background image

Page  1

INTRODUCTION

The Outside humidity transmitter uses a highly accurate and reliable Thermoset 

Polymer based capacitance humidity sensor and state-of-the-art digital 

linearization and temperature compensated circuitry in an weatherproof 

enclosure to monitor outside humidity levels. Sensors are mounted in a sun and 

wind shield for more accurate monitoring. An optional temperature sensor is 

also available.

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning 

the humidity transmitter. Failure to follow these instructions may result in 

product damage. Do not use in an explosive or hazardous environment, with 

combustible or flammable gases, as a safety or emergency stop device or in 

any other application where failure of the product could result in personal 

injury. 

Take electrostatic discharge precautions during installation and 

do not exceed the device ratings

.

MOUNTING

Select a suitable mounting spot on an exterior wall where the outside humidity transmitter is best protected from direct exposure to sunlight, 

wind, etc. preferably on a North facing wall.  Do not mount the sensor near opening 

windows, supply/exhaust air louvres or other known air disturbances. Avoid areas 

where the sensor is exposed to vibrations or rapid temperature changes.

The sensor is provided with either a connection hole for 1/2" Conduit or a cable gland 

fitting. When using conduit, run a length of conduit through exterior wall and seal. Use 

14-22 AWG shielded wiring for all connections and do not locate the device wires in 

the same conduit with wiring used to supply inductive loads such as motors. Make all 

connections in accordance with national and local codes.

The sensor installs directly on an exterior wall using the two integrated mounting holes 

provided on the enclosure. Select the best mounting technique based on the exterior 

wall material. The two mounting holes will facilitate a #10 size screw (not supplied). The 

sensor fitting must be pointing down. See Figure 1.

The enclosure has a hinged cover with a latch.  Open the cover by pulling slightly on 

the latch on the right side of the enclosure, at the same time pulling on the cover, as 

illustrated in Figure 2.

When using conduit, feed conduit through the provided hole in the back of the 

enclosure and secure with a lock nut as shown in Figure 3. It is recommended that 

weatherproof conduit be used. If using a cable gland connection, feed wiring though 

the cable gland on the top of enclosure and tighten as shown in Figure 4.

 

Make wiring connections as per the “Wiring” illustrations on Page 2.

Swing door closed until securely latched.  For added security, 2 screws are provided 

that may be installed in the integrated screw tabs.  See Figure 5.

1/2" Conduit 

Connection

Conduit Connection

Optional Cable Gland Fitting

Figure 2

Figure 3

Figure 4

Figure 5

Figure 1

IN-GE-HSOBXXX-03

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Outside Humidity Transmitter

HSOB Series - Installation Instructions

Reviews: