background image

 

ADEMCO 5817CBXT 

Wireless Commercial/Household Transmitter 

 

Installation and Setup Guide 

GENERAL INFORMATION

 

The 5817CBXT is a universal contact-monitoring transmitter that can be 
used with household and commercial fire and burglary-initiating devices 
such  as  door/window  contacts,  motion  and  glassbreak  detectors, 
sprinkler  water  flow  switches,  tamper  switches,  post  indicator  valves, 
manual  pull  stations,  and  remote  duct  detectors.  The  5817CBXT  has 
three unique input loops (zones).  

Loop 1:

  Supervised and typically used for high-priority alarm reporting 

such  as  commercial  fire  or  burglary.  It  requires  a  470K  ohm 
end-of-line resistor (PN EOLR 470K) to be placed across the 
sensor. Short circuit reports as loop 1; open circuit reports as 
loop 4 (tamper). Response time is approx. 320mS. 

Loop 2:

  Built-in, normally closed reed switch (used in conjunction with 

a magnet). 

Loop 3:

  Normally  closed  household  burglary  loop.  Response  time  is 

approx. 320mS. 

Loop 4:

  Tamper  loop  (automatically  enrolled)  contains  two  tamper 

switches. A built-in cover tamper switch is activated when the 
cover is removed. A unit tamper switch is activated if the unit 
is separated from its mounting plate. 

 

ENROLLING

 

 

The 5817CBXT has a built-in serial number that must be enrolled in the 
control panel prior to its usage in the alarm system. Assign loops 1-3 to 
individual zones respectively. Refer to the control panel's installation 
instructions for specific programming procedure.  
When programming the 5817CBXT transmitter, set as Input Type "RF" 
(i.e., supervised RF) (mandatory for UL installations). 

NOTE

: DIP switch 1 must be set to OFF during enrollment. 

MOUNTING 

  Signal strength may vary from location to location. Before mounting 

the transmitter permanently, conduct Go/No Go tests (see control's 
instructions) to verify adequate signal strength from this location.  

  When a satisfactory location is found

,

 remove the battery and 

proceed with installation. 

IMPORTANT:

 

Do  not  mount  the  transmitter  on  or  near  metal 

objects,  as  this  may  affect  transmission  range.  It  is  also  good 
practice  to  avoid  locating  the  transmitter  near  wiring  such  as  AC, 
telephone, HVAC, computer data cables, etc. 

1.  Remove  the  tamper  switch  hold  down  tab  from  the  mounting  plate 

and set it aside. It will be needed if not using the mounting plate. 

2.  Remove  the  transmitter's  cover  using  the  flat  blade  of  a  small 

screwdriver  in  the  pry-off  slot  and  twisting.  To  replace  the  cover, 
engage the hooks along the top edge and snap shut. 

3.  Disengage  the  mounting  plate  from  the  case  back  by  inserting  the 

blade  of  a  small  screwdriver  into  the  mounting  plate  release  hole 
(see Figure 3) and pushing the locking tab out (see Figure 1). Slide 
the mounting plate downward along the case back.  

4.  For Concealed Wiring: Feed the wires through the concealed wiring 

entry  hole  at  the  bottom  corner  of  the  mounting  plate  (and/or  case 
back). 

 

For  Surface  Wiring:  Remove  the  knockout  slot  in  the  case  back 
(near loop 3 terminal block).  

 

Do not connect the wiring to the terminal block(s) yet. 

5. 

If Using the Mounting Plate 

(for easy removal later for servicing): 

 

a. Install the mounting plate in the location determined, with its case-

holding posts pointing up. Use two flat head dry-wall screws. 

NOTE:  

To

 

ensure  proper  operation  of  the  unit's  back  tamper,  the 

screws must be anchored to a wall stud or other solid wood 
material. 

b. 

Attach  the  case  back  to  the  mounting  plate  by  sliding  the 
keyhole  slots  in  the  case  back  down  onto  the  mounting 
plate's  holding  posts.  The  locking  tab  clicks  as  the  case 
back locks in place. 

 

 

If Not Using the Mounting Plate: 

 

a. Make note of the location of the tamper switch hold-down as shown 

in Fig. 1 for the proper placing of the hold-down tab in Fig. 2. 

 

b. Remove  the  PC  board  from  the  case  back.  Slide  a  small  flat 

bladed screwdriver between the case back and PC board near the 
board hold-down clip and carefully pry the board out. 

 

c. In the area that was marked, install the hold-down tab with a 5/8” 

flat  head  dry-wall  screw.  The  tab  must  be  aligned  with  the 
corresponding slot in the case back as shown in Figure 2. The tab 
as well as the case back must be anchored to a wall stud or other 
solid wood material. 

 

d. Mount  the  case  back  to  the  wall  using  two  flat  head  dry-wall 

screws, anchoring it to a wall stud or other solid wood material. 

 

e. Reinstall the PC board into the case back, position the board onto 

the two retaining studs on one side of the case back and snap the 
board  into  place.  The  hold-down  tab  must  mate  with  the 
corresponding cutout in the case back after case back is installed. 

5817CB-004-V0

MOUNTING

PLATE

HOLE

CASE
HOLDING
POSTS

CONCEALED

WIRING

ENTRY

HOLE

MOUNTING
PLATE HOLE

TAMPER

SWITCH

HOLD

DOWN

LOCKING
TAB

HOLD-DOWN
TAB

   

Figure 1.  Mounting Plate

 

5817CB-001-V0

TAMPER SWITCH
HOLD-DOWN TAB

CASE
BACK

CONCEALED

WIRING

ENTRY HOLE

MOUNTING
HOLES (2)

INSTALL

IN LINE

WITH

CUT-OUT

IN CASE

BACK

 

Figure 2.  Case Back

 

6.  Set  the  DIP  switch  (after  the  control  panel  has  enrolled  the 

transmitter  loops)  for  the  desired  primary  loop  characteristics,  as 
described in the Primary Loop Options Table. 

 

Notes

:  

 

  The DIP switch may be set by the installer only. It is not a user 

function. 

 

  Due to FCC regulation 15.231(a)(4), this switch may not be set to 

ON unless loop 1 is used to indicate a type of emergency 
involving fire, security, or safety of life. 

PRIMARY LOOP OPTIONS

 

SWITCH 

SET TO 

DIP SWITCH POSITION 

ON

 

REPEATING TRANSMISSION  (every 4 sec.)  

UPON PRIMARY LOOP 1 FAULT 

Use for high priority alarm, such as fire.

 

OFF

 

SINGLE TRANSMISSION  

PER PRIMARY LOOP CHANGE-OF-STATE

 

Notes:

 

  In  order  for  the  control  panel  to  enroll  the  transmitter,  DIP 

switch 1 

must

 be set to OFF (see Figure 3). 

  the Auxiliary loops are not affected by the DIP switch settings. 

WIRING CONNECTIONS 

Connect  the  loop  wiring  to  the  unit's  terminals  before  installing  the 
battery (see Figure 3).  

NOTES

:  

  Primary  loop  1  is  a  supervised  loop  and  must  have  an  end-of-line 

(EOL) resistor (470K ohms, supplied) placed across the last sensor. 
Additionally, for Primary loop 1, a contact device may not be installed 
more than 20 feet from the transmitter. 

  For  UL  household  burglary  and  fire  installations,  the  loop  3  contact 

device (if used) may not be more than 3 feet from the transmitter. 

 

Reviews: