INDOOR UNIT (Cassette Type)

PART No. 9371022635

Deutsch

INNENGERÄT (Kassettentyp)

TM

Français

Español

UNITÉ INTÉRIEURE (type cassette)

UNIDAD INTERIOR (Tipo casete)

Italiano

UNITÀ INTERNA (tipo a cassetta)

Ελληνικ

ά

Português

ΕΣΩΤΕΡΙΚΗ ΜΟΝΑΔΑ (Τύπος Κασέτας)

UNIDADE INTERIOR (Tipo Cassete)

Ру

сский

Türkçe

ВНУТРЕННИЙ МОДУЛЬ (кассетного типа)

İÇ ÜNİTE (Kaset Tipi)

AUXB004GLEH

AUXB007GLEH

AUXB009GLEH

AUXB012GLEH

AUXB014GLEH

AUXB018GLEH

AUXB024GLEH

INSTALLATION MANUAL

For authorized service personnel only.

INSTALLATIONSANLEITUNG

Nur für autorisiertes Fachpersonal.

MANUEL D’INSTALLATION

MANUAL DE INSTALACIÓN

Pour le personnel agréé uniquement.

Únicamente para personal de servicio autorizado.

MANUALE DI INSTALLAZIONE

A uso esclusivo del personale tecnico autorizzato.

ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ

Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό.

MANUAL DE INSTALAÇÃO

Apenas para técnicos autorizados.

РУКОВОДСТВО ПО УСТАНОВКЕ

Только для авторизованного обслуживающего персонала.

Yalnızca yetkili servis personeli için.

MONTAJ KILAVUZU

[Original instructions]

MADE IN P.R.C.

Refer to the rating label for the serial number, 
manufactured year and month.

9371022635-01_IM.indb   1

08/02/2019   17:02:58

Summary of Contents for AIRSTAGE AUXB004GLEH

Page 1: ...ersonnel only INSTALLATIONSANLEITUNG Nur für autorisiertes Fachpersonal MANUEL D INSTALLATION MANUAL DE INSTALACIÓN Pour le personnel agréé uniquement Únicamente para personal de servicio autorizado MANUALE DI INSTALLAZIONE A uso esclusivo del personale tecnico autorizzato ΕΓΧΕΙΡΙΔΙΟ ΕΓΚΑΤΑΣΤΑΣΗΣ Μόνο για εξουσιοδοτημένο τεχνικό προσωπικό MANUAL DE INSTALAÇÃO Apenas para técnicos autorizados РУКОВ...

Page 2: ...ny substance other than the prescribed refrigerant into the refrigera tion cycle If air enters the refrigeration cycle the pressure in the refrigeration cycle will become abnormally high and cause the piping to rupture If there is a refrigerant leakage make sure that it does not exceed the concentration limit If a refrigerant leakage exceeds the concentration limit it can lead to accidents such as...

Page 3: ...lorine gas acid or alkali It will cause the copper pipes and brazed joints to corrode which can cause refrigerant leakage Area that can cause combustible gas to leak contains suspended carbon fibers or flammable dust or volatile inflammables such as paint thinner or gasoline If gas leaks and settles around the unit it can cause a fire Area where animals may urinate on the unit or ammonia may be ge...

Page 4: ...nging bolt position 540 Hanging bolt position 570 Indoor unit 135 250 150 to 200 Min 450 Service access 75 Min 450 A Cassette grille Unit mm Fig C B Ceiling openings Cassette grille Standard type Grid type A 700 620 B 580 to 660 580 to 610 40 102 99 30 58 123 30 40 146 245 262 Drain pipe O D ø25 4 Unit mm Fig D Ceiling Control box Liquid pipe Gas pipe Special nut A Special nut B Hook Hanging bolt ...

Page 5: ...them anymore Do not bend or stretch the pipes more than 3 times CAUTION To prevent breaking of the pipe avoid sharp bends If the pipe is bent repeatedly at the same place it will break 4 3 3 Pipe connection When the flare nut is tightened properly by your hand hold the body side coupling with a separate spanner then tighten with a torque wrench See the table below for the flare nut tightening torq...

Page 6: ...r Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Do not modify the power cables use extension cables or use any branches in the wir ing Improper connections insufficient insulation or exceeding the allowable current can cause electric shock or fire Match the terminal block numbers and connection cable colors with those of the outdoo...

Page 7: ...over wiring of power supply Indoor unit Pull box Pull box Power supply Power supply Power supply Indoor unit Indoor unit Breaker Power supply 6 3 Unit wiring Before attaching the cable to terminal block 6 3 1 Power supply cable Adjust the length of power supply cable to avoid excessive tension with referring the figure Earth Ground cable 20 mm 50 mm A For solid core wiring 1 To connect the electri...

Page 8: ...AUTION Do not bundle the remote controller cable or wire the remote controller cable in parallel with the indoor unit connection cable to the outdoor unit and the power supply cable It may cause erroneous operation 6 5 Optional parts wiring 6 5 1 Layout of the indoor unit PCB CAUTION Do not operate any switches other than prescribed as it can cause the unit to operate improperly or malfunction Use...

Page 9: ...ress a voltage exceeding 24V across pins 1 2 and 1 3 a The allowable current is DC 5mA to 10mA Recommended DC5mA Provide a load resistance such that the current becomes DC10mA or less Select very low current use contacts usable at DC12V DC1mA or less b The polarity is for pin 1 and for pin 2 and 3 Connect correctly When connected to Apply voltage terminals of multiple indoor units with a connected...

Page 10: ...oor unit fan stop DC 12 V Indoor unit fan operation 7 FIELD SETTING There are 3 methods for address setting by FIELD SETTING as follows Set by either of the methods Each setting method is described 1 to 3 below 1 IU AD REF AD SW settings This section 7 1 Setting the address 2 Remote controller settings Refer to the wired or wireless remote controller manual for detailed setting information Set IU ...

Page 11: ... 1 02 Adjust 2 Heat air temperature trigger 31 00 Standard Adjust the heat air trigger tempera ture To lower the trigger temperature by 6 degrees C use setting 01 To lower the trigger temperature by 4 degrees C use setting 02 To raise the trigger temperature use setting 03 01 Adjust 1 02 Adjust 2 03 Adjust 3 Auto restart 40 00 Enable Enable or disable automatic system restart after a power outage ...

Page 12: ...ple ADDRESS 24 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 10 sec 1 cycle 12 sec 8 sec ON OFF 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s 0 5s ON OFF ON OFF ON Refrigerant address example Example ADDRESS 30 OPERATION indicator lamp Green TIMER indicator lamp Orange FILTER indicator lamp Red 9 sec 1 cycle 12 sec ON OFF 1 0s 1 0s 1 0s 1 0s 1 0s 1 0...

Page 13: ...s and outlets free of any obstacles No cooling No heating Does start and stop air conditioner op eration by remote control unit or external device No operation After installation is completed has the proper operation and handling been explained to the user 11 ERROR CODES If you use a wired type remote controller error codes will appear on the remote controller display If you use a wireless remote ...