background image

▍Safety information

Please read the safety information carefully before the use, and use the product correctly.

The alerts declared in the manual are classified into 

Danger 

and 

Warning 

according to their importance.

   

DANGER

Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury

   

WARNING

Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury

   

CAUTION

Indicates a potentially hazardous situation which, if not avoided, may result in minor injury or properties damage

• Please make sure that the product specifications are the same 

   as you ordered. 

• Please use the product in places where corrosive gases (especially 

   harmful gases, ammonia, etc.) and flammable gases are not  generated.

• Please use the product in places without liquids, oils, 

  chemicals, steam, dust, salt, iron, etc. (pollution degree 1 or 2).

• Please avoid places where large inductive interference, static 

   electricity,magnetic noise are generated.

• Please avoid places with heat accumulation caused by direct 

   sunlight, radiant heat, etc.

• When water enters, short circuit or fire may occur, so please 

   inspect the product carefully.

• Do not connect anything to the unused terminals.

•  For DC types, please wire correctly, after checking the polarity of the terminals.  

• When disposing of the product, treat it as industrial waste.

•Since a heat sink corner is sharp, it would lead to a serious injury.

• When electricity flows, desktop or heat sink's corner temperature 

would be high so that it could lead people to suffer burns.

•When it is out of order, please separate SSR from head sink and  change only SSR.

•This model has epoxy molding for the purpose of safety, 

   reliability and extends of the life.

• When applying an electric current, SSR is heated more and more. So, it has 

more durable at low heat sink temperature and ambient temperature. 

• The input/output terminals are subject to electric shock risk. 

   Never let the input/output  terminals come in contact with 

   your body  or conductive substances.

• Please read the safety information carefully before the use, 

   and use the product correctly.

•  If there is a possibility that a malfunction or abnormality  of this 

   product may lead to a serious accident, install an appropriate  

   protection circuit on the outside and plan to  prevent accidents. 

• Please supply the rated power voltage, in order to prevent 

   product breakdowns or malfunctions. 

• To prevent electric shocks and malfunctions, do not supply 

   power until the wiring is completed.

• Please disassemble the product after turning OFF the power. 

• Any use of the product other than those specified by the 

   manufacturer may result in personal injury or property damage.

• Please use this product after installing it to a panel, 

   because there is a risk of electric shock. 

DANGER

WARNING

CAUTION

Single-Phase Solid State Relay

SSR-2

Thank you for purchasing Hanyoung Nux products. Please read the instruction 

manual carefully before using this product, and use the product correctly. 

Also, please keep this instruction manual where you can view it any time.  

MC0801KE180713

INSTRUCTION MANUAL

28, Gilpa-ro 71beon-gil,  Michuhol-gu, 

Incheon, Korea TEL : +82-32-876-4697 

http://www.hynux.com

HANYOUNGNUX CO.,LTD

Jl. Jangari RT.003/002 Hegarmanah Sukaluyu 

Cianjur Jawa Barat Indonesia 43284

TEL : +62-21-5060-7210

PT. HANYOUNG ELECTRONIC INDONESIA

Model

Code

Information

SSR-2

□ □ □ □ □ Single-Phase Solid State Relay

Input Voltage

D

5 - 24 V d.c.

A

100 - 240 V a.c.

Rated load current

10

10 A

20

20 A

30

30 A

40

40 A

Rated load voltage

2

90 - 264 V a.c. (Low voltage)

4

90 - 480 V a.c. (High voltage)

Operation method

(Switching Mode)

Z Zero Cross Switching (Standard product)

R Random Switching

Model

Low

SSR-2D102Z

SSR-2D202Z

SSR-2D302Z

SSR-2D402Z

High

SSR-2D104Z

SSR-2D204Z

SSR-2D304Z

SSR-2D404Z

L

O

A

D

Rated Load

Voltage

Low

90 - 264 V a.c.

High

90 - 480 V a.c.

Peak Voltage

(Non-repetition)

Low

600 V

High

800 V

1,200 V

Rated load current

10 A 

20 A

30 A

40 A

Frequency

50/60 ㎐ (Dual usage)

Surge current

(8.3 ms No repetition)

Low

170 A

260 A

420 A

High

170 A

250 A

370 A

Leakage current

Less than 20 ㎃

Output ON voltage dropping

Less than 1.6 V (R.M.S)

I

N

P

U

T

Rated Voltage

5 - 24 V d.c.

Operating Voltage Range

4.6 - 32 V d.c.

Impedance

Less than 4 ㏀

Operation Voltage

More than4.6 V d.c.

