background image

REMOTE CONTROLLER

Read and understand this manual before using this air conditioner. Keep this manual for future reference.

Lea cuidadosamente este manual antes de poner en marcha el equipo de aire acondicionado. Guarde este manual en un lugar seguro por si
necesita consultarlo en el futuro.

Diese Bedienungsanleitung muB vor der inbetriebnahme der Klimaan lage gelesen und verstanden werden. Das Handbuch für spätere
Rückfragen aufbewahren.

Lire attentivement ce manuel avant taute utilization du climatiseur, et le conserver pour référence ultérieure

Leggere attentamente il presente manuale prima di utilizzare questo condizionatore d’aria. Conservarlo da parte per future consultazioni.

Leia e compreenda este manual antes de operar este ar condicionado. Guarde este manual para futura referencia

De bor laese og forsta denne vejledning, for de tager dette dlimaanlaeg i brug. Opbervar vejledningen til senere reference.

Lees deze hadleiding aandachtig door alvorens de airconditioning in gebruik te nemen.

Läs och första denna manual innan Du sätter igang luftkonditioneraren. Förvara denna manual förvara denna manual för framtida behow.

Griego-griego-griego-griego-djflksjfskdjfklsjdflkjflsjfslkfjslkfjslkdfjslkdfjjjjjjjjjjjjjjjjjjjjjjjjjjjjjjjjjjjjjjjdddddddddddddddñlññññññññññkkkkkk

INSTALLATION  MANUAL

MANUAL DE INSTALACIÓN

INSTALLATIOSANLEITUNG

MANUEL D’INSTALLATION

MANUAL DE MONTAGEM

INSTALLATIONSVEJLEDNING

INSTALLATIEHANDLEIDING

INSTALLATIEHANDLEIDING

ENGLISH

ESP

AÑOL

DEUTSCH

FRANÇAIS

IT

ALIANO

POR

TUGUÊS

D

ANSK

NEDERLANDS

SVENSKA

Model: PC-2H2

Summary of Contents for PC-2H2

Page 1: ...onsultazioni Leia e compreenda este manual antes de operar este ar condicionado Guarde este manual para futura referencia De bor laese og forsta denne vejledning for de tager dette dlimaanlaeg i brug Opbervar vejledningen til senere reference Lees deze hadleiding aandachtig door alvorens de airconditioning in gebruik te nemen Läs och första denna manual innan Du sätter igang luftkonditioneraren Fö...

Page 2: ......

Page 3: ...run any cable for transmission and signal along the power line 220 240V 380 415V DO NOT run any cable for transmission and signal along other cables for transmission and signal If the cables are required to be run along keep a distance more than 30 cm between each cables or insert the cables for each transmission system into the metal conduit tube and ground one end of the conduit tube n Location ...

Page 4: ...f the holding bracket push and turn the screwdriver and remove the controller from the holding bracket as shown in the figure below Fig 2 Installation Procedure Fig 3 Installation Procedure 2 Attach the controller to the holding bracket as follows A In case of exposing Remote Control Cable É Fix the holding bracket onto the wall as shown below Fig 4 Attach the controller Ê Make the hole for drawin...

Page 5: ...nting work is finished Fig 10 Mounting procedures CAUTION Pay attention so that the cable may not be slack If the cable is slack as shown in the above figure the cable cord especially the naked part may be clamped at the hole and it may cause a faulty operation 1 4 WIRING SYSTEM FOR REMOTE CONTROL SWITCH PC 2H2 1 4 1 LENGTH OF WIRE CABLE FOR REMOTE CONTROL SWITCH Length of the standard wire cable ...

Page 6: ...wires B After checking the color of the wires connect each wire of the same color by soldering C Insulate the soldered parts and the wires with insulation tape D The maximum total cable length of the remote control switch cable and the bridge cable s is 200 meters 0 3mm2 wire or 500 meters 0 75mm2 wire 3 Separate the cable more than approximately 30cm from any wires which are utilized for wires hi...

Page 7: ... Bridge Cable 9 Contact of Connectors of Bridge Cable Ë Back to É after checking Ì Select TEST RUN MODE by depressing MODE Switch COOL OR HEAT Í Depress RUN STOP switch a The TEST RUN operation will be started The TEST RUN operation will be finished after 2 hours unit operation or by depressing the RUN STOP switch again b IF the unit do not start or the operation lamp on the remote control switch ...

Page 8: ...pressor Heat Pump Twin 11 Thermistor Abnormality for inlet Air Temperature All Models 12 Thermistor Abnormality for outlet Air Temperature Heat Pump Twin 13 Thermistor Abnormality for Freezing Temperature All Models 20 Thermistor Abnormality for Compressor Top Temperature Heat Pump Twin 22 Thermistor Abnormality for Outdoor Air Temperature Heat Pump Twin 24 Thermistor Abnormality for Outdoor Evapo...

Page 9: ...etting temperature is turned OFF b At the condition of the above item a press the TEMP switch or the TEMP switch of the remote control switch and the indoor unit for which the optional function is to be set can be changed NOTES The indoor unit can be selected among the indoor units connected to the remote control switch In case that both the indications of the address and the refrigerant cycle num...

Page 10: ...0 01 Not Available Available b4 Change of Filter Cleaning Time 00 01 02 03 04 Standard 100 hours 1200 hours 2500 hours Not Indication b5 Fixing of Operation Mode 00 01 Not Available Available b6 Fixing of Setting Temperature 00 01 Not Available Available b7 Fixing of Operation as Exclusive Cooling Unit 00 01 Not Available Available b8 Automatic COOL HEAT 00 01 Not Available Available b9 Fixing of ...

Page 11: ......

Page 12: ...PMML0041B 12 01 Printed in Spain ...

Reviews: