background image

Page  1

INTRODUCTION

This humidity transmitter uses a highly accurate and reliable Thermoset Polymer 
based capacitance humidity sensor and state-of-the-art digital linearization and 
temperature compensated cicuitry in an attractive, low profile enclosure  to 
monitor room humidity levels.  Additional options are available which include 
manual override & LCD display.

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning 
the humidity transmitter. Failure to follow these instructions may result in 
product damage. Do not use in an explosive or hazardous environment, with 
combustible or flammable gases, as a safety or emergency stop device or in 
any other application where failure of the product could result in personal 
injury. Take electrostatic discharge precautions during installation. 

Do not 

exceed the device ratings.

MOUNTING

The humidity sensor installs on a standard electrical box or can be mounted directly to the 
wall. The backplate is configured to be compatible with many different electrical boxes 
types. The humidity transmitter should be mounted five feet from the floor of the area to 
be controlled. Do not mount the sensor near doors, opening windows, supply air diffusers 
or other known air disturbances. Avoid areas where the sensor is exposed to vibrations or 
rapid temperature changes.

Begin by removing the cover. Grasp the bottom of the cover and pull outward from the 
backplate as shown in Figure 1. Set cover aside. Do not remove the PCB from the enclosure 
base.

Feed at least 6" of wire through the wall and out of the junction box. Feed connection 
wires through center hole on backplate and PCB, then secure backplate to electrical box or 
wall with suitable screws (not supplied) as shown in Figure 3. The mounting holes in allow 
for up/down & side to side movement to compensate for unlevel electrical box installation. 

Make wire connections as per the “Wiring illustrations” on Page 2 and re-install decorative 
cover by placing the top of the cover into the cover holders on the top of the backplate 
and snapping the bottom into place.

Two 1/16” Allen Key set screws are provided on the bottom of enclosure to add security and 
lock cover in place. To engage, insert Allen Key and turn counter-clockwise 2-3 rotations. 
As seen in Figure 4.

Figure 1

Figure 3

Figure 2

Figure 4

IN-GE-RH100BXXX-03

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Room Humidity Transmitter

RH100B Series - Installation Instructions