SubDrive Connect Plus

QUICKSTART GUIDE

English

EN

QUICKSTART GUIDE

Physical Installation

Environmental Requirements

The drive is intended for operation in ambient temperatures from -13 °F to 122 °F (-25 °C to 50 °C). 

Allow at least 6 inches (15.24 cm) of clearance on all sides of the unit for air flow.

The drive is suitable for outdoor use with a NEMA 3R rating, provided:

Mount the drive on a back plate 6” (15 cm) larger than the outer dimensions of the 

enclosure in order to maintain the NEMA 3R rating.

The unit must be mounted vertically with the wiring end oriented downward, and the
cover must be properly secured (also applies to indoor installations).

NEMA 3R enclosures are capable of withstanding downward-directed rain only.
Protect from hose-directed or sprayed water as well as blowing rain.

Mounting the Drive

1.

Mount the drive using all three keyhole slots on the top side of the enclosure.

2. At least two keyhole screws at the top must attach to a solid structure such as a stud or

brace.

3. Secure the three additional mounting holes on the bottom.
4. All six screw hole locations should be used to ensure the drive is securely mounted.

IMPORTANT:

 Do not drill holes in the drive.

Risk of damage to drive

,

 or malfunction can occur due to improper handling,

installation, or environment.

Install in a location where temperature is within the range of product rating.

Mount VFD vertically (top up) for proper heat dissipation.

Do not mount VFD in direct sunlight or near other heat sources.

Do not install in corrosive environments.

Install away from direct sunlight and extreme temperatures or humidity.

Installation of non-approved screening may damage the drive and/or reduce output.

Cold Air

6 in mín.

(15.25 cm)

Warm Air

6 in mín.

(15.25 cm)

6 in mín.

(15.25 cm)

6 in mín.

(15.25 cm)

Risk of bodily injury or damage to drive or other equipment.

The drive should be mounted on a structure such as a wall or post capable of supporting the weight
of the unit, at least 18” (45.7 cm) above the ground.

The drive must be mounted on a heat-resistant back plate.

Ensure suitable mounting hardware is used when installing the drive.

Do not install the drive on unreinforced drywall.

Use two persons when lifting the drive for transport or installation. If using lifting equipment, it must
be in good condition and rated for at least 5 times the weight of the drive.

Wear protective gloves while installing the drive to guard against sharp edges.

This 

QuickStart Guide

 

includes basic installa

-

tion, setup, and opera

-

tion information. 
For additional important 
safety and operation 
information, please refer 
to the 

SubDrive Connect Plus 

Owner’s Manual

and the 

AIM Manual

available at:

www.franklinwater.com.

Summary of Contents for SubDrive Connect Plus SDCP-CEN0723

Page 1: ... to improper handling installation or environment Install in a location where temperature is within the range of product rating Mount VFD vertically top up for proper heat dissipation Do not mount VFD in direct sunlight or near other heat sources Do not install in corrosive environments Install away from direct sunlight and extreme temperatures or humidity Installation of non approved screening ma...

Page 2: ...AWG 20 to AWG 2 31 in lbs 3 5 Nm AWG 16 to AWG 2 0 50 in lbs 5 5 Nm Risk of damage to VFD or malfunction can occur Follow all wire routing and grounding instructions carefully Inductive currents caused by parallel wiring or close proximity between high voltage and control wiring can cause unexpected behaviors Do not run input power and motor wires in the same conduit Do not run motor wires from mu...

Page 3: ...ck on the dV dt filter 3 J10 Jumper location two jumpers here 4 J11 Jumper location two jumpers here Ground Connections 1 Make sure a service entrance ground rod is properly installed and connected 2 An input power ground wire from the supply panel must be connected to the drive 3 A dedicated output ground wire from the drive must be connected to the motor Motor and ground wires must be bundled to...

Page 4: ...tions marked Ground Red W Yellow V and Black U For drives that include a dV dt filter motor connections are made at the terminal block on the left side of the dV dt filter 3 at right In this case the terminals are marked Ground Red U Yellow V and Black W NOTE Relay terminals accept wire sizes from 12 to 26 AWG and should be tightened to a torque of 3 in lbs 0 35 Nm Do not use power tools to tighte...

Page 5: ...ode 5 PT100 1000 Connector for external RTD temperature sensor I Positive connection for excitation current circuit for two three and four wire PT100 PT1000 RTD sensors V Positive connection for voltage sensing circuit for two three and four wire PT100 PT1000 RTD sensors I V Negative connections for the excitation and voltage sensing circuits for two three and four wire PT100 PT1000 RTD sensors 6 ...

Page 6: ...ms building up pressure in a controlled manner The Pipe Fill feature is disabled when the switch is in the off down position The Pipe Fill feature is enabled when the switch is in the on up position NOTE Additional configuration of the Pipe Fill feature is available in the SubDrive Connect Plus mobile app Analog Output Selection DIP SW1 Position 4 Use this switch AO to select the signal to be repe...

Page 7: ...ressure is set using the adjusting screw on the sensor itself The Sys tem Response screen is displayed next for Pressure Sensor use Sensor Range This is only configurable when the sensor type is transducer This setting scales system operation to the installed transducer The range is 100 to 300 with a default setting of 200 PSI When changing the setting changes in 10 PSI increments Setpoints Drive ...

Page 8: ...and repeat as necessary Deep Set In cases where the pump is set very deep run the system at open discharge to pump the well down and observe carefully that an Underload is detected properly If the system does not trip as it should adjust to a higher sensitivity setting Underload Off Time This setting determines how long the drive will wait before attempting to run after an Underload event The defa...

Page 9: ...running RUN or stopped STOP 3 When using a pressure transducer the system displays the current sys tem pressure in PSI When using a standard pressure sensor the system displays the current motor speed in Hz When running in HAND mode the system displays the keypad frequency setpoint 4 When using a pressure transducer in AUTO mode the motor speed is displayed at the lower left of the screen In HAND ...

Page 10: ...th Connection After installing the SubDrive Plus app use the following procedure to connect to the drive 1 From the Home screen tap Connect New Product 2 On the New Product Wizard screen tap either Scan QR Code or Enter the Bluetooth Key 3 If using the scanning tool center the QR code on the drive in the screen The code is displayed on the VFD display and on a sticker to the right of the display R...

Page 11: ...s replace drive F7 Auto Overheated Drive High ambient temperature Direct sunlight Obstruction of airflow Fan blocked or inoperable ambient above 122 F 50 C direct sunlight Replace fan or relocate drive as necessary Remove debris from fan intake exhaust F9 Manual Internal PCB Fault A fault was found internal to drive Contact Technical Service F12 Auto Overvoltage High line voltage Internal voltage ...

Page 12: ...ation of this equipment requires detailed installation and operation instructions provided in this manual for use with this product Read entire manual before starting installation and operation End User should receive and retain manual for future use Keep safety labels clean and in good condition High voltages capable of causing severe injury or death by electrical shock are present in this unit T...