Model BDF • Belt Drive Duct Fan

Installation, Operation and Maintenance Manual

Please read and save these instructions for future reference. Read carefully before attempting 
to assemble, install, operate or maintain the product described. Protect yourself and others by 
observing all safety information. Failure to comply with instructions could result in personal injury 
and/or property damage!

®

PN 458341

Model BDF 

Belt Drive Duct Fan

DANGER

Always disconnect, lock and tag power source before 
installing or servicing. Failure to disconnect  power 
source can result in fire, shock or serious injury.

CAUTION

When servicing the fan, motor may be hot enough 
to cause pain or injury. Allow motor to cool before 
servicing.

CAUTION

Precaution should be taken in explosive 

atmospheres.

General Safety Information

Only qualified personnel should install this fan. 
Personnel should have a clear understanding of 
these instructions and should be aware of general 
safety precautions. Improper installation can result 
in electric shock, possible injury due to coming in 
contact with moving parts, as well as other potential 
hazards. Other considerations may be required if 
seismic activity is present. If more information is 
needed, contact a licensed professional engineer 
before moving forward.

  1.  Follow all local electrical and safety codes, as 

well as the National Electrical Code (NEC) and 
the National Fire Protection Agency (NFPA), 
where applicable. Follow the Canadian Electric 
Code (CEC) in Canada.

  2.  The rotation of the wheel is critical. It must be 

free to rotate without striking or rubbing any 
stationary objects.

  3.  Motor must be securely and adequately 

grounded.

  4.  Do not spin fan wheel faster than max cataloged 

fan RPM. Adjustments to fan speed significantly 
effects motor load. If the fan RPM is changed, 
the motor current should be checked to make 
sure it is not exceeding the motor nameplate 
amps.

  5.  Do not allow the power cable to kink or come 

in contact with oil, grease, hot surfaces 
or chemicals. Replace cord immediately if 
damaged.

  6.  Verify that the power source is compatible with 

the equipment.

  7.  Never open access doors to a duct while the fan 

is running.

Model BDF

Belt Drive Duct Fan

Model BDF is a belt drive duct supply, exhaust or return air fan. These 
fans  are  specifically  designed  for  inline  applications.  Performance 
capabilities range up to 15,000 cfm 

(25,500 m

3

/hr) 

and up to 3.0 in. wg 

(747 Pa)

 of static pressure. BDF fans are available in seven sizes with 

nominal wheel diameter ranging from 8 to 20 inches 

(203 to 508 mm)

 

(080 - 200 unit sizes).  Each  fan  shall  bear  a  permanently  affixed 
manufacture’s  engraved  metal  nameplate  containing  the  model 
number and individual serial number.

Summary of Contents for Belt Drive Duct Fan BDF

Page 1: ...ional engineer before moving forward 1 Follow all local electrical and safety codes as well as the National Electrical Code NEC and the National Fire Protection Agency NFPA where applicable Follow the Canadian Electric Code CEC in Canada 2 The rotation of the wheel is critical It must be free to rotate without striking or rubbing any stationary objects 3 Motor must be securely and adequately groun...

Page 2: ...atures should be evenly maintained between 30 to 110 F 1 to 43 C wide temperature swings may cause condensation and sweating of metal parts All accessories must be stored indoors in a clean dry atmosphere Remove any accumulations of dirt water ice or snow and wipe dry before moving to indoor storage To avoid sweating of metal parts allow cold parts to reach room temperature To dry parts and packag...

Page 3: ...oged Open Drip Proof motor Chart 2 Filter Option Dimensions BDF Size K B C D E F G H Filter Size Filter Quantity 80 493 4 1264 181 2 470 157 8 403 153 16 386 1211 16 322 93 4 248 87 8 225 1 25 16 x 20 406 x 508 2 90 547 8 1394 211 4 540 183 4 476 181 4 464 157 8 403 121 4 311 101 2 267 1 25 20 x 25 508 x 635 2 100 517 8 1318 223 4 578 203 4 527 193 4 502 177 8 454 133 4 349 117 8 302 1 25 20 x 20 ...

Page 4: ...rtain all connectors are tight and that all washers are in 5 If adjustments are made it is very important to check the pulleys for proper alignment Misaligned pulleys lead to excessive belt wear vibration noise and power loss See figure 5 6 For all BDF Fans Belt tension can be adjusted by loosening four fasteners marked R figure 6 on the drive frame The motor plate slides on the slotted adjusting ...

Page 5: ...emoving dust buildup on motor housing ensures proper motor cooling Greasing of motors is only intended when fittings are provided Many fractional horsepower motors are permanently lubricated and should not be lubricated after installation Motors supplied with grease fittings should be greased in accordance with manufacturers recommendations Where motor temperatures do not exceed 104 F 40 C the gre...

Page 6: ...s per day in clean relatively dry atmosphere 12 to 18 Infrequent operation or light duty in clean atmosphere Table 2 Grease Manufacturers Manufacturer Grease NLGI 2 U S Electric Motors Grease No 83343 Chevron U S A Inc Chevron SRI Grease 2 Mobil Oil Corporation Mobilith Mobil 532 Texaco Inc Premium BRB 2 Texaco Multifak 2 Amoco Oil Co Rykon Premium 2 Exxon Unirex N2 Shell B Shell Alvania 2 4 Once ...

Page 7: ... 8 in 3 8 in 6 12 Cadium plated lock washer 3 8 in 3 8 in 7 4 Cadium plated washer 1 3 8 in O D x 9 16 in I D x 3 32 in 1 3 8 in O D x 9 16 in I D x 3 32 in 7 12 Cadium plated washer 1 3 8 in O D x 9 16 in I D x 3 32 in 1 3 8 in O D x 9 16 in I D x 3 32 in 8 4 Neoprene or Spring Isolator Reference appropriate table below for replacement Isolator s 8 4 Neoprene or Spring Isolator Reference appropri...

Page 8: ...additional information describing the equipment fan performance available accessories and specification data Phone 715 359 6171 Fax 715 355 2399 E mail gfcinfo greenheck com Website www greenheck com Warranty AMCA Publication 410 96 Safety Practices for Users and Installers of Industrial and Commercial Fans provides additional safety information This publication can be obtained from AMCA Internati...

Reviews: