background image

Copyright HK Instruments 2019

www.hkinstruments.fi

Installation version 8.0 2019

INSTALLATION

INSTRUCTIONS

DIFFERENTIAL PRESSURE TRANSMITTERS 

DPT-Dual Series

•  READ THESE INSTRUCTIONS CAREFULLY BEFORE 

ATTEMPTING TO INSTALL, OPERATE OR SERVICE THIS 
DEVICE.

•  Failure to observe safety information and comply with 

instructions can result in PERSONAL INJURY, DEATH AND/OR 

PROPERTY DAMAGE.

•  To avoid electrical shock or damage to equipment, disconnect 

power before installing or servicing and use only wiring with 
insulation rated for full device operating voltage.

•  To avoid potential fire and/or explosion do not use in potentially 

flammable or explosive atmospheres.

•  Retain these instructions for future reference.
•  This product, when installed, will be part of an engineered 

system whose specifications and performance characteristics 
are not designed or controlled by HK Instruments. Review 
applications and national and local codes to assure that the 
installation will be functional and safe. Use only experienced and 
knowledgeable technicians to install this device.

SPECIFICATIONS

Thank  you  for  choosing  an  HK  Instruments  DPT-Dual  series  dif-
ferential pressure transmitter. DPT-Dual combines two differential 
pressure transmitters into one device. It offers a possibility to meas-
ure pressure from two different points. DPT-Dual is designed with 
five unit selections (Pa, kPa, mbar, inchWC, mmWC) and eight field 
selectable measurement ranges (unidirectional and bi-directional) to 
meet your application requirements. The DPT-Dual series is com-
prised of the DPT-Dual-2500 with ranges from -100–2500 Pa and 
DPT-Dual-7000 with ranges from 0–7000 Pa.

DPT-Dual series devices are commonly used in HVAC/R

systems for:

•  fan, blower and filter monitoring
•  pressure and flow monitoring
•  valve and damper control

SPECIFICATIONS

Performance

Accuracy (from applied pressure):

Model 2500:

     Pressure < 125 Pa = 1 % + ±2 Pa

     Pressure > 125 Pa = 1 % + ±1 Pa

Model 7000:

     Pressure < 125 Pa = 1.5 % + ±2 Pa

     Pressure > 125 Pa = 1.5 % + ±1 Pa

(including: general accuracy, linearity, hysteresis, long 

term stability, and repetition error) 

Overpressure:

Proof pressure: 25 kPa

Burst pressure: 30 kPa

Zero point calibration:

Manual pushbutton 

Response time:

4.0 s or 0.8 s, selectable via jumper

Technical Specifications

Media compatibility:

Dry air or non-aggressive gases

Measuring units:

Pa, kPa, mbar, inchWC, mmWC, selectable via jumper

Measuring element:

MEMS no flow-through

Environment:

Operating temperature: -20...+50 °C

Temperature compensated range 0...+50°C

Storage temperature: -40...+70 °C

Humidity: 0 to 95 % rH, non condensing

Physical

Dimensions: 

Case: 102.0 x 71.5 x 36.0 mm

Weight: 

150 g, with accessories 290 g

Mounting: 

2 each 4.3 mm screw holes, one slotted

Materials:  

Case: ABS

Lid: PC

Pressure inlets: Brass

Duct connectors: ABS

Tubing: PVC

Protection standard: 

IP54

Display (Optional)

2-line display (12 characters/line)

Line 1: active measurement, inlet A

Line 2: active measurement, inlet B

Electrical connections:

4 spring loades terminals, max 1.5 mm

2

Wire: 0.2–1.5 mm

2

 (12–24 AWG)

Cable entry: M20

Pressure fittings:

Male ø 5.0 mm and 6.3 mm

Electrical

Voltage:

Circuit: 3-wire (V Out, 24 V, GND)

Input: 24 VAC or VDC, ±10 %

Output: 2x 0...5/10V (selectable via jumper)

Power consumption: <1.0 W

Resistance minimum: 1 kΩ

 

Conformance

Meets requirements for CE marking:

EMC Directive 2014/30/EU

RoHS Directive 2011/65/EU

WEEE Directive 2012/19/EU

INTRODUCTION

WARNING

APPLICATIONS

RoHS 2

2011/65/EU

COMPANY WITH

MANAGEMENT SYSTEM

CERTIFIED BY DNV GL

= ISO 9001 = ISO 14001 =

Summary of Contents for DPT-DUAL Series

Page 1: ...from 0 7000 Pa DPT Dual series devices are commonly used in HVAC R systems for fan blower and filter monitoring pressure and flow monitoring valve and damper control SPECIFICATIONS Performance Accuracy from applied pressure Model 2500 Pressure 125 Pa 1 2 Pa Pressure 125 Pa 1 1 Pa Model 7000 Pressure 125 Pa 1 5 2 Pa Pressure 125 Pa 1 5 1 Pa including general accuracy linearity hysteresis long term ...

Page 2: ... device is now ready for configuration WARNING Apply power only after the device is properly wired 1 Select the mounting location duct wall panel 2 Use the device as a template and mark the screw holes 3 Mount with appropriate screws Figure 1b Mounting orientation Figure 1c Application connections Display connection Output 0 10 V Output 0 10 V 24 V GND LED Zero button Terminal block Pressure senso...

Page 3: ...talled Circuit closed Grey colour indicates that a jumper is installed Chart 1 Model DPT Dual 2500 Range 1 Range 2 Range 3 Range 4 Range 5 Range 6 Range 7 Range 8 Pa kPa mbar inchWC 100 100 0 10 0 10 1 00 1 00 0 40 0 40 0 100 0 0 10 0 1 00 0 0 40 0 250 0 0 25 0 2 50 0 1 00 0 500 0 0 50 0 5 00 0 2 00 0 1000 0 1 00 0 10 0 0 4 00 0 1500 0 1 50 0 15 0 0 6 00 0 2000 0 2 00 0 20 0 0 8 00 0 2500 0 2 50 0...

Page 4: ... shown under the range number in Chart 3 Grey colour indicates that a jumper is installed Reference figure 3 for jumper installation Chart 3 Inlet B Range 7 Range 8 Range 1 Range 2 Range 3 Range 4 Range 5 Range 6 Jumper J4 Jumper J5 Jumper J6 Grey colour indicates that a jumper is installed Reference Figure 3 and Schematics for jumper installation STEP 6 SELECTING THE RESPONSE TIME The response ti...

Reviews: