INSTALLATION INSTRUCTIONS

The Heat-Fab Saf-T Vent

TM

 is a masonry chimney lining and relining system intended

for use with residential appliances burning liquefied petroleum (LP), natural gas,
home heating oil, and solid (wood or coal) fuels.  Saf-T Vent is a high-quality,
extremely durable lining system constructed of a special alloy of stainless steel high
in both chromium and molybdenum.  This alloy, plus Saf-T Vent's smooth-wall
design, give it a unique combination of corrosion resistance, high temperature
tolerance and desirable flow characteristics not found in any other chimney lining
system.

As with any venting system, its installation must be properly planned and executed in
order to ensure satisfactory results.  Incorporation or substitution of parts or materials
not manufactured or supplied by Heat-Fab, or failure to follow these instructions, may
not provide a UL Listed system, and may result in appliance malfunction, fire or
endanger the health and safety of people.

Heat-Fab recommends that the installation be performed by an experienced
professional who works with venting systems for  residential appliances on a regular
basis.  These instructions are intended as a guide to assist a professional  installer.  The
installation must conform to the requirements of the appliance manufacturers'
instructions, applicable

 

National Fire Protection Association (NFPA) 

standards,

and local codes.  Check your local codes and contact local building or fire officials to
obtain any required permits.

IMPORTANT:

  THE SAF-T VENT SYSTEM MAY BE INSTALLED IN

SEVERAL DIFFERENT WAYS, USING DIFFERENT PARTS, ACCORDING TO
THE TYPE OF APPLIANCE(S) TO BE CONNECTED.  TO ENSURE PROPER
INSTALLATION, FOLLOW THESE MAIN INSTRUCTIONS 

AND

 THE

SUPPLEMENTAL INSTRUCTIONS INDICATED BELOW.

For Solid Fuel or Oil Appliances: 

 The liner

 

must

 be insulated with 

Saf-T Wrap

Insulation

.  

Follow these 

Main Instructions

 and the 

Supplemental General

Residential Instructions

 (PI-WRAP) packed with the Saf-T Wrap Insulation.

Category I gas appliances may also be installed per these instructions if desired.

Page 12

Single-wall metal vent
connector may not pass
through an interior wall or
partition.  It may pass
through a combustible
exterior wall if surrounded
at the point of passage by a
metal ventilated thimble at
least 4 inches larger in
diameter than the
connector, or by a wall
pass-through device Listed
for this purpose.  The
thimble or wall pass-
through must not be located
directly behind the heating
appliance.

M A I N T E N A N C E
INSTRUCTIONS

Cover Plate

Figure 7

Heat-Fab Inc.  Saf-T Vent

T M

Stainless Steel Chimney Liner

For Venting Residential Type

Gas, Oil and Solid Fuel Appliances

Sizes:  3", 4", 5", 6", 7", 8" Diameters

Support
Clamp

Combina-
tion Tee

Saf-T Vent
Sections

Masonry
Rubble

Support
Legs

Vent Con-
nector slant
1/4 inch per
foot

Normal operation of a gas appliance does not result in deposits of combustible soot
or creosote in the venting system.  However, a poorly adjusted or malfunctioning
appliance can deposit soot, and leaves or other debris can enter the flue.  Just as with
all chimneys and vents the Saf-T Vent should be inspected 

annually

 for the presence

of deposits or debris and cleaned if necessary.  This should be done by a Certified
Chimney Sweep

®

 or other qualified person.

To inspect the vent, pry up the locking tabs holding the rain cap to the top of the liner
and remove the cap.  Replace the cap by inserting the locking tabs back under the ring
and bending them back into position.  The system can also be inspected and cleaned
by removing the connector pipe from the liner tee or elbow.

PI-VINS   R0900

Turners Falls, Massachusetts 01376

(800) 772-0739

Summary of Contents for Saf-T Vent

Page 1: ...MENTALINSTRUCTIONSINDICATEDBELOW For Solid Fuel or Oil Appliances The liner must be insulated with Saf T Wrap Insulation Follow these Main Instructions and the Supplemental General Residential Instructions PI WRAP packed with the Saf T Wrap Insulation Category I gas appliances may also be installed per these instructions if desired Page 12 Single wall metal vent connector may not pass through an i...

Page 2: ...late and attached label are a mandatory part of the installation If the vent connector is to be sections of Saf T Vent conduit or other single wall metal connector pipe attach the male end of the first section to the connector adapter and continue with straight sections and elbows back to the appliance When used as a vent connector the flue gas conduit is installed with the male ends up pointing t...

Page 3: ... construct a barrier to prevent loose insulation from falling against the chimney Any resulting gaps between the chimney and framing at floor or ceiling levels must be closed with a firestop If the chimney is currently lined with a clay liner dislodge any loose sections shards or flakes and remove them Make sure that the flue space is at least 1 inch larger at its smallest point than the Saf T Ven...

Page 4: ...ion must conform to the requirements of the appliance manufacturer s instructions TheNationalFuelGasCode NFPA54 and local codes Check your local codes and contact local building and or fire officials to obtain any required permits By following these instructions Saf T Vent may be used to vent Category I gas burning furnaces boilers hot water heaters space heaters and decorative appliances with a m...

Page 5: ...attach it to the liner and lower it down the chimney The chimney flue space must however be large enough to accommodate the horizontal take off from the elbow which extends approximately 5 inches If the flue space is not large enough the elbow will have to be attached to the bottom of the vertical conduit after it is lowered down the chimney Attach the support clamp to the tee or elbow just below ...

Page 6: ...t a rectangular notch out of each corner and fold each side of the plate down 90 degrees so that the top surface is slightly larger than the tile Run a bead of silicone caulk on top of the tile and press the plate down into it If there is no projecting tile run a bead of caulk around the chimney top and press the cover plate flat on top of the chimney Slip the storm collar with the rounded surface...