Input Current

Constant-current system : 8 ㎃ (±3)

Response Time

1/2 Cycle + 1 ms max. (“R”type below 1 ms)

Insulating Resistance

500 V d.c., 100 ㏁ (Between the input / output and case)

Dielectric strength

2,500 V a.c. (For 1 min at 60 ㎐)

Vibration resistance

10 - 55 ㎐, Double amplitude : 1.5 ㎜, X,Y, and Z direction for 2 hours

Shock resistance

1,000 ㎨, X,Y,Z each axis 3 times

Storage Temperature

-30 ~ 90 ℃

Ambient Temperature

-5 ~ 40 ℃ (But without frostiness)

Ambient Humidity

45 ~ 85 % RH

Pollution level grade

2level pollution

Usage

Resistive load / Inductive load

Accepted standard

IEC 62314

Weight

Approx. 89g

Model

Low

SSR-2A102Z

SSR-2A202Z

SSR-2A302Z

SSR-2A402Z

High

SSR-2A104Z

SSR-2A204Z

SSR-2A304Z

SSR-2A404Z

L

O

A

D

Rated Load

Voltage

Low

90 - 264 V a.c.

High

90 - 480 V a.c.

Peak Voltage

(Non-repetition)

Low

600 V

High

800 V

1,200 V

Rated load current

10 A 

20 A

30 A

40 A

Frequency

50/60 ㎐ (Dual usage)

Surge current

(8.3 ms No repetition)

Low

170 A

260 A

420 A

High

170 A

250 A

370 A

Leakage current

Less than 20 ㎃

Output ON voltage dropping

Less than 1.6 V (R.M.S)

I

N

P

U

T

Rated Voltage

100 - 240 V a.c.

Operating Voltage Range

70 - 264 V a.c.

Impedance

Less than 40 ㏀

Operation Voltage

More than 70 V a.c.

Input Current

220 V a.c. : 8 mA

Response Time

1/2 Cycle + 1 ms max. (“R”type below 1 ms)

Insulating Resistance

500 V d.c., 100 ㏁ (Between the input / output and case)

Dielectric strength

2,500 V a.c. (For 1 min at 60 ㎐)

Vibration resistance

10 - 55 ㎐, Double amplitude : 1.5 ㎜, X,Y, and Z direction for 2 hours

Shock resistance

1,000 ㎨, X,Y,Z each axis 3 times

Storage Temperature

-30 ~ 90 ℃

Ambient Temperature

-5 ~ 40 ℃ (But without frostiness)

Ambient Humidity

45 ~ 85 % RH

Pollution level grade

2level pollution

Usage

Resistive load / Inductive load

Accepted standard

IEC 62314

Weight

Approx. 89g

█ DC input

█ AC input

•Please make intervals more than the sizes in the 

  following picture. 

•Please install wiring duct less than half the height of 

  the heat sink to prevent the flow of air. 

•It is good to use Hanyoung Nux's SSR in lower than 

  ambient temperature 40 ℃ so,  please use it lower 

  than standard temperature.

•When installing the SSR, be sure to installthe heat sink 

  in the vertical direction.

•Unavoidably, if installed horizontally, theperformance 

  of the product will drop below 50 %

※ This model does not have a fuse internally.  So we suggest using fast-acting fuse separately on the outside as following picture.

█ SSR-2D

█ SSR-2A

L

45

114

9.8×R2.2

6.8×R2.2

Ø4.5

48.5

75

95 99

86.8

35.1

▍Suffix code

▍Specifications

▍Connection

▍Installation 

▍Dimensions

▍Equivalent Circuit

[단위 : mm]

▍Input/Load/Surge current Characteristics

Input current Characteristics

SSR-2D

SSR-2A

Load current Characteristics

10 A ~ 20 A

30 A ~ 40 A

•SSR-2□10

•SSR-2□20

•SSR-2□40
•SSR-2□30

Surge current Characteristics

• Using standard heat sink is mandatory for this product.

• Even the standard heat sink is used, SSR damage may occur if the environment temperature  

   rises or if the ventilation does not work well. (Environment temperature : over 40 ℃)

•The normal SSR element is damaged at the maximum temperature of 125 ℃ . When the  

   temperature of heat sink is 85° C, the temperature of the element reaches around 125 ℃ . 

   Therefore, during operation, measure the temperature of heat sink.

 •When you connect SSR onto the heat sink, heat-transmitting grease is needed for smooth  

   heat transmission.

• To prevent separation by vibration, tighten up with bolts.

• Do not use any insulating materials such as wood, plastic or rubber. The standard heat sink  

   must be greased on the bottom side as shown below and connected.

※ The heatproof silicon grease must be applied thoroughly on the heat sink as well as the 

    bottom of SSR. The case side of heat sink needs to be installed on up and down directions.

█ Model : HSP series

Model

Applicable Model

Capacity(A)

Length(L)

HSP-10

SSR-2□10□

10 A

48 mm

HSP-20

SSR-2□20□

20 A

80 mm

HSP-40

SSR-2□30□

30 A

109 mm

SSR-2□40□

40 A

▍HEAT SINK

▍Precautions during the use of Heat Sink

[Unit : mm]

Reviews: