background image

Ventilation-Duct

Smoke Switch System
LRS 01 Basic

Installation Instructions 

Summary of Contents for LRS 01

Page 1: ...Ventilation Duct Smoke Switch System LRS 01 Basic Installation Instructions ...

Page 2: ...Installation Instructions LRS 01 2 HEKATRON Vertriebs GmbH Brühlmatten 9 D 79295 Sulzburg 7002428 100206 VDA Ausgabe 10 02 2006 ...

Page 3: ...al data 6 3 General information 7 3 1 Operation of the LRS 01 7 3 2 Transport storage and unpacking 7 3 3 Scope of supply 7 4 Rules and regulations 8 5 Installation instructions 9 5 1 Mounting the LKS 02 9 5 2 Electrical connection of the ORS 210 12 6 Commissioning 14 6 1 Functional testing 14 6 2 Display of operating status of the ORS 210 14 7 Maintenance instructions 15 8 Ordering data 16 ...

Page 4: ...uction Figure 01 The LRS 01 consists of a ventilation duct socket LKS 02 and an ORS 210 optical Smoke Switch with alarm latching It is used for monitoring smoke in ventilation ducts The LKS 02 provides a mounting for Smoke Switch ORS 210 and is fitted on the outside of a ventilation duct The LRS 01 is intended for use inside buildings ...

Page 5: ...e assumed Disruptive factors which could affect reliable operation of the LRS 01 must be eliminated A2 A2 B B A1 A1 min 3 x a A1 Ideale Betriebsumgebung A2 Erhöhte Staubbelastung B Bereich für Rauchfrüherkennung ungeeignet a Kanalmaß a a Luftstromrichtung Figure 02 Figure 02 provides recommendations for project planning To ensure reliable smoke detection in large ducts several LRS 01 Smoke Switche...

Page 6: ...e range of the socket LKS 02 and Smoke Switch ORS 210 combi nation is determined by the technical data of the Smoke Switch Temperature range 20 C to 75 C Permissible rel humidity up to 95 RH dewing and steam condensation can cause false alarms Smoke Switch ORS 210 Operating principle light scattering Reaction thresholds to construction and testing rules for smoke triggered installations 12 76 Oper...

Page 7: ...recy cled Please note the properties of the package The carton in which the LRS 01 is packed complies with minimal package requirements and can support up to 10 times its own weight when stacked The package is only to a limited extent suitable for transport by post or rail For transport in tropical zones transport by sea etc special packages are available For further information please contact the...

Page 8: ...epublic Rules and regulations of the country in which the equipment is installed must be observed Extract Buildings and their equipment must be constructed so that measures are incorporated to prevent outbreaks of fire and restrict the spread of fire and smoke and so that in the event of a fire the rescue of people and animals and effective fire extinguishing operations are possible As a matter of...

Page 9: ...s in the tube must be inside the ventilation duct see Figure 04 Figure 04 The tube must not be bent and it must be cut cleanly at right angles When choosing a place to mount the LKS 02 take care that there is enough space to change the inlet tube If the inlet tube has not been shortened a space of at least 470 mm is required outside the duct The LKS 02 must be mounted on the duct using suitable fa...

Page 10: ...the socket LKS 02 is installed corresponds to the direction of airflow in the duct To help with this the LKS 02 has arrows on its base showing the direction of flow see Figure 05 Figure 05 Warning When mounting the LKS 02 socket it is important to ensure that the airflow direction is correct and that the socket is properly sealed 206 150 Flow direction Flow direction ...

Page 11: ...transparent cover that parts do not fall on the floor cover suction tube etc Handling The connection lead for the Smoke Switch ORS 210 must be passed through the plug supplied into the housing and connected The Smoke Switch ORS 210 is screwed into the socket LKS 02 Then the inlet tube with flow adapter is fitted After a positive functional check with test gas the cover of the LKS 02 can be fitted ...

Page 12: ...erly closed For cable entry 4 x M16 plugs are fitted When properly used they comply with the requirements of IP 54 within their 6 10 mm sealing range The sealing plugs can be replaced supplemented by 16 x 1 5 cable glands with M16 x 1 5 locknuts Terminal assignment in socket of LKS 02 Terminal 1 24 V DC Terminal 2 0 V DC Terminal 3 Option communication RS BUS Terminal 4 and 5 Potential free NC Ter...

Page 13: ... all normal commercially available telecommunications cable with or without screening can be used The conductor cross sections must be chosen to suit the current required by connected equipment and the installed lengths Conductor diameter min 0 6 mm to max 1 4 mm Cable diameter max 9 mm Recommended cable type IY ST Y 4 x 2 x 0 6 mm Only conductors with the same diameter may be connected at a termi...

Page 14: ... to which the optical Smoke Switch should react can reach it For func tional testing of the Smoke Switch ORS 210 test aerosol 918 5 must be used Test aerosol 918 5 is free of halogenated hydrocarbons CFCs etc If a Smoke Switch does not react when so tested then it must be replaced The inlet tube must be free of any obstructions Warning The warnings and safety instructions on the aerosol can must b...

Page 15: ... be needed after a shorter period By observing basic maintenance measures according to DIN 31051 in conjunction with DIN EN 13306 the LRS 01 system should be kept permanently ready for operation it should be serviced annually as specified by the manufacturer Test aerosol 918 5 from HEKATRON is to be used for functional testing of Smoke Switch ORS 210 The interaction of all items of equipment and t...

Page 16: ... 3610370 Locknut M16 x 1 5 3610371 Replacement socket 143 A 5000350 Mains unit NG 519 5400080 Mains unit NAG 03 5400081 Signal display and operating unit SAB 04 4400043 NG 519 with SAB 04 5400083 NAG 03 with SAB 04 5400084 Push button DKT 02 grey 6200118 Push button DKT 02 yellow 6200107 Test aerosol 918 5 6900331 HEKATRON Vertriebs GmbH PO Box 1040 D 79296 Sulzburg Tel 49 76 34 5 00 2 64 FAX 49 7...

Page 17: ...Installation Instructions LRS 01 17 7002428 100206 VDA Ausgabe 10 02 2006 HEKATRON Vertriebs GmbH Brühlmatten 9 D 79295 Sulzburg ...

Page 18: ...Installation Instructions LRS 01 18 HEKATRON Vertriebs GmbH Brühlmatten 9 D 79295 Sulzburg 7002428 100206 VDA Ausgabe 10 02 2006 ...

Page 19: ...Installation Instructions LRS 01 19 7002428 100206 VDA Ausgabe 10 02 2006 HEKATRON Vertriebs GmbH Brühlmatten 9 D 79295 Sulzburg ...

Page 20: ...HEKATRON Vertriebs GmbH Brühlmatten 9 D 79295 Sulzburg Tel 0 76 34 5 00 264 Telefax 0 76 34 5 00 323 info hekatron de www hekatron de A member of the Swiss Securitas Group ...