background image

Ground  Fault 

Circuit Breaker

LED

120Vac 

Duplex 

Receptacle

Load 

Power 

Wire 

(Black)

Load 

Neutral 

Wire 

(White)

Short White 

WireConnects to 

Panel Neutral

Installer Instructions

Install the Ground Fault Circuit Interrupter with 

Self-Test (GFCI) using the following procedure:
1.  Ensure power to the panel is “OFF” and read all 

warnings on the adjacent page before installation of 

the GFCI commences.

2. Move handle of breaker to “OFF” position.
3.  Connect the coiled white wire (pigtail) of the GFCI to 

any terminal on the neutral bar in the panel.

4.  Connect the WHITE insulated neutral load wire of the 

circuit to be protected to the GFCI’s terminal lug 

marked LOAD NEUTRAL.

5.  Connect the BLACK insulated load wire of the circuit 

to be protected to the GFCI’s terminal lug marked 

LOAD POWER. Check to assure the GFCI is still in 

“OFF” position and all wires are properly connected.

6. Install the wired GFCI into the panel.
7. Restore power to the panel.
8.  Test the GFCI using the push button switch on the 

front of the breaker. Follow Test Procedures as 

indicated in next section.

9.  See Troubleshooting Guide for the troubleshooting 

method to be used for a tripped GFCI.

D EH43 3 8 B  H O M EOW N ER  &  I N S TA LLER  I N FO R M ATI O N

Ground Fault Circuit Interrupter  

with Self-Test Feature (GFCI)  

Type THQ/THHQ 15A-30A, 1 Pole

WARNING: Failure to follow these instructions could 

result in death, personal injury, or property damage.

See Troubleshooting Guidelines on the second page 

of this instruction sheet. This equipment must be 

installed and serviced only by a qualified electrician.
WARNING: Turn off power to main breaker before 

beginning installation. Failure to do so will risk 

electrical shock and possible death, personal injury, 

or property damage.
WARNING: Do not reverse-feed or back-wire. Do not 

subject circuit breaker to megger, high-voltage, or 

high-pot tests. Remove the circuit breaker before 

high-pot testing the circuit or the system.
CAUTION: The Ground Fault Circuit Interrupter 

(GFCI) must be supplied with power from the load 

center in order for the push to test to function 

properly. If the power is on and push to test fails to 

trip or the LED turns on or blinks (indicating the 

self-test feature has detected an issue), the GFCI 

may not be able to detect leakage current. The circuit 

breaker is defective and should be replaced.
NOTE: These instructions do not cover all details or 

variations in equipment nor do they provide for 

every possible contingency that may be met in 

connection with installation, operation, or 

maintenance. Should further information be desired 

or should particular problems arise that are not 

covered sufficiently for the purchaser’s purposes, 

the matter should be referred to the ABB Company. 

See contact information on next page.

Test Procedures (GFCI should be tested regularly,  

at least once per month.)

1.  With handle B in “ON” position, press 

“PUSH TO TEST” button A up or down.

2.  Handle B should move to “TRIP” position, 

indicating that GFCI has opened the 

circuit.

3.  To restore power, move handle B to “OFF” 

and then “ON”.

IMPORTANT: If handle B does not move to “TRIP” 

position when “TEST” button is pressed, the GFCI’s 

protection is not complete. Replace breaker 

immediately.

GE 

Industrial Solutions

GFCI = Interruptor de circuito por falla de conexión a 

tierra con función de auto prueba 

Instrucciones de instalación

Instala el interruptor de circuito por falla de 

conexión a tierra con función de auto prueba (GFCI) 

mediante el siguiente procedimiento:

1.   Asegúrate de que el suministro de electricidad al panel esté 

APAGADO (OFF) y lee todas las advertencias en la página 

siguiente antes de comenzar la instalación del GFCI.

2.   Mueve la manija del cortacircuitos a la posición de  

APAGADO (OFF).

3.   Conecta el cable blanco enrollado (cable de extensión) del 

GFCI a cualquier terminal de la barra neutra en el panel.

4.   Conecta el cable BLANCO de carga neutro con aislamiento 

del circuito que se va a proteger, a la lengüeta terminal del 

GFCI marcada como NEUTRO DE CARGA (LOAD NEUTRAL).

5.   Conecta el cable NEGRO de carga con aislamiento del circuito 

que se va a proteger, a la lengüeta terminal del GFCI marcada 

como ALIMENTACIÓN DE CARGA (LOAD POWER). Asegúrate 

de que el GFCI esté aún en la posición de APAGADO (OFF) y 

todos los cables bien conectados.

6.  Instala el GFCI con cables en el panel.

7.   Restaura el suministro de electricidad al panel.

8.   Comprueba el GFCI usando el botón interruptor en la parte 

frontal del cortacircuitos. Sigue los procedimientos de 

prueba enumerados en la siguiente sección.

9.   Consulta la Guía para Solución de Problemas para el método 

adecuado en caso de un GFCI activado.

Procedimientos de prueba

El GFCI debe probarse con regularidad, al menos 

una vez al mes.

1.   Con la manija B en la posición de ENCENDIDO  

(ON), presiona el botón A OPRIME PARA  

PROBAR (PUSH TO TEST) hacia arriba o abajo.

2.   La manija B debe moverse a la posición 

de ACTIVAR (TRIP), indicando que el GFCI 

ha abierto el circuito.

3.   Para restaurar la electricidad, mueve la  

manija B a la posición de APAGADO (OFF)  

y enseguida a ENCENDIDO (ON).

GEH-4338A Instrucciones de instalación e información para propietarios

Interruptor de circuito  

por falla de conexión 

a tierra con función 

de auto prueba (GFCI)

Tipo THQ/THHQ

15 A-30 A, 1 Poste

ADVERTENCIA:

 No seguir estas instrucciones puede ocasionar la 

muerte, lesiones personales o daños a la propiedad.
Consulta las indicaciones de Solución de Problemas en la segunda 

página de esta hoja de instrucciones. La instalación y el mantenimiento 

de este equipo tienen que realizarse sólo por un electricista calificado.

PRECAUCIÓN:

 El interruptor de circuito por falla de conexión a 

tierra (GFCI) debe recibir electricidad del centro de carga para que la 

prueba funcione bien. Si hay suministro de electricidad y la prueba 

no activa el GFCI, o si la luz LED se ilumina o parpadea (indicando que 

la función de auto prueba ha detectado un problema), puede que el 

GFCI no detecte fugas de corriente. El cortacircuitos está defectuoso 

y debe ser reemplazado.

AVISO:

 Estas instrucciones no cubren todos los detalles ni 

variaciones de los equipos ni resuelven toda contingencia que 

pudiera sobrevenir con la instalación, operación o mantenimiento. 

Si deseas más información o se presentan problemas particulares 

que no estén cubiertos suficientemente para los propósitos del 

comprador, el asunto debe remitirse a la compañía GE.  Consulta la 

información de contacto en la página siguiente.

ADVERTENCIA:

 Corta el suministro de electricidad al cortacircuitos 

principal antes de comenzar la instalación. No hacerlo puede 

ocasionar descargas eléctricas y hasta la muerte, lesiones 

personales y daños a la propiedad.

IMPORTANTE:

 Si la manija B no se mueve a la posición de ACTIVAR 

(TRIP) cuando se oprime el botón PRUEBA (TEST), la protección del 

GFCI no está completa. Reemplaza el cortacircuitos de inmediato.

