APPLICATION

Model FSD-331 is a high performance combination fire smoke damper 

with extremely low leakage. High strength airfoil blades ensure the 

lowest resistance to airflow in HVAC systems with velocities to 2000 

fpm (10.2 m/s) and pressures to 4 in. wg (1 kPa). Model FSD-331 may 

be installed vertically (with blades running horizontal) and is rated for 

airflow and leakage in either direction.

RATINgs

UL 555 Fire Resistance Rating

 

 

Fire Rating:

 

3

 

hours 

 

Dynamic Closure Rating:

 Actual ratings are size dependent 

 

Max. Velocity: 

up to 2000 fpm (10.2 m/s) 

 

Max. Pressure: 

4 in. wg (1 kPa)

UL555S Leakage Rating

 

 

Leakage Class:

 

 

Operational Rating:

 

Actual ratings are size dependent 

 

Max. Velocity: 

up to 3000 fpm (15.2m/s) 

 

Max. Pressure: 

4 in. wg (1 kPa) 

 

Maximum Temperature:  350°F (177°C)- depending upon the 

 

 

actuator

sTANdARd CONsTRuCTION

 

Frame: 

 

5 in. x 1 in. (127mm x 25 mm) 

 

 

galvanized steel hat channel with 

 

 

reinforced corners. A low profile head 

 

 

and sill are used on sizes less than 

 

 

17 in. (432mm) 

 

Blades: 

 

Double skin airfoil shape of 

 

 

galvanized steel with full length 

 

 

structural reinforcement. 14 ga. 

 

 

(2 mm) equivalent thickness. 

 

Seals:

 

Extruded silicone rubber blade seals 

 

 

Flexible stainless steel jamb seals. 

 

Linkage:

 

Concealed in jamb. 

 

Closure Device:

 

RRL 165°F (74°C) 

 

Axles:

 

1

2

 in. (13mm) dia. plated steel. 

 

Bearings:

 

Bronze sleeve type.

sIze LImITATIONs:

 

minimum size:

 

8 in. W x 6 in. H 

 

 

(203 mm W x 152mm H) 

 

maximum size (Vertical Only):

  

 

Single Section: 

32 in. W x 36 in.H 

 

 

(813mm W x 914mm H) or  

 

 

30 in. W x 48 in. H 

 

 

(762mm x 1219mm) 

 

Multiple Section:

 

120 in. W x 96 in. H 

 

 

(3048mm W x 2438mm H)

OPTIONAL FeATuRes:

• RRL/OCI (Open closed indication switches)

•  165ºF (74°C), 212ºF (100°C), 250ºF (121°C), 350ºF (177°C) RRL's 

available

•  TOR (remote override closure allows damper to perform smoke 

management functions during a fire emergency.)

•  Electric or pneumatic actuators to accomplish smoke management 

and system functions.

• POC retaining angles

• Smoke detectors

• Momentary Switch

• Transitions (R, C, O)

• PRV (pneumatic relief valve)

• Security Bars

• Sealed transitions and sleeves

model Fsd-331

Combination Fire smoke dampers

 

Steel Airfoil Blades

UL 555S Leakage Class I

UL555 3 Hour Fire Resistance Rating

*W&H dimensions furnished approximately 

1

/

in. ( 6 mm) undersize.

(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.

H*

W*

LH

RH

Model FSD-331 meets the requirements for fire 

dampers, smoke dampers and combination fire 

smoke dampers established by:

National Fire Protection Association 

   

 NFPA Standards 80, 90A, 92A, 92B, 101 & 105

IBC  International Building Codes
ICBO  uniform Building Codes 
CsFm California state Fire marshal

  Fire Damper Listing (#3225-0981:103)
  Leakage (Smoke) Damper Listing (#3230-0981:104)

New York City 

(MEA listing #260-91-M)

“uL CLAssIFIed (see complete marking on 

product)”

“uL CLAssIFIed to Canadian safety standards 

(see complete marking on product)”

 

Standard 555 & 555S (Listing #R13317) 

Installation instructions available at www.greenheck.com

R

Greenheck Fan Corporation certifies that the 

model FSD-331 shown herein is licensed to 

bear the AMCA Seal. The ratings shown are 

based on tests and procedures performed 

in accordance with AMCA Publication 511 

and comply with the requirements of the 

AMCA Certified Ratings Programs. The 

AMCA Certified Ratings Seal applies to air 

performance ratings only.

