background image

 

Model

 

EAT-CH200A 

Description 

Generator interlock kit Eaton / Cutler Hammer 150 and 200 Amp CH 
Series panel PRE 2019 

Main Breaker

 

150 or 200 amp single handle Horizontal throw left (on) to right (off)  

Generator Breaker

 

Top left side 2 positions 

 

 

 

WARNING 

Only qualified personnel should be working on the panel box 

An amateur should 

NEVER

 open the panel box 

Please follow all rules and regulations of the National Electric Code

 

 

Step 1:  Disassemble the interlock. Place the bottom plate (holes only) above the top left breaker and mark holes.  Plate is parallel to 

left top breaker and touches the edge of the right top breaker. 

 

 

Step 2:  Turn off main breaker and remove panel cover.  

 

Step 3:  Drill holes as marked on panel cover with supplied 3/16 drill bit and remove all burs from drilling cover. 

 

Step 4:   Insert screws from rear of cover, install bottom plate, and install top plate (slotted) install thread lock to screws and install 

retaining nuts. Ensure proper movement. 

 

Step 5:  Install 2 pole Generator breaker on top left side and place Generator Warning Sticker on Generator breaker. 

 

Step 6:   Combine the zip ties to make a loop and install zip ties around top set of breakers in panel as shown in picture below. Pull on 

ends to make tight around breakers. Trim zip ties as needed and  Install Warning label next to release tab on zip tie at 
generator breaker. 

 

 