ADVERTENCIA:

 No inviertas la conexión de ningún cable. No 

sometas el cortacircuitos a pruebas Megger ni de alto voltaje o 

exceso de potencia. Retira el cortacircuitos antes de realizar una 

prueba de alta potencia en el circuito o el sistema.

imagination at work

20

B

TRIP

OFF

ON

TEST

A

Ground Fault 

Circuit Breaker

120Vac

Duplex

Receptacle

Load

Neutral

Wire

(White)

Coiled

White Wire

Connects to

Panel Neutral

Load

Power

Wire

(Black)

LED

Toma 

doble 

120 V c.a.

Cable 

neutro 

(blanco)

Cable 

de alta 

tensión

(negro)

El cable blanco en espiral 

se contecta al tablero de  

distribución

Disyuntor 

de descarga a tierra

imagination at work

GE 

Industrial Solutions

GFCI = Ground Fault Circuit Interrupter with Self-Test 

Installation Instructions

Install the Ground Fault Circuit Interrupter with  
Self-Test (GFCI) using the following procedure:

1.   Ensure power to the panel is “OFF” and read all warnings on 

the adjacent page before installation of the GFCI commences.

2.  Move handle of breaker to “OFF” position.
3.   Connect the coiled white wire (pigtail) of the GFCI to any 

terminal on the neutral bar in the panel.

4.   Connect the WHITE insulated neutral load wire of the 

circuit to be protected to the GFCI’s terminal lug marked 
LOAD NEUTRAL.

5.   Connect the BLACK insulated load wire of the circuit to be 

protected to the GFCI’s  terminal lug marked LOAD POWER. 
Check to assure the GFCI is still in “OFF” position and all 
wires are properly connected.

6.  Install the wired GFCI into the panel.
7.   Restore power to the panel.
8.   Test the GFCI using the push button switch on the front of 

the breaker. Follow Test Procedures as indicated in next 
section.

9.   See Troubleshooting Guide for the troubleshooting method 

to be used for a tripped GFCI.

Test Procedures

GFCI should be tested regularly, at least once  
per month.
1.   With handle B in “ON” position, press  

“PUSH TO TEST” button A up or down.

2.   Handle B should move to “TRIP” position,  

indicating that GFCI has opened the circuit.

3.   To restore power, move handle B to “OFF”  

and then “ON”.

GEH-4338A Installation Instructions & Homeowner Information

Ground Fault  

Circuit Interrupter with  

Self-Test Feature (GFCI)

Type THQ/THHQ
15A-30A, 1 Pole

WARNING: Failure to follow these instructions could result in 

death, personal injury, or property damage. 
See Troubleshooting Guidelines on the second page of this instruc-

tion sheet. This equipment must be installed and serviced only by a 

qualified electrician.

CAUTION: The Ground Fault Circuit Interrupter (GFCI) must be 

supplied with power from the load center in order for the push to 

test to function properly. If the power is on and push to test fails 

to trip or the LED turns on or blinks (indicating the self-test feature 

has detected an issue), the GFCI may not be able to detect leakage 

current. The circuit breaker is defective and should be replaced.

NOTICE: These instructions do not cover all details or variations 

in equipment nor do they provide for every possible contingency 

that may be met in connection with installation, operation, or 

maintenance. Should further information be desired or should 

particular problems arise that are not covered sufficiently for the 

purchaser’s purposes, the matter should be referred to the GE 

Company.  See contact information on next page.

WARNING: Turn off power to main breaker before beginning  

installation. Failure to do so will risk electrical shock and possible 

death, personal injury, or property damage.

IMPORTANT: If handle B does not move to “TRIP” position when 

“TEST” button is pressed, the GFCI ’s protection is not complete. 

Replace breaker immediately.

WARNING: Do not reverse-feed or back-wire. Do not subject circuit 

breaker to megger, high-voltage, or high-pot tests. Remove the 

circuit breaker before high-pot testing the circuit or the system.

Ground Fault 

Circuit Breaker

120Vac

Duplex

Receptacle

Load

Neutral

Wire

(White)

Coiled

White Wire

Connects to

Panel Neutral

Load

Power

Wire

(Black)

LED

20

B

TRIP

OFF

ON

TEST

A

imagination at work

GE 

Solutions industrielles

GFCI = Disjoncteur de fuite à la terre avec 
autovérification
 

Instructions d’installation

Installez le disjoncteur de fuite à la terre avec 
autovérification (GFCI) au moyen de la procédure 
suivante :

1.   Vérifiez que l’alimentation électrique au tableau de distribution 

est «COUPÉE (OFF)» et veillez à lire tous les avertissements à la 

page adjacente avant de commencer l’installation du disjoncteur 

de fuite à la terre.

