Safety information
Do not touch or contact the input/output terminals because they may cause electric shock.
• Before you use, read safety precautions carefully, and use this product properly.
• Do not touch or contact the input/output terminals because they may cause electric shock.
• If you are concerned about serious accident due to the malfunction of products,
please install the external safety equipment
• To prevent defection or malfunction of this product, supply proper power voltage in
accordance with the rating.
• To prevent electric shock or devise malfunction of this product, do not supply the
power until the wiring is completed.
• Reassemble this product while the power is off. Otherwise, it may cause malfunction
or electric shock.
• If the user use the product with methods other than specified by the manufacturer,
there may be bodily injuries or property damages.
• Due to the danger of electric shock, use this product installed onto a panel while an
electric current is applied.
• Before using the product you have purchased, check to make sure that it is exactly
what you ordered.
• Do not use this product at any place with corrosive
(especially noxious gas or ammonia) or flammable gas.
• Do not use this product at any place with liquid, oil, medical substances, dust, salt or
iron contents.
• Do not use this product at any place with excessive induction trouble, static electricity
or magnetic noise.
• Do not use this product at any place with possible thermal accumulation due to direct
sunlight or heat radiation.
• When the product gets wet, the inspection is essential because there is danger of an
electric leakage or fire.
• Do not connect anything to the unused terminals.
• For DC types, connect wires at the correct position after checking polarity of terminal.
• The rated heat sink must be used otherwise, the product may be destroyed.
• When product is disposed, treat as a industrial waste.
• Since a heat sink corner is sharp, it would lead to a serious injury.
when electricity flows, desktop or heat sink temperature would be high so that it
could lead people to suffer burns.
•This model has epoxy molding for the purpose of safety, reliability and extends of the life.
•When it is out of order, please separate SSR from head sink and only change SSR.
• When applying an electric current, SSR is heated more and more. So, it has more durable
at low heat sink temperature and ambient temperature.
DANGER
WARNING
CAUTION
Suffix code
Model
Code
Information
HSR-3SL
Slim Type 3-Phase Solid State Relay
Input Operating Voltage D
4 - 32 V DC
Rated load current
15
15 A
25
25 A
40
40 A
Rated load voltage
2
90 - 264 V AC (Low voltage)
4
90 - 480 V AC (High voltage)
Operation method
(Switching Mode)
Z
Zero Cross Switching (Standard product)
R
Random Switching
Specification
Dimension
Model
Low
HSR-3SLD152Z
HSR-3SLD252Z
HSR-3SLD402Z
High
HSR-3SLD154Z
HSR-3SLD254Z
HSR-3SLD404Z
Load
Rated Load
Voltage
Low
90 - 264 V AC
High
90 - 480 V AC
Peak Voltage
(Non-repetition)
Low
600 V
High
800 V
1,200 V
Rated load current
15 A
25 A
40 A
Frequency
50/60 ㎐ (Dual usage)
Surge current
(8.3 ms No repetition)
Low
170 A
260 A
420 A
High
170 A
250 A
370 A
Leakage current
20 ㎃ max
Output ON voltage dropping
1.6 V (R.M.S) max
Input
Rated Voltage
5 - 24 V DC
Operating Voltage Range
4 - 32 V DC
Impedance
Less than 4 ㏀
Operation Voltage
More than 3 V DC
Reset Voltage
Less than 1.5 V DC
Input Current
Constant-current system : 10 ㎃ (±3)
Response Time
1/2 Cycle + 1 ms max. (“R”type below 1 ms)
Insulating Resistance
500 V DC, 100 ㏁ (Between the input / output and case)
Dielectric strength
3,000 V AC (For 1 min at 60 ㎐)
Vibration resistance
10 - 55 ㎐, Double amplitude : 1.5 ㎜, X,Y, and Z direction for 2 hours
Shock resistance
1,000 ㎨, X,Y,Z each axis 3 times
Storage Temperature
-30 ~ 90 ℃
Ambient Temperature
0 ~ 25 ℃ (But without frostiness)
Ambient Humidity
45 ~ 85 % R.H.
Weight
Approx. 1,000 g
Approx. 1,300 g
[Unit : mm]
※ Weight included the weight of box
▒ 15 A, 25 A
▒ 40 A
MC0601KE140227
28, Gilpa-ro 71beon-gil, Nam-gu, Incheon, Korea
TEL : (82-32)876-4697 FAX : (82-32)876-4696
http://www.hynux.com
HANYOUNGNUX CO.,LTD
HEAD OFFICE
JL.CEMPAKA BLOK F 16 NO.02 DELTA SILICON II INDUSTRIAL PARK
LIPPO CIKARANG CICAU, CIKARANG PUSAT, BEKASI INDONESIA 17550
TEL : 62-21-8911-8120~4 FAX : 62-21-8911-8126
PT. HANYOUNG ELECTRONIC INDONESIA
INDONESIA
FACTORY
Slim Type
HSR-3SL
3-Phase Solid State Relay
Thank you for purchasing HANYOUNG product.
Please check whether the product is the exactly same as you ordered.
Before using the product, please read this instruction manual carefully.
Please keep this manual where you can view at any time
INSTRUCTION MANUAL
DANGER indicates an imminently hazardous situation which, if
not avoided, will result in death or serious injury
WARNING indicates a potentially hazardous situation which, if
not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation which, if
not avoided, may result in minor or moderate injury
DANGER
WARNING
CAUTION
Before using the product, please read the safety information thoroughly and use it properly.
Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality
● HSR-3SL 외형 및 패널 가공치수 (단위:mm)
- 15A,25A
- 40A -
96.6
87.6
4.
5
20.5
10.0
(43.1)
44.5
79.0
4.5
6.5
13.8
146
74.0
120
74
96.6
87.6
4.
5
20.5
10.0
(43.1)
44.5
95.0
4.5
6.5
13.8
● HSR-3SL 외형 및 패널 가공치수 (단위:mm)
- 15A,25A
- 40A -
96.6
87.6
4.
5
20.5
10.0
(43.1)
44.5
79.0
4.5
6.5
13.8
146
74.0
120
74
96.6
87.6
4.
5
20.5
10.0
(43.1)
44.5
95.0
4.5
6.5
13.8
All manuals and user guides at all-guides.com
all-guides.com