Summary of Contents for Steel Airfoil Blades FSD-331

Page 1: ...tures RRL OCI Open closed indication switches 165ºF 74 C 212ºF 100 C 250ºF 121 C 350ºF 177 C RRL s available TOR remote override closure allows damper to perform smoke management functions during a fire emergency Electric or pneumatic actuators to accomplish smoke management and system functions POC retaining angles Smoke detectors Momentary Switch Transitions R C O PRV pneumatic relief valve Secu...

Page 2: ...strates a fully ducted damper This configuration has the lowest pressure drop of the three test configurations because entrance and exit losses are minimized by straight duct runs upstream and downstream of the damper Figure 5 2 Illustrates a ducted damper exhausting air into an open area This configuration has a lower pressure drop than Figure 5 5 because entrance losses are minimized by a straig...

Page 3: ...500 0 34 2500 0 34 2500 0 33 2500 0 51 3000 1 04 3000 0 49 3000 0 49 3000 0 48 3000 0 74 3500 1 41 3500 0 67 3500 0 67 3500 0 65 3500 1 00 4000 1 84 4000 0 87 4000 0 88 4000 0 85 4000 1 31 12in X 48 in 305mm x 1219mm 48 in x 12 in 1219mm x 305mm 24 in x 24 in 610mm x 610mm 36in x 36 in 914mm x 914mm 12 in x 12 in 305mm x 305mm R Greenheck Fan Corporation certifies that the model FSD 331 shown here...

Page 4: ...00 0 21 3000 0 24 3000 0 42 3500 0 73 3500 0 32 3500 0 29 3500 0 33 3500 0 57 4000 0 95 4000 0 42 4000 0 38 4000 0 43 4000 0 74 24 in x 24 in 610mm x 610mm 36in x 36 in 914mm x 914mm 12in X 48 in 305mm x 1219mm 48 in x 12 in 1219mm x 305mm 12 in x 12 in 305mm x 305mm 1 2 x 1 2 4 8 x 1 2 1 2 x 4 8 24x24 3 6 x 3 6 Sizes are in inches R Greenheck Fan Corporation certifies that the model FSD 331 shown...

Page 5: ...0 81 2500 0 75 2500 0 77 2500 0 89 3000 1 68 3000 1 17 3000 1 08 3000 1 11 3000 1 28 3500 2 29 3500 1 60 3500 1 48 3500 1 51 3500 1 75 4000 2 09 4000 2 14 4000 1 93 4000 1 97 4000 2 29 24 in x 24 in 610mm x 610mm 36in x 36 in 914mm x 914mm 12in X 48 in 305mm x 1219mm 48 in x 12 in 1219mm x 305mm 12 in x 12 in 305mm x 305mm R Greenheck Fan Corporation certifies that the model FSD 331 shown herein i...

Page 6: ...ire these worst case clearances If space availability above or below the damper sleeve is limited each damper size should be individually evaluated Application Data 53 8 5 Right hand drive is shown Left hand drive available upon request LH RH A Sleeve Length Varies 6 33 4 11 2 max B S T With the exception of dampers 10 in high 254mm or less NOTE Entire damper frame is not required to be installed ...

Page 7: ... designed to inflate and provide a tighter seal against leakage as pressure on either side of the damper increases Jamb seals shall be stainless steel compression type Blades shall be completely symmetrical relative to their axle pivot point presenting identical resistance to airflow in either direction or pressure on either side of the damper Damper must be rated for mounting vertically with blad...