SiXCOMBO-CN 

 

Combination Smoke/Carbon Monoxide (CO) Detector w/Built-in Wireless 

Transmitter 

(features voice and 360 degree viewable LED ring) 

Installation and Setup Guide 

This device is intended for use with Honeywell Home control panels that support SiX series devices. 

Before installing detectors, please thoroughly read these installation instructions and read the 

Limitations of Fire Alarm Systems

 Insert (P/N 800-15144 5/13), 

System Smoke Detectors 

Application Guide

 (P/N SPAG9101 7/12), and Limitations of Carbon Monoxide Detectors (P/N 

K14670V1 4/8 Rev B). 

See Quick Installation Guide I56-6225 – https://mywebtech.honeywellhome.com.

 

 

 

FEATURES 

  Multi-Criteria Sensing: 

uses four 

sensing elements to react faster 

while minimizing false alarms: 

  -

 Photoelectric smoke sensor 

detects airborne smoke 

particles 

  -

 Carbon Monoxide (CO) sensor 

detects smoldering fires 

  -

 Infrared (IR) sensor measures 

ambient light and flame 

signatures, such as flame 

flicker 

  -

 Heat detection monitors for 

dangerous rise in temperature 

 

 

 

 

  One Go / All Go: all smoke 

detectors in the system 

programmed as one-go-all-

go will sound on alarm.

 

  CO Detector End-of-Life 

reporting (detector needs 

replacing) 

  Smoke detector maintenance 

reporting (detector needs 

cleaning) 

  Low Battery Detection

 

 

 

 

Table 1: Operation Modes 

MODE 

Status LED 

(Top) 

LED Windows 

(Side) 

 

Sounder 

Speaker 

 

Power Up  Blink Green, 

every 2 secs 

Dark 

Silent 

Voice welcome, 

instructions after first 

time power up or  

after default 

Normal 

(Standby) 

Single Blink 

Green every  

10 secs 

Dark 

Silent 

Silent 

Smoke 

Alarm 

Blink Red 

every 10 secs 

Blink red 

Temp-3 

Voice smoke 

warning 

Heat 

Alarm 

Blink Red 

every 10 secs 

Blink red 

Temp-3 

Voice smoke 

warning 

CO Alarm 

Blink Red 

every 10 secs 

Blink blue 

Temp-4 

Voice CO 

warning 

Powered 

Down 

Dark 

Dark 

Silent 

Silent 

    

ENROLLMENT

 

 

 

The SiXCOMBO has a unique MAC ID number. The heat, 

smoke, and CO are assigned to loops 1-3 respectively 

and are enrolled in separate zones. 

NOTE:

 Once enrolled, the device cannot be used with 

another system until it is removed from the current 

controller. See the 24-hour Enrollment Deletion 

section below or the controller’s instructions. 

Enroll the Device Services (Smoke, Heat, CO) 

1. Remove the detector from the base plate (tamper 

switch must be faulted when enrolling). 

2. Put the control panel in Programming mode, when 

prompted: 

3. Pull the battery tab to activate enrollment process (be 

sure batteries are seated properly to avoid a false low 

battery condition). If the battery tab has already been 

removed and the unit is powered up, press either Test 

switch for less than 3 seconds to activate the 

enrollment process. 

 

 

4. The device attempts enrollment (green LED flashes about 8 seconds). If 

successful, the green LED lights steady for 3 seconds and the device 

announces successful enrollment. 

  If the LED does not light steady, enrollment failed. Retry by pressing either 

Test switch for less than 3 seconds. 

All services (Smoke, Heat, and CO) are automatically enrolled in sequential 

(or next available) zone numbers with the following default attributes: 

Zone 

Device Type 

Zone Response 

Type 

Smoke 

Det. 

Smoke Detector 

Fire No Verification 

Heat Det. 

Heat Sensor 

Fire No Verification 

CO Det. 

Carbon Mono. 

Det. 

Carbon Monoxide 

NOTE

: Maintenance and CO End-of-Life are automatically enrolled for 

the respective smoke and CO zones. Contact ID code E386 “Low 

Maintenance Smoke” is sent for the CO zone at End-of-Life and Contact ID 

code E385 “High Maintenance Smoke” is sent for the Smoke Zone when dirty. 

 

Supervision

: Detector supervision is factory set for 1 minute and is not 

programmable. 

 

 

24-Hour Enrollment Deletion 

Use this procedure within 24 hours of initial enrollment to delete this 

device from the controller. This allows reenrollment in a specific 

controller in case enrollment in that controller failed. This resets the 

device to factory default settings and removes the communication link 

data in the controller in which it is enrolled. 

1.  Press and hold both the Smoke and CO test switches 

simultaneously until the welcome message announces, then 

release. 

2.  Wait for the green LED to flash rapidly. 

3.  Press and hold both switches again for one second and release. 

4.  LED blinks rapidly after 15 seconds, confirming deletion. 

LANGUAGE SELECTION 

1.  Press and hold both the Smoke and CO test switches 

simultaneously for 5 seconds until Welcome message is 

announced, then release. The green light flashes rapidly.  

 

 

2.  Pres the Test button corresponding to the desired language: 

  English: Press the Smoke (•) test button 

  Spanish: Press the CO (••) test button 

 

MOUNTING 

After enrolling, verify adequate signal strength with the 

device in its intended mounting location. Adjust the 

device location and orientation as necessary. 
1.  Using two supplied screws and anchors, mount the 

base.  

2.

  Attach the smoke detector to the mounting base 

with a clockwise motion.  

 

 

3.Test each detector as described in the Testing 

section. 

4.  Confirm all desired signals have been received by 

the Central Station. 

NOTE:

 NFPA 72 recommends the installation of 

detectors only after completing construction or any 

other dust producing activity. 

NOTE:

 This device should not be located within 5 ft. 

(1.5 m) of any cooking appliance. 

 