2.  Déplacez la manette du disjoncteur en position «ARRÊT (OFF)».

3.   Connectez le fil blanc en spirale (queue-de-cochon) du 

disjoncteur de fuite à la terre à n’importe quelle borne de la 

barre neutre du tableau de distribution.

4.   Connectez le fil BLANC isolé neutre du circuit devant être 

protégé à la cosse de borne du disjoncteur de fuite à la terre 

portant la mention NEUTRE (LOAD NEUTRAL).

5.   Connectez le fil NOIR isolé du circuit devant être protégé à 

la cosse de borne du disjoncteur de fuite à la terre portant 

la mention SOUS TENSION (LOAD POWER). Vérifiez que le 

disjoncteur de fuite à la terre est toujours en position «ARRÊT 

(OFF)» et que tous les fils sont connectés correctement.

6.   Installez le disjoncteur de fuite à la terre câblé dans le tableau de 

distribution.

7.   Restaurez le courant au tableau de distribution.

8.   Essayez le disjoncteur de fuite à la terre au moyen de 

l’interrupteur à bouton-poussoir sur le devant du disjoncteur. 

Suivez les procédures d’essai indiquées dans la section suivante.

9.   Consultez le Guide de dépannage pour la procédure à suivre 

dans le cas d’un disjoncteur de fuite à la terre déclenché.

Procédures de vérification

Le disjoncteur de fuite à la terre doit être vérifié régulièrement, 

au moins une fois par mois.
1.   Avec la manette B en position «MARCHE (ON)», 

appuyez sur le bouton A «POUSSOIR DE TEST 
(PUSH TO TEST)» vers le haut ou le bas.

2.   La manette B doit se déplacer en position 

«DISJONCTÉ (TRIP)», pour indiquer que le 
disjoncteur de fuite à la terre a ouvert le circuit.

3.   Afin de restaurer l’alimentation électrique,  

déplacez la manette B en position  
«ARRÊT (OFF)» puis «MARCHE (ON)».

GEH-4338A Instructions d’installation et renseignements pour les 

propriétaires résidentiels

Disjoncteur de fuite 

à la terre avec fonction 

d’autovérification (GFCI)

Type THQ/THHQ
15 A à 30 A, 1 pôle 

AVERTISSEMENT : Tout manquement à suivre ces instructions peut 

entraîner la mort, des blessures ou des dommages matériels.
Consultez le Guide de dépannage à la seconde page de cette 

feuille d’instructions. Cet équipement doit être installé et réparé 

par un électricien qualifié uniquement.

ATTENTION : Le disjoncteur de fuite à la terre (GFCI) doit être  

alimenté par le courant du tableau de distribution pour que le  

bouton poussoir de test fonctionne correctement. Si l’alimentation  

électrique est en marche et que le bouton poussoir de test ne 

fait pas disjoncter ou que le voyant à DEL s’allume ou clignote 

(indiquant que la fonction d’autovérification a détecté un 

problème), il se peut que le disjoncteur de fuite à la terre ne 

puisse pas détecter un courant de fuite. Le disjoncteur est 

défectueux et il faut le remplacer.

AVIS : Ces instructions ne prétendent pas couvrir tous les détails et 

variantes de l’équipement, ni informer sur toutes les éventualités 

rencontrées lors de l’installation, l’utilisation et l’entretien. Si vous  

souhaitez plus d’informations ou rencontrez un problème spécifique,  

qui ne soit pas suffisamment couvert ici pour vos besoins, la demande  

d’assistance doit être adressée à GE Company.  Les coordonnées se 

trouvent à la page suivante.

AVERTISSEMENT : Coupez l’alimentation électrique au disjoncteur 

principal avant d’entamer l’installation. Tout manquement à le faire 

peut entraîner un choc électrique, voire la mort, des blessures ou 

des dommages matériels.

IMPORTANT : Si la manette B ne se déplace pas en position «DISJONCTÉ 

(TRIP)» lorsque vous appuyez sur le bouton «TEST», la protection offerte 

par le disjoncteur de fuite à la terre n’est pas complète. Remplacez 

immédiatement le disjoncteur.

AVERTISSEMENT : N’inversez pas les connexions et n’effectuez pas  

de câblage arrière. Ne soumettez pas le disjoncteur à un mégohm-

mètre, à une tension élevée ou à des essais diélectriques. Retirez 

le disjoncteur avant l’essai diélectrique du circuit ou du système.

20

B

TRIP

OFF

ON

TEST

A

Ground Fault 

Circuit Breaker

120Vac

Duplex

Receptacle

Load

Neutral

Wire

(White)

Coiled

White Wire

Connects to

Panel Neutral

Load

Power

Wire

(Black)

LED

Double 

prise 

120 V c.a.

Fil 

sous

tension

(noir)

Le fil blanc en spirale

se branche sur le

tableau de distribution

16760_GFCI_Instructions_1pole_Eng_Fr_Sp_17x8.5_FINAL.indd   1-3

7/29/15   9:28 AM

NOTE: The neutral pigtail on eMCB’s (AFCI, GFCI and 

DFCI) can be cut to length in the field or extended 

using approved connectors. Additionally, eMCB’s with 

shortened neutrals can be installed as shown 

providing a fast and clean installation.

Summary of Contents for THQ Series

Page 1: ...ll the Ground Fault Circuit Interrupter with Self Test GFCI using the following procedure 1 Ensure power to the panel is OFF and read all warnings on the adjacent page before installation of the GFCI commences 2 Move handle of breaker to OFF position 3 Connect the coiled white wire pigtail of the GFCI to any terminal on the neutral bar in the panel 4 Connect the WHITE insulated neutral load wire o...

Page 2: ... a 2 pole GFCI breaker Other forms of shared neutrals can only be corrected by some rewiring This GFCI must have its own private circuit GFCI Self Test Breaker Functional Checks Unplug all items from the receptacles in the circuit Reset the breaker by switching it OFF and then ON 1 If the breaker trips go to step 2 If LED turns on or blinks continuously or LED turns on or blinks and the breaker ha...

Page 3: ...acircuitos de inmediato imag GE Industrial Solutions GFCI Ground Fault Circuit Interrupter with Self Test Installation Instructions Install the Ground Fault Circuit Interrupter with Self Test GFCI using the following procedure 1 Ensure power to the panel is OFF and read all warnings on the adjacent page before installation of the GFCI commences 2 Move handle of breaker to OFF position 3 Connect th...

Page 4: ...ste GFCI tiene que contar con su propio circuito privado Comprobaciones de la función de auto prueba del cortacircuitos GFCI Desenchufa todos los equipos de los receptáculos del circuito Reinicia el cortacircuitos colocándolo en APAGADO OFF y enseguida en ENCENDIDO ON 1 Si el cortacircuitos se activa ve al paso 2 Si la luz LED se enciende o parpadea constantemente o se enciende o parpadea y la man...

Page 5: ...a manette B ne se déplace pas en position DISJONCTÉ TRIP lorsque vous appuyez sur le bouton TEST la protection offerte par le disjoncteur de fuite à la terre n est pas complète Remplacez immédiatement le disjoncteur imag GE Industrial Solutions GFCI Ground Fault Circuit Interrupter with Self Test Installation Instructions Install the Ground Fault Circuit Interrupter with Self Test GFCI using the f...

Page 6: ...cteur de fuite à la terre à 2 pôles D autres mises en commun de fils neutres ne peuvent être corrigées qu en re câblant Ce disjoncteur de fuite à la terre doit être doté de son propre circuit Essais de fonctionnement de l autovérification du disjoncteur de fuite à la terre Débranchez tous les appareils des prises du circuit Réarmez le disjoncteur en le mettant à l ARRÊT OFF puis en MARCHE ON 1 Si ...

Reviews: