TTOONNEE TTYYPPEE
TTOONNEE DDEESSCCRRIIPPTTIIOONN// AAPPPPLLIICCAATTIIOONN
970Hz
800Hz/970Hz @ 2Hz
800Hz – 970Hz @ 1Hz
970Hz 1s OFF/1s ON
970Hz, 0.5s/ 630Hz, 0.5s
554Hz, 0.1s/ 440Hz, 0.4s (AFNOR NF S 32 001 )
500 – 1200Hz, 3.5s/ 0.5s OFF (NEN 2575:2000)
420Hz 0.625s ON/0.625s OFF (Australia AS1670 Alert tone)
500 – 1200Hz, 0.5s/ 0.5s OFF x 3/1.5s OFF ( AS1670 Evacuation)
550Hz/440Hz @ 0.5Hz
970Hz, 0.5s ON/0.5s OFF x 3/ 1.5s OFF (ISO 8201 )
2850Hz, 0.5s ON/0.5s OFF x 3/1.5s OFF (ISO 8201)
1200Hz – 500Hz @ 1Hz (DIN 33 404)
400Hz
550Hz, 0.7s/1000Hz, 0.33s
1500Hz – 2700Hz @ 3Hz
750Hz
2400Hz
660Hz
660Hz 1.8s ON/1.8s OFF
660Hz 0.15s ON/0.15s OFF
510Hz, 0.25s/ 610Hz, 0.25s
800/1000Hz 0.5s each (1Hz)
250Hz – 1200Hz @ 12Hz
500Hz – 1200Hz @ 0.33Hz
2400Hz – 2900Hz @ 9Hz
2400Hz – 2900Hz @ 3Hz
800Hz – 970Hz @ 100Hz
800Hz – 970Hz @ 9Hz
800Hz – 970Hz @ 3Hz
800Hz, 0.25s ON/1s OFF
500Hz – 1200Hz, 3.75s/0.25s OFF (AS2220)
DDIIPP SSW
WIITTCCHH
O - O - O - O - O
O - O - O - O - I
O - O - O - I - O
O - O - O - I - I
O - O - I - O - O
O - O - I - O - I
O - O - I - I - O
O - O - I - I - I
O - I - O - O - O
O - I - O - O - I
O - I - O - I - O
O - I - O - I - I
O - I - I - O - O
O - I - I - O - I
O - I - I - I - O
O - I - I - I - I
I - O - O - O - O
I - O - O - O - I
I - O - O - I - O
I - O - O - I - I
I - O - I - O - O
I - O - I - O - I
I - O - I - I - O
I - O - I - I - I
I - I - O - O - O
I - I - O - O - I
I - I - O - I - O
I - I - O - I - I
I - I - I - O - O
I - I - I - O - I
I - I - I - I - O
I - I - I - I - I
ddBBAA @
@ 11m
m
99
100
100
99
99
97
99
96
98
97
98
94
99
95
98
104
99
106
96
96
96
98
100
98
99
101
104
100
99
100
99
99
m
mAA
17
16
16
10
15
09
12
5
6
10
8
17
13
9
13
30
14
41
13
8
7
11
17
9
14
36
36
16
16
6
4
13
22nndd
18
1
1
5
1
1
1
9
1
19
1
1
1
18
1
1
1
1
18
19
19
1
1
1
1
18
18
1
1
1
1
8
AS363 & AS364 Sounder Range
Installation Instructions
Fig. 1
GE Security, Kelvinstraat 7, NL- 6003DH Weert, The Netherlands.
Phone +31 495 45 67 35 Fax: +31 495 55 00 42
Revision 1.
1
(
July
2007) 18-186755
Copyright © 2007GE Security B.V.. All Rights Reserved
http://www.gesecurity.eu
EN54-3
Technical Data Document 18-186213
Fire Alarm Device - Sounder
Type A: For indoor use
(Shallow Base)
Type B: For outdoor use
(Deep Base)
0832
06
AS363: 0832-CPD-0556
AS364: 0832-CPD-0557
AS363W 0832-CPD-0558
AS364W 0832-CPD-0559
FFRR
NNLL
EENN
DDEE
EESS
PPTT
IITT
PPLL
SSEE
DDKK