background image

Installation OZD Profi 12M ...

Release 01 07/2017

Technical Support

https://hirschmann-support.belden.eu.com

User Manual

Installation
Fiberoptic Repeater
OZD Profi 12M ...

Summary of Contents for OZD Genius G12-1300

Page 1: ...Installation OZD Profi 12M Release 01 07 2017 Technical Support https hirschmann support belden eu com User Manual Installation Fiberoptic Repeater OZD Profi 12M ...

Page 2: ... here are binding only if they have been expressly agreed when the contract was made This document was produced by Hirschmann Automation and Control GmbH according to the best of the company s knowledge Hirschmann reserves the right to change the contents of this document without prior notice Hirschmann can give no guarantee in respect of the correctness or accuracy of the information in this docu...

Page 3: ...ical fiber link monitoring 27 2 2 Star topology 28 2 3 Redundant ring 30 3 Installation guidelines 32 3 1 Electromagnetic compatibility EMC 32 3 2 Interference suppression of switched inductances 32 3 2 1 Suppressing switched inductances with fuses 32 3 2 2 Cabinet lighting 32 3 3 Arrangement of devices and cables 33 3 3 1 Reducing interference by providing adequate space 33 3 3 2 Standard recomme...

Page 4: ...itting power 45 4 5 Connecting the optic bus cables 46 4 6 Connecting the electric bus cables 47 4 7 Connecting the function ground and the shield of the bus cable 49 4 8 Connecting the power supply 50 4 9 Connecting the signal contact optional 51 4 10 Connecting the analog voltage outputs optional 52 5 Configuration 54 6 Disassembly 56 7 Technical data 57 8 Scope of delivery order numbers and acc...

Page 5: ...sonnel to work on the device Qualified personnel have the following characteristics Qualified personnel are properly trained Training as well as practical knowledge and experience make up their qualifications This is the prerequisite for grounding and labeling circuits devices and systems in accordance with current standards in safety technology Qualified personnel are aware of the dangers that ex...

Page 6: ...ound the device before connecting any other cables Disconnect the grounding only after disconnecting all other cables Ground the device via the ground screw Requirements for connecting electrical wires Before connecting the electrical wires always verify that the requirements listed are complied with All of the following requirements are complied with The electrical wires are voltage free The cabl...

Page 7: ...ent air temperatures of at least 167 F 75 C The power cord wires are made of copper The wire diameter of the power supply cable is at least 0 75 mm North America AWG18 on the supply voltage input The following requirements are alternatively complied with Alternative 1 The power supply complies with the requirements for a limited power source LPS as per EN 60950 1 Alternative 2 Relevant for North A...

Page 8: ...he disposal of the relevant authorities at the following address Hirschmann Automation and Control GmbH Stuttgarter Str 45 51 72654 Neckartenzlingen Germany The product can be used in the industrial sector Interference immunity EN 61000 6 2 Emitted interference EN 55032 Reliability EN 60950 1 You find more information on technical standards here Technical data on page 57 Warning This is a class A ...

Page 9: ...hese requirements are designed to provide sufficient protection against interference when the device is being used in a business environment The device creates and uses high frequencies and can also radiate these frequencies If it is not installed and used in accordance with this operating manual it can cause radio transmission interference The use of this device in a residential area can also cau...

Page 10: ...al The Installation user manual contains a device description safety instructions a description of the display and the other information that you need to install the device Key The symbols used in this manual have the following meanings Listing Work step Subheading ...

Page 11: ...n line star or ring topology and an arbitrary combination of these can also be built up Device casing The device is supplied in a metal housing You have the option of mounting the device onto the DIN rail Glass fiber technology The use of glass fiber transmission technology enables a very large transmission range and ensures optimal protection from EMC effects on the transmission path and due to t...

Page 12: ...ce has 2 3 4 mutually independent ports channels which in turn consist of a transmitting and a receiving component The electric ports are a 9 pole D Sub socket female A PROFIBUS bus segment can be connected to this ports The optical ports are BFOC 2 5 ST sockets CH3 CH4 CH3 CH3 CH4 CH1 CH1 CH2 ...

