5
6
ML0201KE120820
Model
Code
Description
MA4N -
Ӂ
Analog multi timer (48 × 48
㎜
)
Device
selection
A
2c (Time limit) ※ 11 pin type
B
2c (Time limit + Constantaneous) ※ 11 pin type
C
2c (Time limit), 2c (Time limit + Constantaneous)
※Processed by mode selection (8pin type)
Power supply voltag
24 - 240 V a.c / d.c (50 - 60
㎐
) Dual usage
Model
MA4N-A
MA4N-B
MA4N-C
Power Supply voltage
24 - 240 V a.c / d.c 50 - 60
㎐
Voltage regulation
±10 % from supply voltage
Power consumption
5.3 VA (240 V a.c), 2.5 W (240 V d.c)
Resetting time
0.1 sec max
Min
Signal
length
START
Input
20 ms min
-
INHIBIT
Input
RESET
Input
Input
condition
START
Input
Non voltage Input
Impedance in a short circui t : 2
㏀
max
Residual voltage in a short circuit : 0.7 V d.c max
Impedance in open : 100
㏀
min
-
INHIBIT
Input
RESET
Input
Output
Time limit 2c
Time limit 1c
Instautaneous 1c
Time limit 2c
Time limit 1c
Instautaneous 1c
N.O : 10 A 125 V a.c, 5 A 250 V a.c, 5 A 30 V d.c
N.C : 3 A 125 V a.c, 2 A 250 V a.c, 1 A 30 V d.c
Setting error
± 5 % ±0.05 sec max
Repeat error
± 0.3 % max
Temperature error
± 2 % max
Insulation resistance
100
㏁
min (Base on 500 V d.c)
Dielectric strength
2000 V a.c 50 / 60
㎐
for 1 min
Impulse voltage
±2000 V max
Vibration
Mechanical
durability
10 - 55
㎐
double amplitude 0.75
㎜
Malfunction
durability
10 - 55
㎐
double amplitude 0.5
㎜
Shock
Mechanical
durability
300
㎨
(Approx. 30 G)
Malfunction
durability
100
㎨
(Approx. 10 G)
Life
expectancy
Mechanical
Over 10 million operations (Open & Short frequency : 180 / min)
Electrical
Over 100,000 (250 V a.c 3 A load resistance)
Terminal type
Socket type 11 Pin
Socket type 8 Pin
Ambient
temperature
-10 ~ 55 ℃ (With no condensation)
Conservation
temperature
-20 ~ 65 ℃ (With no condensation)
Ambient humidity
35 ~ 85 %R.H.
Weight
About 100g (Including fixing bracket)
Analog multi timer
MA4N
Thank you for purchasing HANYOUNG product.
Please check whether the product is the exactly same as you ordered.
Before using the product, please read this instruction manual carefully.
Please keep this manual where you can view at any time
INSTRUCTION MANUAL
1381-3, Juan-Dong, Nam-Gu Incheon, Korea.
TEL:(82-32)876-4697
FAX:(82-32)876-4696
http://www.hynux.net
Jl. cempaka blok F16, No.02 Delta Silicon II
Cikarang Bekasi Indonesia
TEL : 62-21-8911-8120~4
FAX : 62-21-8911-8126
HANYOUNGNUX CO.,LTD
PT. HANYOUNG ELECTRONIC INDONESIA
HEAD OFFICE
INDONESIA
FACTORY
Safety information
Suffix code
Specification
DANGER indicates an imminently hazardous situation
which, if not avoided, will result in death or serious injury
WARNING indicates a potentially hazardous situation
which, if not avoided, could result in death or serious injury
CAUTION indicates a potentially hazardous situation which,
if not avoided, may result in minor or moderate injury
Before using the product, please read the safety information thoroughly and use it properly.
Alerts declared in the manual are classified to Danger, Warning and Caution by their criticality
DANGER
WARNING
CAUTION
• The contents of this manual may be changed without prior notification.
• Before using the product you purchased, make sure that it is exactly what you ordered.
• Make sure that there is no damage or abnormality of the product during delivery.
• Do not use this product at any place with corrosive
(especially noxious gas or ammonia) or flammable gas.
• Do not use this product at any place with direct vibration or impact.
• Do not use this product at any place with liquid, oil, medical substances,
dust, salt or iron contents.
• Do not polish this product with substances such as alcohol or benzene.
• Do not use this product at any place with a large inductive difficulty or
occurring static electricity or magnetic noise.
• Do not use this product at any place with possible thermal accumulation due
to direct sunlight or heat radiation.
• Install this product at place under 2,000 m in altitude.
• When the product gets wet, the inspection is essential because there is a
danger of electric leakage or fire.
• If there is excessive noise from the power supply, using insulating
transformer or noise filter is recommended. The noise filter must be attached
to a panel which is already connected to a ground and the wire between the
filter output and power supply terminal must be as short as possible.
• If puttig power cables closely together then It is effective against noise.
• Do not connect anything to the unused terminals.
• After checking the polarity of terminal, connect wires at the correct position.
• When this product is connected to a panel, use a circuit breaker or switch
approved with IEC60947-1 or IEC60947-3.
• Install the circuit breaker or switch at near place for convenient use.
• Write down on a label that if the circuit breaker or switch is operating then
the power will be disconnected since the circuit breaker or switch is installed.
•
For the continuous and safe use of this product, the periodical maintenance is recommended.
• Some parts of this product have limited life span, and others are changed by their
• The warranty period for this product including parts is one year if this product is properly used.
CAUTION
• If there is a possibility of an accident caused by errors or malfunctions of this
product, install external protection circuit to prevent the accident.
• This product does not contain an electric switch or fuse, so the user needs to
install a separate electric switch or fuse externally. (Fuse rating: 250V 0.5A)
• To prevent defection or malfunction of this product, supply proper power
voltage in accordance with the rating.
• To prevent electric shock or malfunction of product, do not supply the power
until the wiring is completed.
• Since this product is not designed with explosion-protective structure, do not
use it any place with flammable or explosive gas.
• Do not decompose, modify, revise or repair this product. This may be a
cause of malfunction, electric shock or fire.
• Reassemble this product while the power is OFF. Otherwise, it may be a
cause of malfunction or electric shock.
• If you use the product with methods other than specified by the
manufacturer, there may be bodily injuries or property damages.
• Due to the danger of electric shock, use this product installed onto a panel
while an electric current is applied.
WARNING
There is a danger of occurring electric shock in the input/output terminals so
please never let your body or conductive substance is touched.
DANGER
5
6
Time unit
sec
min
hrs
×10h
Max time
Setting
range
1.2
0.12 ~ 1.2
1.2 ~ 12
3
0.3 ~ 3
3 ~ 30
12
1.2 ~ 12
12 ~ 120
30
3 ~ 30
30 ~ 300
▒
MA4N-A / MA4N-B
▒
Selection of time unit
·MA4N-A : 2 relay work as Time limit.
· MA4N-B : The relay connected
①
,
③
,
④
work as Instantaneous and othr ealys
work as time limit.
※ Please refer to Timing charts for working
of relays
· Two relays in Mode A1 and D1 work as
Time limit.
· The relays in Mode B1, C1, E1, F1
connected
①
,
③
,
④
work as
Instantaneous.
And other realys work as time limit.
※ MA4N-C : According to timing charts,
relays works as Time limit or
Instantaneous.
※ Please refer to Timing charts for working
of relays.
[unit : mm]
Time range
Dimension and panel cutout
Connection diagram
Part name
▒
External connection
▒ Selection of time unit
Please select operation mode by turning of operation mode switch in
front of panel.
User can select 6 types of operation modes Operation mode is
displayed as like
A, B, C, D, E, F or A1, B1, C1, D1, E1, F1.
Please select time by turning of Time range switch
Use can select 16 types of time ranges and it is displayed as like sec,
min, hrs, 10h