1
6E 6360E
6E
63
60
E
§
2 channel programmer
annual and weekly cycle
User instructions
Navigation &
value setting
Validation
Enter in PROGRAMME mode &
return to previous step
Selection of days of the week
1 = Monday, 2 = Tuesday
... 7 = Sunday
Canal B command
Canal A command
Keyboard locked by PIN code
menu
+
ok
At any time, pressing the button menu allows you
to return to the previous choice level.
Programming
To do the yearly programming of the clock, you
have the following 4 types of programme:
-
Basic weekly programme
This is a non-priority weekly programme.
-
Sub-programmes 1 to 10
These are weekly sub-programmes which are
activated for a defined date-to-date period. As
the sub-programme number increases, so does
the priority.
-
DATE/TIME
This is a programme step composed of a time
and a date which will run in addition to the usual
programme. If there is conflict between this
programme step and another programme step
(SP or weekly), this step has priority.
-
Holidays
This programme allows you to define a
permanent ON or OFF from date-to-date.
This programme has the highest priority.
Product Presentation
Connection diagram
A
B
1 3 5
2 4 6 8 10 12 14 16
11 13 15
7 9
L
N
EG293B
Menu
Press the button
menu
to access the programming/
setting mode.
All of the programming and adjustments are
based on the following principle :
- the 1st line and/or 2nd line of the display
indicate the requested setting,
- the buttons
+
/
-
allow navigation through the
menus and settings,
- the button
ok
allows validation.
Pressing the button menu allows you to access
the following settings :
PROGRAM
SETTINGS
FUNCTIONS
DATE-TIME
S/W TIME
LANGUAGE
FACTORY
SETTINGS
BACK AUTO
PROGRAM
CREATE
PROGRAM
READ
PROGRAM
MODIFY
PROGRAM
DELETE
PROGRAM
COPY
BACK AUTO
COUNTER
CYCLE
PIN CODE
INPUT
BACK AUTO
menu
Electrical characteristics
⦁
Supply voltage :
230 V
+
10/-15%
⦁
Frequency :
50/60 Hz
⦁
Power consumption :
< 2 VA
⦁
Output :
2 changeover contacts
⦁
Maximum load :
AC1 µ 10A 250 V
~
Incandescent lighting :
1500 W
Halogen lighting :
230 V 1500 W
Compensated fluorescent tubes // :
(max. 45 µF) 400 W
Non compensated fluorescent tubes,
compensated in series :
1000 W
Compact fluorescent lamps :
400 W
⦁
Minimum load :
AC1
100 mA 250 V
~
⦁
Galvanic insulation between power supply and
output :
< 4 kV
⦁
Rated impulse voltage :
4 kV
Technical specifications
Functional characteristics
⦁
Programming capacity :
300 steps
⦁
Minimum time between 2 steps :
1 minute
⦁
Running accuracy :
± 0,2 sec/ 24h
⦁
Operating reserve : lithium battery, total of 5
years autonomy (unlimited programme backup)
⦁
The product is set into standby state (display
switched-off) after 1 minute with power off.
It switches back into automatic mode as soon
as power is back on or when pressing any key.
⦁
Protection degree :
IP 20 / IK 04
⦁
Action type
:
1B
⦁
Degree of pollution :
2
⦁
Software class :
A
Environment
⦁
Operating temperature :
-10 °C to
+
50 °C
⦁
Storage temperature :
-20 °C to
+
70 °C
⦁
Temperature for the ball pressure Test :
75° to 125°C
Connection by quick-connect terminals
⦁
Flexible :
0,75 to 2,5 mm
2
⦁
Rigid :
0,75 to 2,5 mm
2
Standards
60730-1
60730-2-7
Presentation
⦁
Product delivered with current time and date set.
⦁
Automatic change of summer/winter time.
⦁
Programming key
-
For permanent overrides
-
For program copy or save
⦁
300 programme steps ; ON, OFF, pulses
or
.
⦁
Permanent overrides On or Off (
permanent
light on).
⦁
Temporary overrides On or Off (
flashing).
⦁
Overrides (temporary, permanent or time delayed)
remote activation possible.
⦁
Simulation of presence
.
⦁
Keyboard lock function
by PIN number.
⦁
Counter of operating time on every output.
⦁
Programmable with power off.
⦁
Display with backlight.
*
*
Input for external override
Pressing simultaneously the
menu
,
–
,
+
,
ok
keys
allows you to réinitialize the product.
The program is kept in memory.
Reinitializing
EG293B
When using for the first time, the following
settings must be done :
- select the language
- select the year, month, day
- select the hour and the minutes
- select the automatic change summer/winter.
Press the buttons
+
/
–
to set the display.
Press
OK
to validate.
When the settings are finished, the clock goes to
automatic mode.
First commissioning
§
Warranty
NOT APPLICABLE FOR AUSTRALIA
A warranty period of 24 months is offered on hager
products, from date of manufacture, relating to any material
of manufacturing defect. If any product is found to be
defective it must be returned via the installer and supplier
(wholesaler). The warranty is withdrawn if:
- after inspection by hager quality control dept the device is
found to have been installed in a manner which is contrary
to IEE wiring regulations and accepted practice within the
industry at the time of installation.
- The procedure for the return of goods has not been
followed. Explanation of defect must be included when
returning goods.
This device must be installed only by
a qualified electrician according to the
installation standards in force in the
country.
Usable in all Europe
å
and in Switzerland