Page 13: ...ions are uncoupled by means of diodes to prevent reverse voltage supply or destruction through incorrect pole connection There is no load distribution between the sources With redundant supply the power supply unit with the higher output voltage must supply the repeater alone Signal contact A signal contact relay with unconnected contacts is used to signal various disruptions in the repeaters The ...

Page 14: ...specific requirements by means of DIP switches which can easily be operated from outside The following settings are possible Setting the compatibility to OZD Profi a version See Setting compatibility on page 40 Setting the operating mode and transmitting power See Setting the operating mode and transmitting power on page 43 Reducing the optical transmitting power See Reducing the optical transmitt...

Page 15: ... blocked If the transmission rate changes during operation this is detected by the repeaters which then automatically adjust their settings accordingly Transfer malfunctions may temporarily occur while the rate is being altered Signal regeneration The repeaters regenerate the signal form and amplitude of the data received This allows up to 122 OZD Profi 12M to be cascaded limited by the address sp...

Page 16: ...ode Electric port without segment monitoring Interference from the electrical segment affects the entire network The following functions are only available for the optical channels Whether the functions can be activated depends on the operating mode which has been set Line monitoring with echoes The repeaters enable the connected optical paths to be actively monitored for interruptions in the fibe...

Page 17: ...l network send test frames to the segmented ports These test frames which are to be received regularly can be used by both repeaters to check the status of the field bus partial network The segmentation is automatically lifted as soon as the test frames indicate to both repeaters that the segmented field bus partial network is no longer disturbed If all active bus subscribers are deactivated in a ...

Page 18: ...ntact measuring output 2 8 pin DIP switch 3 CH1 electrical port 4 Grounding screw 5 CH3 optical port only applies to the device variants OZD Profi 12M G11 G11 1300 P11 6 CH3 CH4 optical ports only applies to the device variants OZD Profi 12M G12 G12 1300 G12 EEC G12 1300 EEC P12 7 LED display element for system status and port status CH1 S0 S1 S2 S3 S4 S5 S6 S7 S8 1 0 System CH1 CH3 CH4 System CH1...

Page 19: ...2 1300 EEC P22 1 8 pin terminal block for power supply signal contact measuring output 2 8 pin DIP switch 3 CH2 electrical port 4 Grounding screw 5 CH3 CH4 optical ports 6 CH1 electrical port 7 LED display element for system status and port status CH1 CH2 CH3 CH4 S0 S1 S2 S3 S4 S5 S6 S7 S8 1 0 2 3 6 4 5 1 System CH1 CH2 CH3 CH4 7 ...

Page 20: ...er has been activated token frames on their own are not enough to set the transfer rate The connected RS 485 segment is only terminated at one end Signal contact no signal red green flashes Transmission rate recognized but the network slot time could not be determined network parameter HSA is set too low no transmitting bus subscriber present one optical port is set to Redundant optical ring mode ...

Page 21: ...to Port 1 CH1 Signal contact signal repeater and another bus subscriber connected via Port 1 CH1 are both sending at the same time e g because an address has been assigned twice the setting of the slot time is too low or during lifting of the segmentation in the optical lin Signal contact no signal RS 485 driver of the repeater is defective e g after lightning strike none Bus subscriber is not con...

Page 22: ... optical fiber connector Optical fiber in the optical fiber connector is loose Only one active bus subscriber is connected which only sends tokens to itself A fault should not be signaled as soon as a second subscriber is activated Signal contact signal none Transmission rate has not yet been recognized LED System flashes red No transmitting bus subscriber present Send and receive optical fibers h...

Page 23: ...ed at the optical channel Signal contact no signal none No transmitting bus subscriber present Send and receive optical fibers have been transposed No partner repeater connected or partner repeater is not switched on Connected partner repeater is defective Signal contact no signal LED Color Meaning ...

Page 24: ... optical fiber lines in order to exclude the possibility of EMC affecting the whole network Optically only OZD Profi 12M of the same type can be connected together OZD Profi 12M P11 with P12 OZD Profi 12M G11 with G12 and G12 EEC OZD Profi 12M G11 1300 with G12 1300 and G12 1300 EEC Optical ports which are connected by optical fiber must be set to the same operating mode Junctions between differen...

Page 25: ... monitoring determines the availability of this fiber line It is recommended that fiber link monitoring be used in homogeneous OZD Profi networks default factory setting Please note that the following ambient conditions must be fulfilled to ensure that network configuration functions correctly The parameters MIN TSDR described in the PROFIBUS standard EN 50170 must be set to a value 11 on all term...

Page 26: ...d and by activation of the signaling contacts The segmentation is lifted automatically as soon as both repeaters recognize that the field bus network is functioning correctly with the help of test frames Please note that in the case of networks with several active bus subscribers two logical token rings are formed in the event of an error Every time the partial networks are switched together netwo...

Page 27: ... with another optical fiber network component which does not send a frame echo and does not expect or is not compatible with a frame echo in accordance with PROFIBUS guidelines optical electrical converter Individual fiber links are not monitored in this operating mode Monitoring mechanism Send echo no Monitor echo no Suppress echo no Monitor no Segmentation no ...

Page 28: ...cal port electrical star segment All OZD Profi 12M types for different fiber types plastic PCF glass can be combined using the electrical star segment CH1 CH3 Terminal unit s bus segment OZD P11 G11 1300 CH1 CH3 Terminal unit s bus segment OZD P11 G11 1300 CH1 CH3 Terminal unit s bus segment OZD P11 G11 1300 CH1 CH3 Terminal unit s bus segment OZD P11 G11 1300 CH1 CH3 Terminal unit s bus segment O...

Page 29: ...ect a bus subscriber to the electrical star segment wherever possible This applies exclusively to device variants OZD Profi 12M x22 Connect other bus subscribers to the second electrical port CH2 Repeaters with one or two optical ports can be used to create an active PROFIBUS star coupler Repeaters with one optical port are sufficient for connecting a terminal or an RS 485 bus segment to the activ...

Page 30: ...e terminals connected to this repeater or the RS 485 segment are uncoupled from the ring The remainder of the network itself continues to function as a line The error is indicated by the LEDs on the two OZD Profi 12M connected to the malfunctioning optical fiber and their signaling contacts The segmentation is lifted automatically as soon as both repeaters recognize that the segmented field bus ne...

Page 31: ... This condition can arise when a master selects a device whose address has been configured but which does not physically exist The master tries to address this device cyclically and waits for a reply only until the configured slot time has been exceeded GAP request The OZD Profi 12M recognizes this condition and closes the optical line to an optical ring in the middle of this request sequence This...

Page 32: ... 3 2 1 Suppressing switched inductances with fuses Switching inductances e g in relays and fans generates interference voltages which are many times higher than the switched operating voltage These interference voltages can affect electronic devices The interference voltages of inductances must be limited at their source of emission by means of fuses by connecting diodes or RC elements Only use in...

Page 33: ...rections around OZD Profi 12M The power supply wires 24 V DC and 0 V for the OZD Profi 12M must not be laid in the same cable duct as cables for load circuits The wires 24V DC and 0 V should be twisted together 3 3 2 Standard recommendations for the arrangement of devices and cables EN 50174 2 contains recommendations for arranging devices and cables which are aimed at reducing mutual interference...

Page 34: ... the aluminum foil shield One side of the foil shield is attached to a plastic film to increase its tearing strength and is therefore non conductive The shields of all cables which are routed into a cabinet from the outside must be clamped at the point of entry inside the cabinet and connected to the cabinet ground with a large contact surface area When removing the cable jackets it is important t...

Page 35: ...facturer s instructions Laying cables outside of control cabinets PROFIBUS cables and cables for DC and AC voltages 400 V unscreened areas with explosion hazard and telephone cables separate cable runs spaced at least 10 cm apart All cable ducts should be constructed of electrically conducting material and connected to functional ground at regular intervals Bus cables should not be subject to mech...

Page 36: ...ny places as possible Electrically conducting pipes parts of machines or supporting structures should be integrated in the potential equalization system In order to ensure long term reliability appropriate measures should be undertaken to protect against corrosion The potential equalization cable must be protected against corrosion The cross section of the potential equalization cable should be ch...

Page 37: ...ciple the same rules apply to laying cables outside of buildings as within buildings However for outside installation the cables should be provided with additional protection by laying them inside a suitable plastic pipe The transition from external to internal cables should always use an auxiliary terminal block It is used to interconnect the cable for burial in the ground with the standard bus c...

Page 38: ... Mounting the device Setting compatibility Connecting the optic bus cables Connecting the electric bus cables Connecting the function ground and the shield of the bus cable Connecting the power supply Connecting the signal contact optional Connecting the analog voltage outputs optional 4 1 Checking the package contents Proceed as follows Check whether the package includes all items named in the se...

Page 39: ...e in a location where the climatic threshold values specified in the technical data are adhered to See Technical data on page 57 Ensure that there is sufficient room to connect the bus and power supply cabling Connect the optical fiber line before mounting the repeater as this simplifies the procedure Proceed as follows Slide the upper snap in guide of the device into the DIN rail Press the device...

Page 40: ...rectly compatible When operating OZD Profi 12M with OZD Profi G3a G4a G3a 1300 G4a 1300 P3a P4a the functional compatibility must be switched on S8 1 Only turn switch S8 to Position 1 if the OZD Profi 12M a is being used as a spare or expansion device in existing networks in conjunction with these devices and a direct optical connection is to be made The following tables show the switch assignment...

Page 41: ...3 1 CH2 terminated S4 Termination S4 0 CH2 not terminated not relevant Termination extern S4 1 CH2 terminated S5 optical Power Distance S5 0 Network configuration Standard S4 0 Network configuration Standard S5 1 Network configuration Extended S4 1 Network configuration Extended S6 optical Power S6 0 Without function S6 1 Without function S8 1 Compatibility ON S0 S5 0 Without function S6 S7 0 in P...

Page 42: ...n S4 0 CH2 not terminated not relevant Termination extern S4 1 CH2 not terminated S5 optical Power Distance S5 0 CH3 optical Power Standard S6 0 CH2 optical Power Standard S5 1 CH3 optical Power High S6 1 CH2 optical Power High S6 optical Power Distance S6 0 CH4 optical Power Standard S7 0 CH3 optical Power Standard S6 1 CH4 optical Power High S7 1 CH3 optical Power High S8 1 Compatibility ON S0 S...

Page 43: ...ical port CH2 This applies exclusively to device variants OZD Profi 12M x22 The DIP switches S2 and S3 are used to set the operating mode of the optical port CH3 The DIP switches S4 and S5 are used to set the operating mode of the optical port CH4 4 4 1 Setting the operating mode of the electrical ports CH1 CH2 Operating mode electrical ports CH1 CH2 with segments monitoring CH1 is activated in th...

Page 44: ...the optical ports Operating mode Line with optical fiber link monitoring and segmentation CH1 is activated in this operating mode if S0 is in Position 1 Please note that this operating mode should only be set in the star segment of the star topology Applies to device variants with 2 electrical ports CH2 is activated in this operating mode if S1 is in Position 1 Please note that this operating mode...

Page 45: ... is used to set the transmitting power of CH3 The DIP switch S7 is used to set the transmitting power of CH4 CH3 is activated in this operating mode if S2 is in Position 1 and S3 is in Position 0 CH4 is activated in this operating mode if S4 is in Position 1 and S5 is in Position 0 CH3 is activated in this operating mode if S2 and S3 are in Position 1 CH4 is activated in this operating mode if S4 ...

Page 46: ... the Technical Data Make sure that each optical input is connected to an optical output at the opposite end cross overlink The corresponding BFOC sockets of the two ports are marked on the lower front panel Ensure sufficient strain relief for the fiber optic cables and pay attention to their minimum bend radiuses Unused BFOC sockets are to be covered with the protective caps supplied Incident ambi...

