in which it is installed.
•
Interconnected smoke alarms installed in every room and on every level of
the household offers maximum protection.
We recommend interconnecting
smoke alarms so that when one smoke alarm senses smoke and sounds its alarm,
all others will sound as well. Do not interconnect smoke alarms from one individual
family living unit to another. Do not connect this smoke alarm to any other type of
alarm or auxiliary device.
•
Smoke alarms may not alert every household member every time.
The
alarm horn is loud in order to alert individuals of a potential danger. However,
there may be limiting circumstances where a household member may not hear
the alarm (i.e. outdoor or indoor noise, sound sleepers, drug or alcohol usage,
the hearing impaired, etc.). If you suspect that this smoke alarm may not alert a
household member, install and maintain specialty smoke alarms. Household
members must hear the alarm’s warning sound and quickly respond to it to
reduce the risk of damage, injury, or death that may result from fire. If a house-
hold member is hearing impaired, install special smoke alarms with lights or
vibrating devices to alert occupants.
•
Smoke alarms can only sound their alarms when they detect smoke.
Smoke alarms detect combustion particles in the air. They do not sense heat,
flame, or gas. This smoke alarm is designed to give audible warning of a devel-
oping fire. However, many fires are fast-burning, explosive, or intentional.
Others are caused by carelessness or safety hazards. Smoke may not reach
the smoke alarm QUICKLY ENOUGH to ensure safe escape.
•
Smoke alarms have limitations.
This smoke alarm is not fool-proof and is not
warranted to protect lives or property from fire. Smoke alarms are not a substitute
for insurance. Homeowners and renters should insure their lives and property. In
addition, it is possible for the smoke alarm to fail at any time.
For this reason,
you must test the smoke alarm weekly and replace every 10 years.
SMOKE ALARM PLACEMENT
It is recommended to achieve complete coverage protection by installing a
smoke alarm in every room of your home.
At a minimum, smoke alarms shall be installed outside of each separate sleeping
area in the immediate vicinity of the bedrooms and on each additional storey of the
family living unit including basements and excluding crawl spaces and unfinished
attics. Any home requires a minimum of two smoke alarms.
FOR BEST PROTECTION, IT IS RECOMMENDED THAT YOU
INSTALL A SMOKE ALARM IN EVERY ROOM
In addition, it is recommended that all smoke alarms be interconnected.
Typical Efficiency
Home (Apartment)
•
Install a smoke alarm on the ceiling or wall
closest to the sleeping area. Install a
smoke alarm with False Alarm Control in
the kitchen/living area.
Typical Single Storey Home
•
Install a smoke alarm on the ceiling or wall
inside each bedroom and in the hallway
outside each separate sleeping area. If a
bedroom area hallway is more than 9 m
long, install a smoke alarm at each end.
Typical Two-Storey Home
•
Install a smoke alarm on the ceiling or wall
inside each bedroom and in the hallway
outside each separate sleeping area.
If a bedroom area hallway is more than 9
m long, install a smoke alarm at each end.
•
Install a smoke alarm at the top
of a first-to-second floor stairwell.
IMPORTANT SMOKE ALARM PLACEMENT AND
EXCEPTION INFORMATION:
•
Install a smoke alarm as close to the centre of the
ceiling as possible. If this is not practical, mount no
closer than 10 cm
(4 inches) from a wall or corner. Also, if local codes
allow, install smoke alarms on walls, between 10
and 30 cm (4 and 12 inches) from ceiling/wall inter-
sections.
•
I
nstall a minimum of two smoke alarms in every
home, no matter how small the home. Any size
home requires fitting a minimum of two smoke
alarms.
•
Install a smoke alarm in each room that is divided
by a partial wall (either coming down from the
ceiling at least 60 cm (24 inches), or coming up
from the floor).
•
I
nstall smoke alarms on peaked, cathedral, or
gabled ceilings 1 m from the highest point (meas-
ured horizontally).
•
I
nstall a smoke alarm in lived-in attics or attics
which house electrical equipment like furnaces,
air conditioners, or heaters.
DO NOT install smoke alarms:
Near appliances or areas where normal combustion regularly occurs
(kitchens, near boilers, hot water heaters). Use specialized smoke
alarms with unwanted alarm control for these areas.
In areas with high humidity, like bathrooms or areas
near dishwashers or washing machines. Install at least 3 metres
away from these areas.
Near air returns or heating and cooling supply vents. The air could
blow smoke away from the detector, interrupting its alarm.
In rooms where temperatures may fall below 5˚C (41˚F) or rise above
45˚C (113˚F).
In extremely dusty, dirty, or insect-infested areas.
Loose particles interfere with smoke alarm operation.
Do not site this alarm in area where water or other liquids may enter
the alarm.
HOW TO INSTALL THIS SMOKE ALARM
DANGER:
ELECTRICAL SHOCK HAZARD. Turn off power at
the main fuse box or circuit breaker by remov-
ing the fuse or switching the circuit breaker to
the OFF position and securing it.
WARNING:
Mains operated smoke alarms should be installed
by a qualified electrician in accordance with the
Regulations for Electrical Installations published
by the Institution of Electrical Engineers (BS).
Failure to install this smoke alarm correctly may
expose the user to shock or fire hazards.
WARNING:
The smoke alarm, its associated supply, and
interconnect wiring must be installed in accor-
dance with BS 7671 published by the institution
of Electrical Engineers.
•
Install smoke alarm on a wall, ceiling, standard electrical box, or surface mount-
ing pattress.
1.
Align mounting plate with mounting holes of standard electrical box or surface
mounting pattress. For siting on wall or ceiling, use mounting plate as template to
mark holes. Drill holes (for wall or ceiling only) and insert supplied screw plugs into
holes until flush with wall or ceiling.
2.
Secure mounting plate to electrical box, pattress, wall, or ceiling. (Diagram illus-
trates fixing mounting plate to electrical box.)
3. Connect blue wire from connector plug of smoke alarm to neutral (black or
blue) mains power wire.
4. Connect brown wire from connector plug of smoke alarm to live (red or
brown) mains power wire .
5.
If interconnection is desired, connect orange wire from connector to interconnect
wire between smoke alarms. See section, “Interconnecting Smoke Alarms.”
NOTE:
If this will be a single-station smoke alarm, cover orange wire with electrical
tape and tuck into ceiling, wall, or pattress.
6. Attach connector plug to pins on back of smoke alarm. Plug will only fit one
way and will snap into place.
7. Gently tug connector to be sure it is attached securely.
8. Position smoke alarm to mounting plate so that keyslot on side of smoke
alarm is to left of tab on mounting plate. Turn clockwise to lock into
place.
9. Turn on power at main fuse box or circuit breaker. The green LED on the cover
should be illuminated.
10. Remove arrow tab and close battery door. Smoke alarm may beep briefly as
door is closed.
11. Test smoke alarm. See “TESTING THE SMOKE ALARM”.
INTERCONNECTING SMOKE ALARMS
•
Use 1.5mm
2
minimum solid or stranded wire with a rating of 230V. When inter-
connecting, maximum wire length between any two is 450 m for 1.5mm
2
or
1200 m for 2.5mm
2
(20 OHMS loop resistance).
•
This smoke alarm may be interconnected with as many as 35 other Models
GC240, I240C, PG240, PAD240, PADC240, IAR230C, FADC230, and PAR230
smoke and H230, H230CT, HR230C heat alarms. DO NOT connect to any
other type or model smoke alarm.
•
Connect smoke alarms to a single AC branch circuit. If local codes do not per-
mit, be sure the neutral wire is common to both phases. Wiring must conform
to IEE Regulations for electrical installation.
RED AND GREEN LED INDICATORS
This smoke alarm features red and green LED indicators that can be seen through
the Push-to-Test button or the LED lens above the test button. The LEDs indicate
the following:
GREEN LED
ON
—
AC power is present
.
OFF
—
AC power is not present.
RED LED
Blinks once a minute
— indicating normal operation.
Blinks once a second
— smoke alarm senses smoke and simultane-
ously sounds an audible alarm.
Blinks once every 10 seconds
— smoke alarm is quieting an unwanted alarm.
(Interconnected system only):
OFF —
another smoke alarm in the network has sensed
smoke and is signalling this alarm.
RED blinks 3 times
— indicates this unit initiated an
every minute
alarm in an inteconnected
system (press the test button
to reset).
RED blinks 4 times every
— indicates weak or improperly
minute preceded by an
connected battery.
audible chirp
1
2
3
4
Smoke Alarm
USER’S
MANUAL
PLEASE READ AND SAVE
INSTALLER: Please leave this manual with the product.
354-00004-001 Rev. A
BS5446 : Pt 1 : 2000
LICENSE NO. 7832
PU
SH TO HUSH
H
O
LD
TO TEST WE
EK
LY
SLIDE TO OPEN DOOR
TU
RN
TO
RE
M
OV
E
RE
FER
TO
OW
NER'S
MANUAL FOR OPERA
TING
INS
TRU
CTI
ON
S
DO
N
OT
PA
IN
T
Model
FADC230
Ionisation
!
SLEEPING
AREA
KITCHEN
LIVING
AREA
FAMILY ROOM KITCHEN
BEDROOM
BEDROOM
BEDROOM
FIREPLACE
DINING
ROOM
BEDROOM
BEDROOM
BEDROOM
KITCHEN
LIVING
ROOM
GARAGE
DINING ROOM KITCHEN
LIVING ROOM
BEDROOMBEDROOM
BEDROOM
Key
• Smoke Alarm
Δ
Smoke Alarm with False Alarm Control
60cm
STUB WALL
SOFFIT
10cm
10cm
MINIMUM
30cm
MAXIMUM
CEILING
SIDE
WALL
ACCEPTABLE HERE
NEVER HERE
TOP OF DETECTOR
ACCEPTABLE HERE
1M
PEAKED CEILING
!
!
!
BLUE
ORANGE
BROWN
LINE
INTERLINK
NEUTRAL
CEILING
ELECTRICAL BOX OR PATTRESS
MODEL FADC230