QUICK START GUIDE
MSD-1001-L
10.1" Modero S Series Wall Mount Touch Panel
Overview
The MSD-1001-L 10.1" (Landscape) Wall Mount Touch Panel (FG2265-01) features brilliant
24-bit color depth, PoE connectivity, and streaming video (FIG. 1).
Product Specifications
MSD-1001-L Installation
The MSD-1001-L can be installed via several mounting options:
• Use the included clear plastic Backbox to attach the panel to most standard wall
materials.
• Other optional AMX mounting solutions include the MSA-MMK-10 Multi Mount Kit, the
MSA-AMK-10 Any Mount Kit, and the CB-MXSA-10 Rough-In Box. Refer to the Quick
Start Guide included with each mounting kit for instructions.
Plastic Backbox
The MSD-1001-L comes with a clear plastic Backbox. This Backbox can be used to mount the
touch panel into most standard wall materials. The Backbox can also used to mount the panel
into other mounting options.
STEP 1: Install the Plastic Backbox
Use the included Installation Template to determine the placement of the Backbox in the
mounting surface. The outside edges of the template are the same dimensions as the touch
panel, which allows you to troubleshoot possible conflicts with wall edges, doors, and other
potential obstacles.
1.
After ensuring proper placement, cut an opening in the mounting surface for the
Backbox, using the included Installation Template as a guide.
Note: Consider making the actual cutout opening slightly smaller than the provided
dimensions. This provides a margin of error if the opening needs to be expanded. Too little
wall material removed is always better than too much.
2.
Thread the incoming cables (Ethernet and Micro-USB) from their terminal locations
through the surface opening, leaving enough slack in the wiring to accommodate any re-
positioning of the panel.
3.
Remove the Backbox knockouts and thread incoming cables through the knockout
holes.
4.
Gently push the Backbox into the mounting surface.
• This Backbox uses four Locking Tabs to secure the Backbox to the wall. For typical
mounting surfaces, such as drywall, the locking tabs are the primary method for
securing the Backbox to the wall.
• To ensure a stable installation, the thickness of the wall material must be a minimum of
.50 inches (1.27cm) and a maximum of .875 inches (2.22cm). The mounting surface
should also be smooth and flat. For thin walls or solid surfaces, use mounting screws
(not included) - see FIG. 2.
5.
Extend the Locking Tabs by tightening the Locking Tab screws until snug (FIG. 3):
CAUTION: The maximum recommended torque to screw in the locking tabs on the plastic
Backbox is 5 IN-LB [56 N-CM]. Excessive torque on the tab screws can strip out the
locking tabs or damage the Backbox.
• Extend the Locking Tabs only AFTER the Backbox is inserted into the wall.
• When installing the Backbox, make sure that it is positioned correctly.
• The Backbox is clear to allow visual confirmation that the tabs have been extended and
are gripping the wall, as well as in assisting with removal if necessary.
STEP 2: Insert Connectors on the Touch Panel
1.
Before installing the touch panel into the Backbox, connect the Ethernet and USB cables
to the rear of the panel (FIG. 4):
2.
Remove power at the terminal end before continuing with the installation.
Note: Do not disconnect the connectors from the touch panel. The panel must be installed
with the attached connectors before being inserted into the mounting surface.
STEP 3: Secure the Touch Panel To the Backbox
The Backbox uses notches and tabs on the front edges (top and bottom) to secure the panel
into place. Follow the steps below to install the panel into the Backbox, starting the upper edge
of the touch panel:
UPPER TABS FIRST
1.
Center the top edge of the touch panel against the upper outside edge of the Backbox
and latch the top of the panel onto the Backbox top-hooks (FIG. 5):
2.
Gently press the top edge of the touch panel into place to engage the panel’s notches
and the top-hooks on the Backbox.
FIG. 1
MSD-1001-L
MSD-1001-L SPECIFICATIONS
Dimensions (HWD) 6 13/16" x 10 1/16" x 2" (174mm x 255mm x 51mm)
Weight
• 1.95 lbs (.885 Kg), with Backbox,
• 1.5 lbs (.680 Kg), without Backbox
Power
Consumption
• Full-On: 14W
• Typical: 7.5W
• Standby: 4.7W
• Shutdown: 0.8W
• Start-Up Inrush Current: Not
applicable - PoE standard
External Power
Supply Required
Optimal performance requires use of one of the following AMX PoE power
supplies (not included):
• PS-POE-AF-TC, PoE Injector, 802.3AF Compliant (FG423-83)
• NXA-ENET8-2POE, Gigabit PoE Ethernet Switch (FG2178-63)
Certifications
• FCC Part 15 Class B
• CE EN 55022, 55024, 60950-1
• IEC 60950-1
• C-Tick CISPR 22 Class B
• IC CISPR 22 Class B
• UL 60950-1
• VCCI CISPR 22 Class B
• RoHS
• WEEE
Environmental
• Temperature (Operating): 32°F to 104°F (0°C to 40°C)
• Temperature (Storage): 4°F to 140°F (-20°C to 60°C)
• Humidity (Operating): 20% to 85% RH
• Humidity (Storage): 5% to 85% RH
• Power ("Heat") Dissipation: On: 27.3 BTU/hr, Standby: 10.9 BTU/hr
Included
Accessories
• Installation Template 10.1" S Modero S (68-2265-03)
• Backbox, Wall Mount, 10.1" (60-2265-19)
FIG. 2
10.1" MODERO S BACKBOX (FRONT VIEW)
Sleep Button
Microphone
Left
LED
Right
LED
Backbox
(side view)
Locking Tab (X4)
Locking Tab screw (x4)
Mounting holes (X4) for installing the Backbox into a Rough-In Box (screws not included)
Mounting holes (X4)
for use with mounting
screws (not included)
Use these mounting holes
to install the Backbox into
thin walls (less than 0.5”
Locking Tab (X4)
Locking Tab screw (x4)
thick) or solid surfaces
FIG. 3
BACKBOX - LOCKING TAB AND LOCKING TAB SCREW (X4)
FIG. 4
REAR OF THE MSD-1001-L
FIG. 5
ENGAGING THE TOP EDGE OF THE PANEL WITH THE TOP HOOKS ON THE BACKBOX
Locking Tab screw (x4) - tighten to extend
each of the four Locking Tabs
(max torque = 5 IN-LB)
Locking Tab (x4)
10.1” Wall Mount Backbox
(detail - lower left corner)
Micro-USB Port
Ethernet Connector
Use the top-hooks on the top edge of the
Plastic Backbox
MSD-1001-L Touch Panel
Backbox to latch the top of the touch
panel into place