Page 47: ...dard At Pin 6 there is a short circuit proof 5 V output for supplying external pull up pull down resistors As opposed to the 24V power supply the RS 485 bus lines RxD TxD N and RxD TxD P are indirect coupled functional separation within SELV restrictions The RS 485 interface is electrically connected to the front panel function ground Only use shielded and twisted pair wiring as a RS 485 bus line ...

Page 48: ...e the RS 485 bus line from the OZD Profi 12M if a device is not connected to the other end or there is an OZD Profi which has been disconnected from the power supply The open line otherwise acts as an antenna and can cause interference When connecting a RS 485 bus line to the OZD Profi 12M in an active network keep to the following sequence in order to avoid interference Place the RS 485 bus conne...

Page 49: ...ent earth potential The different voltages could destroy the repeaters Avoid electrical bus lines which are partly or entirely laid outside buildings If lightening strikes close by this could destroy the repeaters Use F O cables for bus connections outside buildings The shield of the bus cable together with the function ground connection must be connected to an equipotential rail in the switch cab...

Page 50: ... power supply consisting of separate sources can be used You can input the supply voltage in two ways Terminal 24 V L1 of the terminal block Terminal 24 V L2 of the terminal block The minus connection for each is indicated by 0V The two voltages can have any values even different ones within the specified limits However there is no load distribution If necessary the power supply unit with the high...

Page 51: ...of a relay can be used as signal contacts When the OZD Profi 12M is working correctly the contact is closed If there is an error or a power failure the contact is opened The following problems with the network and the repeater can be signalled by means of the signal contact Supply voltage interrupted incorrectly connected Internal device errors Received data no input signal at port 3 optical The n...

Page 52: ...is purposes and for example for preventative maintenance in the range from 0 5 V each with reference to GND of the 8 pin terminal block The analog voltage outputs are electrically connected to the front panel function ground The measuring voltage can be determined by a standard volt meter ungrounded high impedance This allows the incoming optical power to be documented e g for later measurements a...

Page 53: ...vel meter However it provides each optical port with a voltage derived from the peak value of the optical PROFIBUS telegram without disrupting the communication of data With regular bus operation this analog voltage can be used as an indicator for an alteration in optical attenuation Because data traffic and temperature can affect the voltage value you should not set any warning threshold too clos...

Page 54: ... the user specific profile of the configuration tool to set the parameters under 2 and 3 Calculate the slot time with the following equation Slot time a b LengthOF c NumberOZD Slot time is the monitoring period in bit times Length OF is the sum of all the optical fiber lines segment lengths in the network Number OZD is the number of OZD Profi 12M in the network Data rate a b c 12 Mbit sa a Use the...

Page 55: ... Profi 12M G11 1300 and G12 1300 EEC at data rates of 12 MBit s 6 MBit s 3 MBit s and 1 5 MBit s the minimum slot times according to the following table must be met See table 9 on page 55 Data rate a b c 12 Mbit sa 1651 240 28 6 Mbit sa 951 120 24 3 Mbit sa 551 60 24 1 5 Mbit sa 2011 30 24 500 kBit s 771 10 24 187 5 kBit s 771 3 75 24 93 75 kBit s 451 1 875 24 45 45 kBit s 851 0 909 24 19 2 kBit s...

Page 56: ...56 Installation OZD Profi 12M Release 01 07 2017 6 Disassembly To remove the device pull down on the locking slide 1 ...

Page 57: ...each voltage input Nominal rating Characteristic 2 A slow blow Output voltage current for terminal resistors Pin 6 D Sub socket 5 V DC 5 10 Peak inrush current 4 A Signal contact See Requirements for connecting electrical wires on page 6 Maximum Switching current 1 A Maximum switching voltage 60 V DC Maximum switching capacity max 30 V DC resistive load Signal transmission Transmission speed 9 6 1...

Page 58: ...his variant is designated the OZD Profi 12M G12 1300 EEC The DIP switches on the OZD Profi 12M G12 1300 EEC may also only be operated at ambient temperatures between 32 F 140 F 0 C 60 C Optical port P G G 1300 Wavelength 650 nm 860 nm 1300 nm Launchable optical power in fiber 10 125 default 19 dBm in fiber 50 125 default 17 dBm 17 dBm in fiber 62 5 125 default 13 dBm 17 dBm in fiber 200 230 125 de...

Page 59: ...ed emission EN 55022 Class A EN 55032 Class A FCC 47 CFR Part 15 Class A EMC interference immunity Electrostatic discharge EN 61000 4 2 IEEE C37 90 3 Contact discharge 4 kV EN 61000 4 2 IEEE C37 90 3 Air discharge 8 kV Electromagnetic field EN 61000 4 3 80 MHz 1000 MHz 10 V m 1400 MHz 2000 MHz Fast transients burst EN 61000 4 4 IEEE C37 90 1 DC supply connection 2 kV EN 61000 4 4 IEEE C37 90 1 Dat...

Page 60: ...60 Installation OZD Profi 12M Release 01 07 2017 Dimension drawings 39 5 110 4 4 35 16 35 0 64 10 75 0 42 12 47 0 49 mm inch 83 95 3 31 1 56 20 0 79 ...

Page 61: ... OZD Profi 12M G11 942 148 001 OZD Profi 12M G12 942 148 002 OZD Profi 12M G22 942 148 003 OZD Profi 12M G11 1300 942 148 004 OZD Profi 12M G12 1300 942 148 005 OZD Profi 12M G22 1300 942 148 006 OZD Profi 12M P11 942 148 007 OZD Profi 12M P12 942 148 008 OZD Profi 12M P22 942 148 009 OZD Profi 12M G12 EEC 942 148 102 OZD Profi 12M G12 1300 EEC 942 148 105 OZD Profi 12M G22 EEC 942 148 103 OZD Pro...

Page 62: ...logy equipment Radio disturbance characteristics Limits and methods of measurement EN 55032 Electromagnetic compatibility of multimedia equipment EN 61000 3 2 Electromagnetic compatibility EMC Part 3 2 Limits Limits for harmonic current emissions EN 61000 3 3 Electromagnetic compatibility EMC Part 3 3 Limits Limitation of voltage changes voltage fluctuations and flicker EN 61000 6 2 Electromagneti...

Page 63: ...bus segment using a PROFIBUS bus monitor Check the configuration of all bus subscribers Fault indicated on CH3 CH4 Make sure that optically only repeaters of the same type are connected together See Network Topologies on page 24 Make sure that the optical ports which are connected via optical fibers have been set to the same operating mode See Setting the operating mode and transmitting power on p...

Page 64: ...mitting power on page 43 See Setting compatibility on page 40 Were the following points taken into account regarding topology Line topology Line topology selected and set according to the specifications in chapter Line topology with or without F O link monitoring See Line topology on page 25 Star topology CH1 must be switched to Monitor off mode S0 1 for all OZD Profi 12M connected to the electric...

Page 65: ...ooting have been clarified then please contact our support with answers to the following questions Exact type designation of the OZD Profi 12M For identification purposes please provide the order number printed on the device 18 digits What data rate is being used How are the DIP switches set on all the devices Send us a detailed network plan with the fiber type and fiber length the location and le...

Page 66: ...mann Competence Center is ahead of its competitors on three counts with its complete range of innovative services Consulting incorporates comprehensive technical advice from system evaluation through network planning to project planning Training offers you an introduction to the basics product briefing and user training with certification You find the training courses on technology and products cu...

Page 67: ...Installation OZD Profi 12M Release 01 07 2017 67 ...

Page 68: ...68 Installation OZD Profi 12M Release 01 07 2017 ...

Page 69: ...Installation OZD Profi 12M Release 01 07 2017 69 ...

Page 70: ...70 Installation OZD Profi 12M Release 01 07 2017 ...

Page 71: ...Installation OZD Profi 12M Release 01 07 2017 71 ...

Page 72: ......

Reviews: