background image

1.  Smoke Damper requirementS anD 

application

 

Smoke dampers are required to close and prevent 
the passage of air and smoke through ducts or 
ventilation openings in smoke barriers. Smoke 
dampers are also applied in engineered smoke 
control systems to establish air pressure differentials 
and thereby prevent the spread of smoke. These 
dampers are designed to operate with blades running 
horizontally. Dampers can be vertically or horizontally 
installed at, in accordance with NFPA-90A, or 
adjacent to the point where the duct passes thru the 
smoke barrier.

2.  location of Damper in Ductwork

  Place the damper assembly in its proper position 

relative to the barrier. The plane of the closed 
damper blades must be within 24 in. (610mm) of the 
rated smoke barrier and before any duct inlets or 
outlets.

3.  attaching Damper to the Duct

  The damper is flange mounted to the duct, sleeve, 

or wall opening with

 

using #10 sheet metal screws, 

1/4 in. (6mm) diameter bolts and nuts, tack or spot 
welds, or 3/16 in. (5mm) diameter steel pop rivets. 

Attachments must be made at each flange spaced 
a maximum of 6 in. (152mm) on centers and a 
maximum of 2 in. (51mm) from corners.

4.  Sealing the inStallation

  The following duct sealants may be used to seal 

between the dampers flange and the mating surface: 
PA2084T duct sealant adhesive manufactured 
by Precision, DP1010 water base duct sealant 
manufactured by Design Polymetrics, Grey Pookie 
or Ductmate PROseal® in accordance with SMACNA 
recommendations.

5.  actuator connectionS

  Electrical and/or pneumatic connections to damper 

actuators should be made in accordance with wiring 
and piping diagrams developed in compliance with 
applicable codes, ordinances and regulations.

part number 472664 

inStallation inStruction Supplement

Refer to:
‘Installation Instructions for SMD, SESMD, SSSMD, SMDR, 
SESMDR, and SSSMDR series Models’ (Part #) 
for additional details. 

flange mounted installation

SmD-xxx, SeSmD-xxx, 

SSSmD-xxx Series

Smoke Dampers

“ul claSSifieD 

(see complete marking on product)”

“ul claSSifieD to canadian safety standards                   

(see complete marking on product)”

 

Standards UL 555 & 555S

Classifications Filed at UL under Listing #R13317 

Damper model

Maximum Single  

Section Size

in. (mm)

Maximum Overall 

Size for Multiple

Section Dampers

in. (mm)

SMD-301, 302

32 x 50

(813 x 1270)

128 x 100 or 256 x 50

(3251 x 2540) or 

(6502 x 1270)

SMD-301M, 302M

32 x 50

(813 x 1270)

128 x 100 or 256 x 50  

(3251 x 2540) or

(6502 x 1270)

SMD-401

48 x 60

(1219 x 7315)

192 x 72, 48 x 288,

or 384 x 36

(4877 x 1829, 

1219 x 7315 or 

9754 x 914) 

SMD-401M

48 x 36

(1219 x 914)

144 x 36

(3658 x 914)