Model

 

SIE-P1 

Description 

Generator interlock kit Siemens and Murray 100 Amp Panel with 

Spacing 7/8 to 1 ¼ between Main and Generator breaker

 

Main Breaker

 

100 amp single handle Horizontal throw Left (on) Right (off)  

Generator Breaker

 

Top Left side 2 positions 

 

   

 

WARNING 

Only qualified personnel should be working on the panel box 

An amateur should 

NEVER

 open the panel box 

Please follow all rules and regulations of the National Electric Code

 

 

Step 1:  Disassemble the interlock. Place the bottom plate (holes only) and follow cutout of the main breaker as in picture 

 

 

Step 2:  Turn off main breaker and remove panel cover.  

 

Step 3:  Drill holes as marked on panel cover with supplied 3/16 drill bit and remove all burs from drilling cover. 

 

Step 4:  Insert screws from rear of cover, install bottom plate, and install top plate (slotted) install retaining nuts, and thread lock. And 

Ensure proper movement. 

 

Step 5:  Install 2 pole Generator breaker on top left side and place Generator Warning Sticker on Generator breaker. 

 

Step 6:   Combine the zip ties to make a loop and install zip ties around top set of breakers in panel as shown in picture on the next 

page. Pull on ends to make tight around breakers. Trim zip ties as needed and install Warning label next to release tab on zip 
tie at generator breaker. 