background image

.TYPE 

ONLINE 

UNINTTERRUPTIBLE 

POWER SUPPLY 

.POWER RANGE 

-

 

4,000VA 

-

 

6,000VA 

English 

 

 

 

OPERATIONAL MANUAL 

Summary of Contents for 4KVA

Page 1: ... TYPE ONLINE UNINTTERRUPTIBLE POWER SUPPLY POWER RANGE 4 000VA 6 000VA English OPERATIONAL MANUAL ...

Page 2: ...ode 8 3 10 Inverter mode 9 3 11 Warning and fault indicator 9 3 12 Battery capacity level 10 3 13 Load percentage indicator 10 4 INSTALLATION 16 4 1 Inspecting the Equipment 16 4 2 Placement 16 4 3 Charging 16 4 4 Load Connection 16 4 5 Modem Phone line Connection 16 4 6 DC Start Function 16 4 7 Turn On Off 16 4 8 UPS Setup 16 4 9 Tower Setup 17 4 9 1 TOWER CONFIGURATION SETUP 17 4 9 2 RACK MOUNT ...

Page 3: ... failure the maintenance free batteries will power the whole system This manual covers the following Models of UPS Please confirm if the model purchased is included in the following list Model No Type 4KVA Long backup time on line UPS 6KVA Long backup time on line UPS Features Pure sine wave output Rotatable LCD display design Tower Rack multi configuration for flexible installation Microprocessor...

Page 4: ...ve the input power cord when this UPS is turned on This removes the safety ground from this UPS and the equipment connected to the UPS 4 Turn off this UPS and disconnect input power cord before battery replacement 5 The battery contains high short circuit current Replacing or servicing the battery which should be performed and supervised by qualified service personnel knowledgeable of batteries an...

Page 5: ...e supply from battery The battery supply should be therefore disconnected from the plus and minus pole of the battery when performing inside maintenance or service of the unit 13 The mains socket outlet that supplies the UPS shall be installed nearby the UPS and shall be accessible easily 2 2 Description of Commonly Used Symbols Some of all the following symbols may be used in this manual It is ad...

Page 6: ...5 3 SYSTEM DESCRIPTION 3 1 Front Panel 4K 6K ...

Page 7: ...Switch For doing the UPS parameter configuration 3 Enter Switch To confirm the parameter setting 4 Input Information Input parameters voltage frequency 5 Output Information Output parameters voltage frequency 6 Bypass Indicator Operating in bypass mode 7 ECO Indicator Operating in economic mode 8 Inverter Indicator Operating in inverter mode 9 Warning Information Warning and fault indicators 10 Ba...

Page 8: ... wide range input source including frequency and waveform 4 The default settings are Economic mode disabled Bypass mode disabled Generator input type disabled and the rated output voltage is at 230V 5 Your configuration will be memorized by UPS which means that the default setting could be changed 3 5 Enter Switch This button has three functions z To confirm the selected setting in Config mode acc...

Page 9: ...t including output voltage and output frequency The LCD panel indicates that the output voltage is 230V and output frequency is 50Hz 3 8 Bypass mode The LCD symbol indicates that the UPS is in Bypass mode The typical display when UPS is in bypass mode 3 9 Economic mode The LCD symbol illuminates when UPS is in Economic mode The typical display when UPS is in economic mode ...

Page 10: ...Fan fails Steady Fan fails and the time is out Flash UPS is overload Steady UPS is overload and the time is out Flash Battery is bad or battery is disconnected Flash Battery is overcharged Steady Output voltage is out of range Flash Over temperature alarm In Bypass Steady Over temperature fault Output Off Steady Inner circuitry fault Note If the symbol flashes it means the minor problem and the ou...

Page 11: ... current load percentage in rated load of the UPS Examples for LCD display z The AC source is available and the UPS is turned on UPS in Bypass mode Economic mode or Inverter mode z The AC source is not present and UPS is turned on UPS in battery mode z The AC source is present but UPS doesn t be turned on UPS in standby mode ...

Page 12: ...ypass mode The default setting is 0 Part C This part is for the rated output voltage setting 220V 230V 240V are supplied for selecting and setting The default setting is 230V Part D This part is for the Generator input type enabled or disabled setting Setting to 1 means the Generator input type is enabled Otherwise setting to 0 means disable the Generator input type The default setting is 0 For ex...

Page 13: ...appear in the LCD as below And the first setting item 1 is blinking Step 2 Push the Config button to switch the option which makes 1 switch to 0 and blink Step 3 Push the Enter button to confirm the option and then the ECO mode is changed to be disabled Simultaneously the second setting item 0 starts to blink Step 4 Push the Config button to switch the option which makes 0 switch to 1 and blink St...

