INDUSTRIAL FIXED GAS DETECTOR, FD-60 

FORENSICS DETECTORS

TM

 

 

 

FORENSICS DETECTORS

TM 

www.forensicsdetectors.com 

 

!

 

INDUSTRIAL  
FIXED GAS  
DETECTOR 

Model: FD-60 

 

USER MANUAL 

 

 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

CONFIGURATION & 

COMPONENTS 

INCLUDED 

 

Serial #: 

 

Gas Sensor  

 

Remote Control 

 

Hex Tool 

 

24V Wall Adapter 

 

Detector 

 

Power Cable 

 

LED/Buzzer Fixture 

 

Calibration Cap 

 

QC/CAL Certificate 

 

User Manual 

 

Other 

 

 
 

 

 

 
 
 
 

Summary of Contents for FD-60

Page 1: ...TORSTM www forensicsdetectors com 1 INDUSTRIAL FIXED GAS DETECTOR Model FD 60 USER MANUAL CONFIGURATION COMPONENTS INCLUDED Serial Gas Sensor Remote Control Hex Tool 24V Wall Adapter Detector Power Cable LED Buzzer Fixture Calibration Cap QC CAL Certificate User Manual Other ...

Page 2: ...ATURES INDUSTRIAL Heavy duty fixed gas detector Comes FACTORY CALIBRATED Mount and Operate USE Remote Control up to 8 meters Analog Output 4 20mA 2 x relay alarm triggered switch 1kW to control fans pumps electrical items garage doors or additional alarms FEATURES Large LED alarm and buzzer Adjustable audio visual Alarm digital time stamp Remote Control ROBUST Explosion dust water and flame proof ...

Page 3: ...INDUSTRIAL FIXED GAS DETECTOR FD 60 FORENSICS DETECTORSTM FORENSICS DETECTORSTM www forensicsdetectors com 3 PCB Connections Remote Control ...

Page 4: ...pply DC 24V 15 Working condition Temperature 0 122F Humidity 95 RH with no condensation Storage condition Temperature 0 122F Humidity 85 RH Connection G1 2 male proof hose pipe thread size Thread size M20x1 5mm Sensor housing cap M37 x 1 5 Electrical Output 2 x relay contact output max power 1kW Communication 4 20mA only RS485 not available Weight Approx 3 pounds Dimension 200 180 90mm Warranty 1 ...

Page 5: ...m 5 F S 25s 1ppm 50ppm 100ppm CO2 0 5000ppm 5 F S 25s 1ppm 1000ppm 2000ppm H2S 0 100ppm 5 F S 30s 1ppm 10ppm 20ppm NO2 0 20ppm 5 F S 25s 0 1ppm 3ppm 10ppm NO 0 250ppm 5 F S 60s 1ppm 25ppm 50ppm SO2 0 100ppm 5 F S 30s 0 1ppm 2ppm 10pppm CL2 0 20ppm 5 F S 30s 0 1ppm 1ppm 10ppm NH3 0 100ppm 5 F S 50s 1ppm 25ppm 50ppm H2 0 1000ppm 5 F S 60s 1ppm 50ppm 10ppm HCN 0 50ppm 5 F S 200s 0 1ppm 10ppm 20ppm HC...

Page 6: ...e detector has been FACTORY calibrated Hence it is NOT necessary to perform any CALIBRATION however do ensure ALARMS are set to the users satisfaction and local exposure limit requirements as necessary per your safety officer advice or consult with local state or federal authorities The detector can be turned off by directly disconnecting the power supply We recommend BUMP testing to confirm opera...

Page 7: ...hannel Set Manufacturer only access 3 Host Set 4mA Manufacturer only access 4 Host Set 20mA Manufacturer only access 5 Set Max Manufacturer only access 6 Save Factory Manufacturer only access 7 Reset Factory Manufacturer only access 8 System Info Summarized alarms and Software Version 9 Language English or Chinese MAIN MENU 1 Back 2 Setting 3 AlarmSet 4 Gas Zero 5 Gas Check 6 AlarmData 7 Time Set ...

Page 8: ...degradation Sometimes the sensor does not return back to its ZERO baseline Also sometimes the sensor is exposed to HIGH concentrations of toxic gas and the sensor may be permanently poisoned Please ensure fresh air is exposed to the sensor for at least 30 minutes before making this determination If the zero drift of the sensor is unacceptable the user can perform a ZERO calibration operation Pass ...

Page 9: ...r example in very cold or very hot environment 0 122F Do not install within 5 ft of heating or cooking appliances Do not install near vents flues chimneys or air ventilation openings Do not install near ceiling fans doors windows or areas directly exposed to the weather so external air water or rain reaches the detector Do not install in dead air spaces such as peaks of vaulted ceilings or gabled ...

Page 10: ...TED VAPORS HARSH CHEMICALS OR EXTREMELY HIGH CONCENTRATION LEVELS AS IT MAY POISON THE SENSOR SEE APPENDIX FOR RANGES Ø FOLLOW INSTRUCTIONS AS THE DETECTOR IS VERY SENSITIVE Ø Connect the cable according to the Ex request The end of the cable need to be treated properly and should be connected to Ex junction box or equipment When the detector doesn t need to work with the controller the block is n...

Page 11: ...hird parties We shall not be liable for any incidental or consequential damages caused by the breach of any express or implied warranty Except to the extent prohibited by applicable law any implied warranty of merchantability or fitness for a particular purpose is limited in duration for 1 year THIS PRODUCT CANNOT BE REPAIRED IF THE UNIT IS TAMPERED WITH IT WILL INVALIDATE THE GUARANTEE IF THE UNI...

Page 12: ...INDUSTRIAL FIXED GAS DETECTOR FD 60 FORENSICS DETECTORSTM FORENSICS DETECTORSTM www forensicsdetectors com 12 WEB www forensicsdetectors com Email sarah forensicsdetectors com ...