background image

HOBO® Motor On/Off Data Logger (UX90-004x) Manual 

15432-F 

The HOBO Motor On/Off data logger records motor on and off conditions by detecting the AC 
magnetic fields given off by a rotating motor using its internal sensor. A second external input 
can be used to detect a variety of external contact closure type inputs. Using HOBOware®, you 
can easily configure the logger for equipment monitoring in a wide variety of applications. This 
compact data logger has a built-in LCD screen for checking status, battery usage, and memory 
consumption. You can also use the LCD screen to quickly calibrate the logger’s motor sensor 
near the motor to be monitored or you can set calibration to preset sensitivity levels with 
HOBOware. There are two models of the HOBO Motor On/Off data logger: the UX90-004 has a 
memory capacity of 128 KB while the UX90-004M has 512 KB. 

Specifications 

Internal Motor Sensor 

 

AC Magnetic Field Threshold 

>40 mGauss at 60 Hz 

External Input 

 

External Contact Input 

Electronic solid state switch closure or logic driven voltage output  

Range 

0 to 3 V DC (USB powered), 0 to 2.5 V DC (battery powered) 

Maximum State and Runtime 
Frequency 

1 Hz 

Solid State Switch Closure 

Input Low: < 10 K

; Input High: > 500 K

 

Internal Weak Pull-Up 

100 K

 

Input Impedance 

Solid state switch closure: 100 K

 pull up 

Logger 

 

Resolution 

Pulse: 1 pulse, Runtime: 1 second, State and Event: 1 State or Event 

Memory Modes 

Wrap when full or stop when full 

Start Modes 

Immediate, push button, date & time, or next interval 

Stop Modes 

When memory full, push button, or date & time 

Time Accuracy 

±1 minute per month at 25°C (77°F) (see Plot A) 

Power Source 

One 3V CR2032 lithium battery and USB cable 

Battery Life 

1 year, typical with logging intervals greater than 1 minute and 
normally open contacts 

Memory 

UX90-004: 128 KB (84,650 measurements, maximum) 
UX90-004M: 512 KB (346,795 measurements, maximum) 

Download Type 

USB 2.0 interface 

Full Memory Download Time 

10 seconds for 128 KB; 30 seconds for 512 KB 

Logger Operating Range 

Logging: -20° to 70°C (-4° to 158°F); 0 to 95% RH (non-condensing) 
Launch/Readout: 0° to 50°C (32° to 122°F) per USB specification 

LCD 

LCD is visible from: 0° to 50°C (32° to 122°F); the LCD may react slowly 
or go blank in temperatures outside this range 

Size 

3.66 x 8.48 x 1.52 cm (1.44 x 3.34 x 0.6 in.) 

Weight 

30 g (1.06 oz) 

Environmental Rating 

IP50 

 

The CE Marking identifies this product as complying with all relevant 
directives in the European Union (EU). 

 

 

 

 

HOBO Motor  
On/Off Data Logger 

Models: UX90-004 

UX90-004M 

Included Items: 

 

Command™ strip 

 

Double-sided tape 

 

Hook & loop strap 

Required Items: 

 

HOBOware 3.3 or later 

 

USB cable (included with 
software) 

Accessories: 

 

Voltage Input Cable 
(CABLE-2.5-STEREO) 

 

AC Current Switch (CSV-A8) 

 

U-Shuttle (U-DT-1) 

Additional sensors and 
accessories available at 
www.onsetcomp.com. 

 

Shop for Data Logging products online at:   

www.

DataLoggerStore

.ca   

1.877.766.5412

Summary of Contents for UX90-004

Page 1: ...1 pulse Runtime 1 second State and Event 1 State or Event Memory Modes Wrap when full or stop when full Start Modes Immediate push button date time or next interval Stop Modes When memory full push button or date time Time Accuracy 1 minute per month at 25 C 77 F see Plot A Power Source One 3V CR2032 lithium battery and USB cable Battery Life 1 year typical with logging intervals greater than 1 mi...

Page 2: ...o stop the logger Note If you also launched the logger with a push button Start this symbol will not appear on the display for 5 minutes The battery indicator shows the approximate battery power remaining If the logger has been configured to stop logging when memory fills the memory bar indicates the approximate space remaining in the logger to record data In this example the logger memory is almo...

Page 3: ...e occurs One state change to the next represents the event duration Runtime The logger checks the state of the line once every second At the end of each logging interval the logger records how many seconds the line was in the logic low state 3 Configure optional filters as necessary Click the Filters button to create additional filtered data series based on the sensor configuration Any filtered se...

Page 4: ... auto calibration process the AC magnetic field is measured via a built in analog to digital converter and the resulting value is used to generate a calibration threshold Note Auto calibration button calibration must be done at the location where the logger will be deployed Preset values are used when motor levels are known in advance and deployment speed is critical In addition the logger has a b...

Page 5: ...close to the motor being monitored as practical Minimize any unwanted vibrations when the motor being monitored is off Protecting the logger The logger is designed for indoor use and can be permanently damaged by corrosion if it gets wet Protect it from condensation If the message FAIL CLK appears on the LCD screen there was a failure with the internal logger clock possibly due to condensation Rem...

Page 6: ...rate heat above 85 C 185 F or recharge the lithium battery The battery may explode if the logger is exposed to extreme heat or conditions that could damage or destroy the battery case Do not dispose of the logger or battery in fire Do not expose the contents of the battery to water Dispose of the battery according to local regulations for lithium batteries HOBOware provides the option of recording...