background image

 
 
 

Max.Hp 

For AC Motors

Max.  
Volt-  
age

Max. 

Continous  

Amp  

Rating

AC Volts

Single-
Phase

Poly- 
Phase

600 

45

115 
200 
230 

460/575 

7½ 

-

10 
15 
25

CAUTION

:

 

Before  installing  in  a  nuclear 

application, determine that the product is 
intended for such use.

 

DESCRIPTI

 

ON

  

ABB

 300-Line full voltage magnetic c

 

o

 

mbination starter consists of a magnetic c
ontactor with a three leg block overload 
relay and a manually operated circuit 
breaker or disconnect switch. The 
disconnect 

 

switch may either be fusible or 

non-fusible. The

 

 non-fusible disconnect 

switch prov

 

ides a means of manually 

disconnecti

 

ng the motor from the line. The 

circuit break

   

er or fusible disconnect switch 

provides m

 

otor branch short-circuit 

protection. 

 

The overload relay provides, 

motor prote

   

ction against running and 

stalled mot

 

or overload.

The  overload  relay  is  provided  with  a 
yellow  trip  indicator  which  is  located  to 
the  right  of  the  reset  arm,  and  is  visible 
when  the  overload  relay  is  tripped. 

FEATURES 
1.

Strongbox coil.

2.

Overload relay, incorporates a dial for

±10% field adjustment of tripping current,
so that it is no longer necessary to change
heaters to eliminate such problems as
nuisance tripping in hot weather.

3.

Overload trip indicator.

4.

Straight through wiring.

5.

Oversized power terminals will

accommodate up to #4 wire.

6.

Starter can be disassembled and

inspected in a matter of seconds.

7.

Circuit breaker or disconnect switch is

mechanically interlocked with the
enclosure door to prevent opening the door
until the handle is moved to the OFF
position.

COIL REMOVAL

  

The encapsulated coil is impervious 
to moisture, dirt, and oil. It resists 
mechanical damage and failure due 
to high humidity. No tools are 
required to remove coil. 

1.

Remove power from device.

2.

Press against coil while pulling up

slightly on coil retainers (A—Figure 1
or 2) and move retainers away from
coil.

3.

Withdraw magnet assembly, coil,

molded cover, and movable arm
from device.

4.

Withdraw spring clip (B—Figure 1

or 2) and remove armature from
movable arm.

5.

Remove coil from magnet.

6.

Replace coil.

7.

Reassemble device by reversing

procedure.

2.

Clean magnet mating surfaces

of any dust or foreign matter.

3.

Select heaters in accordance

with heater table, which
accompanies each device.

4.

Operate movable magnet and

operating arm by pressing on the
nameplate to assure free
movement.

5.

Mount the starter on a sturdy

vertical support.

6.

The overload relay may be reset

manually by depressing and
releasing the reset arm. Overload
relays with an optional normally
open contact are electrically
isolated from the normally closed
contact.

7.

Provide motor branch circuit

protection in accordance with the
National Electrical Code.
 

CONTACT REMOVAL

Movable contacts can be inspected
and replaced in seconds—without
tools (Figure 3).

WARN

 

ING:

 Disconnect 

power before Installing or 

servicing.

RATINGS 

INSTALLATION 

Before connecting the starter: 

1.

Remove all packing.

These instructions do not purport to cover all details or variations in equipment not to provi

 

de for every possible contingency to 

be met in connection with installation, operation or maintenance. Should further information be desired or should particular 
problems arise which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to the

 ABB 

Company.

 

1

GEH

-

4776 

Installation Instructions 

for NEMA S

ize

 2

300/400 -Line Combination  Magnetic Starters 

CR307-CR308, CR310-CR311, CR387, CR390, CR407-CR408 

CR410-CR415, CR487, CR490, CR492, CR494 Series 