Page 14: ...p 8 Push the Enter button to confirm the option and then the rated output voltage is changed to 220V Simultaneously the last setting item 0 starts to blink Step 9 Push the Config button to switch the option which makes 0 switch to 1 and blink Step 10 Push the Enter button to confirm the option and then the Generator input type is changed to be enabled Simultaneously all the settings are completed ...

Page 15: ...Can be silenced Warning for over temperature Continuously Sounding Can be silenced Warning for battery bad Continuously Sounding Can be silenced Warning for battery overcharged Continuously Sounding Can be silenced Warning for battery disconnected Sounding every second Can be silenced Warning for overload Sounding every second Can be silenced Warning for battery test Sounding every two seconds Can...

Page 16: ...15 Rear Panel Description Rear panel description table 1 I P Terminal 5 External Battery Connector 2 O P Terminal Socket 6 RS232 DRY CONTACT 3 RJ11 RJ45 7 I P Breaker 4 SNMP Slot 8 EPO Connector ...

Page 17: ... charge may be lost during shipping The battery should be recharged prior to use Plug the UPS into an appropriate power supply and allow the UPS to charge at least 4 hours 4 4 Load Connection Connect one load related device to each of the power receptacles supplied at the rear of the UPS 4 5 Modem Phone line Connection Plug incoming telephone line into the In socket at the back of the UPS Use on t...

Page 18: ...he optional UPS stand to stabilize the UPS when the UPS is positioned in vertically The UPS stand must be attached to the bottom of the tower 4 9 1 TOWER CONFIGURATION SETUP This model is provided with the UPS stand necessary to stabilize the UPS when it s positioned in vertically The UPS stand must be inserted to the bottom of the tower 4KVA 6KVA ...

Page 19: ...Align the mounting ears with screw holes on the side of the UPS 2 Fix the slide to the rack enclosure with screws 3 Insert UPS into the slide assemblies and lock it in the rack enclosure 4 9 3 LCD display cover setup The LCD display of the this model can be rotate to adapt to rack or tower installation Follow the below steps and charts you can rotate the LCD display ...

Page 20: ...to enable power to the UPS output receptacles 6 Plug in the UPS then pressing power switch ON OFF button to turn on the UPS 7 Activate the external EPO switch to test the EPO function 8 De activate the external EPO switch and restart the UPS 4 9 5 Net Tel Connection A telephone modem or network cable can be connected to the modular RJ 45 RJ11 connectors located on the rear of the UPS Doing this ca...

Page 21: ...Properly recycle or dispose of used battery Do not dispose of batteries in a fire The batteries may explode Note If you are not qualified service personnel do not attempt to open the battery door Please call local dealer or distributor immediately Recycle the used battery z Never dispose the batteries in a fire It may explode z Do not open or mutilate the batteries Released electrolyte is harmful ...

Page 22: ...y Output Low Battery Output normally open pull to Pin 5 when battery low alarm in battery mode 2 TxD Output TxD 3 RxD Input RxD 4 DTR Input tied to pin 6 5 Common Common tied to chassis 6 DSR Output tied to pin 4 7 RTS Input No connection 8 AC Fail Output AC Fail Output normally open pull to Pin 5 when UPS is in battery mode ...

Page 23: ...es 2 Ensure loads are not detective or shorted internally The UPS is not on when power switch is pressed Internal fuse may be blown Please contact your local dealer Power presents on one output receptacle Check the output fuse UPS could not provide power to the load No output from any output receptacle 1 Check the connected cable 2 Ensure the load does not exceed the maximum rating of UPS Battery ...

Page 24: ...o 3 1 Output connection Hard wire Output Overload capacity Line mode Over 110 for 2mins then transfer to bypass and alarm Over 150 for 1s then transfer to bypass and turn off output after 1min and alarm Battery mode Over 110 for 30s then turn off output and alarm Over 120 for 1s then turn off output and alarm Transfer time AC to DC 0 ms Inverter mode 93 Battery mode 92 Efficiency ECO mode 97 Batte...

Page 25: ... 500m 0 40 C 1 501 3 000m 0 35 C Storage temp 20 C 55 C Relative humidity 0 95 humidity non condensing Environmental Operating elevation 3 000 meters Installation Rack Tower 2 in 1 Dimension DxWxH 454x440x88mm 454x440x132mm Physical Net weight kg 12kg 13 5kg Safety CE Others EMC EN 50091 2 EN 55022 EN 61000 4 2 Level 4 ESD EN 61000 4 3 Level 3 EN 61000 4 4 Level 3 EN 61000 4 5 Level 4 Surge ...

Page 26: ...25 9 SOFTWARE INSTALLATION WinPower XP is a brand new UPS monitoring software which provides user friendly interface to monitor and control your UPS ...