background image

9

A

B

A.

Cable compartment lid

B.

"ON" LED light

1.OVERVIEW

2.Connections/buttons/led lights

USB CONNECTION

CONNECTION AT GE552Y058

Before connecting anything, switch the power o

, complete the cabling, close the lid and

power the device on.

TROUBLESHOOTING

1) The device does not start:

2) The blue LED light does not stop 

ashing:

3) Not all the meters are revealed:

3.WALL FASTENING AND CABLE PASS

Temperature range:

Ingress Protection:
Protection Class:
Fastening:
Dimensions:
Power supply:

Consumption:
Radio Frequency:
W. M-Bus Mode:
Max distance between
two RPT:

7.TECHNICAL DATA

1

2

3

+55°C

-20°C

GE552Y053_QSG_2.4_en

Giacomini

 reserves the right to make changes to this product without any notice 

  - in case of network power supply, check that the power is on

  - in case you are using a USB port, check the USB cable quality and that the PC is enabled 

    to handle 500 mA of electrical power

  - check that the meters that were not revealed are not too distant from GE552Y053 or that 

     the signal is not disturbed by thick concrete or metal walls

  - check that the devices are on the list loaded in GE552Y053 or that the W. M-Bus devices 

      list receivable from GE552Y053 is not blocked

  - warning: some W.M-Bus devices transmit periodically (within hours)

  - check that the MESH network is not interrupted using GE552Y058 web interface or GE552Y056 sw

- Receiver and radio repeater for W. M-Bus devices (EN13757-4)

- Remarkable radio coverage due to multi-hop network 

  architecture (MESH)

- Manages up to 500 meters

- Last acquired data stored in a non-volatile memory

- Easy installation with software setup

- Simple and elegant design

- 100..240Vac power or via USB

- "Wall mounting" like installation

- USB interface for local data reading

- Optional WEB interface to match to GE552Y058

1

2

1 - Power input 100..240Vac (with clips)

2 - Multifunction button

3 - Multifunction button

4 - Reset button

5 - USB port

3 4

6 - MESH network TX-RX LED

7 - Wireless M-Bus network TX-RX LED 

8 - Signal/reception level LED

9 - State LED 

5

6 7

8

GE552Y053 repeater devices are provided with a MESH- ID=1 and channel 13, make sure that 

all the repeaters and/or GE552Y058 have the same MESH network ID and radio channel 

through GE552Y056

Operative: -20°C ... +55°C
Storage: -25°C ... +85°C
IP 40 (EN60529)
II
wall clipped
LxHxP 160x160x35mm
100..240Vac 50/60Hz
USB (5Vdc, 500mA) for commissioning
4.5W
868MHz - Max transmission power: 27dBm
S / T / C+T / S & C+T

   - check that the device GE552Y058  is on and that the antenna is connected and in good position 

     (avoid placing it in switchboards or shielded environments)

   - 1 blink "RAM memory error", 2 blinks "W.M-Bus radio module error", 

     3 blinks "MESH radio module error", 4 blinks "FLASH memory error", 5 blinks "Real Time Clock error" 

   - If turning o

 and restarting the GE552Y053,  the error does not reset, the hardware

     must be replaced.

   - check that GE552Y053 is at least 5 metres distant from GE552Y058 and from other GE552Y053

   - check that the ID and the MESH network channel are correct using GE552Y056 sw and are the

     same ones  used by GE552Y058   

1 - upper hole

2 - lowe pre-hole

3 - cable pass pre-hole

4 - power supply connection

6. REPEATER NETWORK CONFIGURATION

1. Power on GE552Y058, connect to web interface and start antenna and device scan following 

    the user’s manual

2. Power on the 

rst device GE552Y053 to be installed and move it away to a minimum distance 

    of 5 metres from GE552Y058

3. Fixed blue GE552Y053 LED shows the connection to the MESH network

4. Once connected, it shows the MESH radio signal quality to the gateway, by turning on the green 

    front LED, 1 – insu

cient reception, 2 – su

cient, 3- good, 4 – excellent

5. Put GE552Y053 in a place where the reception signal is >=2 and of all the W. M-Bus 

    devices you expect to receive with this antenna is satisfactory

6. Check through GE552Y058 web interface or through GE552Y056 software and a PC connected to the 

    antenna by USB that W. M-Bus devices, that you want to receive, reach the GE552Y053  

7. Fasten the GE552Y053 and proceed with powering a second repeater keeping at least 5 metres 

     away from both the GE552Y053 and GE552Y058  

8. Once connected, it shows the MESH radio signal quality to the gateway, by turning on the front LED, 

    so proceed as for the 

rst GE552Y053

2 x Anchor 5x25

2 x Screws 5x30

2 x Glands

1 x GE552Y053

4.PACKAGE CONTENT

N

Power

supply

connection

GE552Y053 - QuickStart Guide

Wireless M-Bus 868 MHz REPEATER

DOWNLOAD DOCUMENTATION

: https://giacomini.com/en/products/ge552-w

2 x Screw  2,2x9,5

1 x clamp headband

USB

Mini USB

GE552Y058

MIN 5 m

MIN 5 m

MIN 5 m

a) The scanning phase is 12 hours. You can modify its duration through GE552Y058

b) You can have various independent GE552Y053 networks in the same building , in that case, 

    you need to have di

erent  ID or channel for each GE552Y056 group and the relative 

    GE552Y058. 

    You can modify these parameters through GE552Y056 software installed on a pc and connected via 

    USB to GE552Y053, see user’s manual for details.

c) In case the receiver receives more than 500 W. M-Bus devices or it receives devices belonging 

    to other plants, it might be necessary to make it selective. Therefore, you can load a list of W. M-Bus 

    devices marked by their serial number through GE552Y056 software. 

    In this way, the repeater will receive the data exclusively from the listed devices.

d) The USB / Mini USB cable is not included and is not present in the package

5.POSITIONING AND OPERATING DISTANCES

MAX 25 m

MAX 25 m

GE552Y058

GE552Y053

FLOOR 1

FLOOR 0

MAX 15 m

GE552Y053

FASTENING

WALL

WALL

CEILING

MIN

20 cm

MIN

20 cm

1) Fix the GE552Y053 repeater on fastening wall at a minimum 

    distance of 20 cm from the ceiling and from the adjacent wall.

2) The maximum operating distance between the devices 

    installed on the same 

oor is 25 meters, with no major 

    obstacles such as reinforced concrete or metal walls, columns 

    or beams or other metal structures.

3) The maximum operating distance between the devices 

     installed on di

erent 

oors is 15 meters.

MIN 5 m

GE552Y053

MIN 5 m

GE552Y053

MAX 25 m

MAX 15 m

Manufactured by GIACOMINI SPA - Via per Alzo 39 - 28017 San Maurizio d'Opaglio (NO) - Italy

For details on the con

guration of the GE552Y053 using the buttons, see the back of this

document, in the dedicated section.

L

max 2x1,5 mm

o 6 mm

4

Reviews: