▍Safety information
Please read the safety information carefully before the use, and use the product correctly.
The alerts declared in the manual are classified into
Danger
and
Warning
according to their importance.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor injury or properties damage
• Please make sure that the product specifications are the same
as you ordered.
• Please use the product in places where corrosive gases (especially
harmful gases, ammonia, etc.) and flammable gases are not generated.
• Please use the product in places without liquids, oils,
chemicals, steam, dust, salt, iron, etc. (pollution degree 1 or 2).
• Please avoid places where large inductive interference, static
electricity,magnetic noise are generated.
• Please avoid places with heat accumulation caused by direct
sunlight, radiant heat, etc.
• When water enters, short circuit or fire may occur, so please
inspect the product carefully.
• Do not connect anything to the unused terminals.
• For DC types, please wire correctly, after checking the polarity of the terminals.
• When disposing of the product, treat it as industrial waste.
•Since a heat sink corner is sharp, it would lead to a serious injury.
• When electricity flows, desktop or heat sink's corner temperature
would be high so that it could lead people to suffer burns.
•When it is out of order, please separate SSR from head sink and change only SSR.
•This model has epoxy molding for the purpose of safety,
reliability and extends of the life.
• When applying an electric current, SSR is heated more and more. So, it has
more durable at low heat sink temperature and ambient temperature.
• The input/output terminals are subject to electric shock risk.
Never let the input/output terminals come in contact with
your body or conductive substances.
• Please read the safety information carefully before the use,
and use the product correctly.
• If there is a possibility that a malfunction or abnormality of this
product may lead to a serious accident, install an appropriate
protection circuit on the outside and plan to prevent accidents.
• Please supply the rated power voltage, in order to prevent
product breakdowns or malfunctions.
• To prevent electric shocks and malfunctions, do not supply
power until the wiring is completed.
• Please disassemble the product after turning OFF the power.
• Any use of the product other than those specified by the
manufacturer may result in personal injury or property damage.
• Please use this product after installing it to a panel,
because there is a risk of electric shock.
DANGER
WARNING
CAUTION
Single-Phase Solid State Relay
SSR-2
Thank you for purchasing Hanyoung Nux products. Please read the instruction
manual carefully before using this product, and use the product correctly.
Also, please keep this instruction manual where you can view it any time.
MC0801KE180713
INSTRUCTION MANUAL
28, Gilpa-ro 71beon-gil, Michuhol-gu,
Incheon, Korea TEL : +82-32-876-4697
http://www.hynux.com
HANYOUNGNUX CO.,LTD
Jl. Jangari RT.003/002 Hegarmanah Sukaluyu
Cianjur Jawa Barat Indonesia 43284
TEL : +62-21-5060-7210
PT. HANYOUNG ELECTRONIC INDONESIA
Model
Code
Information
SSR-2
□ □ □ □ □ Single-Phase Solid State Relay
Input Voltage
D
5 - 24 V d.c.
A
100 - 240 V a.c.
Rated load current
10
10 A
20
20 A
30
30 A
40
40 A
Rated load voltage
2
90 - 264 V a.c. (Low voltage)
4
90 - 480 V a.c. (High voltage)
Operation method
(Switching Mode)
Z Zero Cross Switching (Standard product)
R Random Switching
Model
Low
SSR-2D102Z
SSR-2D202Z
SSR-2D302Z
SSR-2D402Z
High
SSR-2D104Z
SSR-2D204Z
SSR-2D304Z
SSR-2D404Z
L
O
A
D
Rated Load
Voltage
Low
90 - 264 V a.c.
High
90 - 480 V a.c.
Peak Voltage
(Non-repetition)
Low
600 V
High
800 V
1,200 V
Rated load current
10 A
20 A
30 A
40 A
Frequency
50/60 ㎐ (Dual usage)
Surge current
(8.3 ms No repetition)
Low
170 A
260 A
420 A
High
170 A
250 A
370 A
Leakage current
Less than 20 ㎃
Output ON voltage dropping
Less than 1.6 V (R.M.S)
I
N
P
U
T
Rated Voltage
5 - 24 V d.c.
Operating Voltage Range
4.6 - 32 V d.c.
Impedance
Less than 4 ㏀
Operation Voltage
More than4.6 V d.c.
Input Current
Constant-current system : 8 ㎃ (±3)
Response Time
1/2 Cycle + 1 ms max. (“R”type below 1 ms)
Insulating Resistance
500 V d.c., 100 ㏁ (Between the input / output and case)
Dielectric strength
2,500 V a.c. (For 1 min at 60 ㎐)
Vibration resistance
10 - 55 ㎐, Double amplitude : 1.5 ㎜, X,Y, and Z direction for 2 hours
Shock resistance
1,000 ㎨, X,Y,Z each axis 3 times
Storage Temperature
-30 ~ 90 ℃
Ambient Temperature
-5 ~ 40 ℃ (But without frostiness)
Ambient Humidity
45 ~ 85 % RH
Pollution level grade
2level pollution
Usage
Resistive load / Inductive load
Accepted standard
IEC 62314
Weight
Approx. 89g
Model
Low
SSR-2A102Z
SSR-2A202Z
SSR-2A302Z
SSR-2A402Z
High
SSR-2A104Z
SSR-2A204Z
SSR-2A304Z
SSR-2A404Z
L
O
A
D
Rated Load
Voltage
Low
90 - 264 V a.c.
High
90 - 480 V a.c.
Peak Voltage
(Non-repetition)
Low
600 V
High
800 V
1,200 V
Rated load current
10 A
20 A
30 A
40 A
Frequency
50/60 ㎐ (Dual usage)
Surge current
(8.3 ms No repetition)
Low
170 A
260 A
420 A
High
170 A
250 A
370 A
Leakage current
Less than 20 ㎃
Output ON voltage dropping
Less than 1.6 V (R.M.S)
I
N
P
U
T
Rated Voltage
100 - 240 V a.c.
Operating Voltage Range
70 - 264 V a.c.
Impedance
Less than 40 ㏀
Operation Voltage
More than 70 V a.c.
Input Current
220 V a.c. : 8 mA
Response Time
1/2 Cycle + 1 ms max. (“R”type below 1 ms)
Insulating Resistance
500 V d.c., 100 ㏁ (Between the input / output and case)
Dielectric strength
2,500 V a.c. (For 1 min at 60 ㎐)
Vibration resistance
10 - 55 ㎐, Double amplitude : 1.5 ㎜, X,Y, and Z direction for 2 hours
Shock resistance
1,000 ㎨, X,Y,Z each axis 3 times
Storage Temperature
-30 ~ 90 ℃
Ambient Temperature
-5 ~ 40 ℃ (But without frostiness)
Ambient Humidity
45 ~ 85 % RH
Pollution level grade
2level pollution
Usage
Resistive load / Inductive load
Accepted standard
IEC 62314
Weight
Approx. 89g
█ DC input
█ AC input
•Please make intervals more than the sizes in the
following picture.
•Please install wiring duct less than half the height of
the heat sink to prevent the flow of air.
•It is good to use Hanyoung Nux's SSR in lower than
ambient temperature 40 ℃ so, please use it lower
than standard temperature.
•When installing the SSR, be sure to installthe heat sink
in the vertical direction.
•Unavoidably, if installed horizontally, theperformance
of the product will drop below 50 %
※ This model does not have a fuse internally. So we suggest using fast-acting fuse separately on the outside as following picture.
█ SSR-2D
█ SSR-2A
L
45
114
9.8×R2.2
6.8×R2.2
Ø4.5
48.5
75
95 99
86.8
35.1
▍Suffix code
▍Specifications
▍Connection
▍Installation
▍Dimensions
▍Equivalent Circuit
[단위 : mm]
▍Input/Load/Surge current Characteristics
Input current Characteristics
SSR-2D
SSR-2A
Load current Characteristics
10 A ~ 20 A
30 A ~ 40 A
•SSR-2□10
•SSR-2□20
•SSR-2□40
•SSR-2□30
Surge current Characteristics
• Using standard heat sink is mandatory for this product.
• Even the standard heat sink is used, SSR damage may occur if the environment temperature
rises or if the ventilation does not work well. (Environment temperature : over 40 ℃)
•The normal SSR element is damaged at the maximum temperature of 125 ℃ . When the
temperature of heat sink is 85° C, the temperature of the element reaches around 125 ℃ .
Therefore, during operation, measure the temperature of heat sink.
•When you connect SSR onto the heat sink, heat-transmitting grease is needed for smooth
heat transmission.
• To prevent separation by vibration, tighten up with bolts.
• Do not use any insulating materials such as wood, plastic or rubber. The standard heat sink
must be greased on the bottom side as shown below and connected.
※ The heatproof silicon grease must be applied thoroughly on the heat sink as well as the
bottom of SSR. The case side of heat sink needs to be installed on up and down directions.
█ Model : HSP series
Model
Applicable Model
Capacity(A)
Length(L)
HSP-10
SSR-2□10□
10 A
48 mm
HSP-20
SSR-2□20□
20 A
80 mm
HSP-40
SSR-2□30□
30 A
109 mm
SSR-2□40□
40 A
▍HEAT SINK
▍Precautions during the use of Heat Sink
[Unit : mm]